Manual · Allen-Bradley
Communication Adapter Module (cat. no. 1771-KA2) User's Manual
Manual144 pagesPDF 2.0 MB
User's manual for the Allen-Bradley 1771-KA2 Communication Adapter Module, the Data Highway interface for PLC-2 family processors.
What this file really is
The old site listed this file as a manual for the Allen-Bradley 1771-KA and 1771-KA2. The file is named for the 1771-KA, but the manual is written for the 1771-KA2 Communication Adapter Module and lists the 1771-KA manual as a separate publication.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley user's manual for the 1771-KA2 Communication Adapter Module, which connects PLC-2 family processors (PLC-2, PLC-2/20, PLC-2/30 and the Mini-PLC-2 models) to the Data Highway. It covers the station hardware, switch settings, keying and cable installation, write, bit write and read commands, communication zone rungs, status words, starting and monitoring commands, station interfacing, start-up and troubleshooting, design forms and an error code listing.
Its parts
- Introduction
- Station Hardware
- Module Installation
- Commands
- Communication Zone Rungs
- Status Words
- Command Initiation, Execution, and Monitoring
- Station Interfacing
- Start-up and Troubleshooting
- Design Aids and Documentation
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Allen-Bradley user's manual for the 1771-KA2 communication adapter module, which connects PLC-2 family processors to the Data Highway network. It describes the station hardware, specifications, switch settings, installation and cabling, plus the communication zone rungs, status words, start-up checks and an error code list. The module it covers is the 1771-KA2.
- Module type
- Data Highway station interface for PLC-2 family (Bulletin 1772) processors p. 5
- Compatible processors
- PLC-2 1772-LR; PLC-2/20 1772-LP1, -LP2; PLC-2/30 1772-LP3; Mini-PLC-2 1772-LN1, -LN2, -LN3; Mini-PLC-2/05 1772-LS, LSP; Mini-PLC-2/15 1772-LV p. 5, 6
- Communication rates
- Data Highway 57.6k baud (recommended); programming terminal or second module 9.6k baud; processor 91.2k baud, except PLC-2 1772-LR p. 18
- Connectors
- Three: DATA HIGHWAY (15-pin dropline), PROGRAM INTERFACE, PROCESSOR p. 13, 14
- Power
- +5V DC at 1.2A (max.) from the backplane p. 18, 20
- Network size
- Up to 64 controllers and computers on one Data Highway cable over 10,000 feet (3,048m); droplines 100 feet max p. 5, 6
- Processor cables
- 1771-CN (1.5 ft.), 1771-CO (3.5 ft.), 1771-CR (10.5 ft.); Data Highway cable is user-assembled p. 23
- Programming cable
- Program panel interconnect cable 1772-TC on the PROGRAM INTERFACE connector, 9600 baud p. 15
- Power supplies
- 1771-P1 system supply; 1772-P1 series B or later; 1771-P3, -P4, -P5 modular supplies p. 18, 20
- Chassis
- Bulletin 1771 I/O chassis 1771-A1, -A2, -A4; with PLC-2/20 or PLC-2/30, any slot except the far left p. 19
- Indicators
- Five LEDs: XMTG, RCVG, RDY, red PROG and red PROC p. 15, 16, 17
- Switches
- Three sets: write option (6 switches), station number (SW2, SW3, SW4, octal), Data Highway baud rate p. 25, 26, 29
- Temperature, humidity
- 0 to 60 C (32 to 140 F) operating; -40 to 85 C storage; 5% to 95% humidity without condensation p. 18
- Keying
- Positions 4-6 and 22-24 p. 18
What this manual walks you through
- Planning a Data Highway station and its components p. 11, 12
- Choosing a compatible power supply and checking its series p. 20, 21
- Reading the five LED indicators p. 15, 16, 17
- Setting the write option switches p. 26, 27, 28
- Setting first or second module for a daisy chain p. 28
- Setting the station number switches p. 28, 29
- Testing the receiving station during start-up p. 120
- Looking up rung format and communication error codes p. 139, 140
Good to know
- If the module finds a programming error in the communication zone rungs, PROG stays on and the module cannot function. p. 17
- A disconnected Data Highway cable or a faulted module does not shut down the station processor. p. 19
- Set the switches with a ball-point tip, not a pencil, since lead could jam a switch. p. 26
- From revision D, write option switch 3 becomes the Execute Download in Run Program switch. p. 27
- A Mini-PLC-2/05 station needs a 1771-P3, -P4 or P5 power supply. p. 20
Questions this manual answers
Which cable connects a 1771-KA2 to a PLC-2/30?
The 10.5 ft. Data Highway/processor cable 1771-CR, used with PLC-2, PLC-2/20 or PLC-2/30. The 1771-CN and 1771-CO are for the Mini-PLC-2 family. p. 23
How much power does the 1771-KA2 draw?
It takes +5V DC at 1.2 amperes maximum from the I/O chassis backplane. p. 20
How many stations can a 1771-KA2 talk to?
Through its 15-pin Data Highway connector, one module can communicate with up to 63 other Data Highway stations. p. 14
What does the red PROC light on a 1771-KA2 mean?
An error in data transmission with the processor: a disconnected processor cable, a processor fault, or a wrong processor link rate switch setting. p. 17
Which slot does the 1771-KA2 go in?
With Mini-PLC-2 controllers, any unoccupied I/O slot; with PLC-2/20 or PLC-2/30, any slot except the far left, which takes a PLC-2 I/O adapter or a backplane jumper board. p. 19
The whole text · 15 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 101-10
- Pages 11 to 2011-20
- Pages 21 to 3021-30
- Pages 31 to 4031-40
- Pages 41 to 5041-50
- Pages 51 to 6051-60
- Pages 61 to 7061-70
- Pages 71 to 8071-80
- Pages 81 to 9081-90
- Pages 91 to 10091-100
- Pages 101 to 110101-110
- Pages 111 to 120111-120
- Pages 121 to 130121-130
- Pages 131 to 140131-140
- Pages 141 to 144141-144
The file