Page 11

Chapter

2

Station Hardware

General

The following components make up a Data Highway station with a PLC-2 family PC: Communication Adapter Module Processor PLC-2 I/O adapter module for PLC-2/20 and PLC-2/30 processors Bulletin 1771 I/O chassis Power supply Data Highway/Processor cable Data Highway cable dropline Figure 2.1 shows the configuration of a typical Data Highway station for PLC-2/20 and PLC-2/30 processors. Figure 2.2 shows a typical configuration for the mini-processor module.

Figure 2.1 Typical Station Configuration--PLC-2/20 and PLC-2/30 Processors

Data Highway Cable Trunkline Station

Processor I/O Chassis

Station Dropline 100 feet maximum

Communication Adapter Module (cat. no. 1771-KA2)

Data Highway Processor Cable (cat. no. 1771-CR) 12326

2-1

Page 12

Chapter 2 Station Hardware

Figure 2.2 Typical Station Configuration--Mini-PLC-2, Mini-PLC-2/05, and Mini-PLC-2/15 Controllers

Data Highway Cable Trunkline

Station

Mini-Processor Module (cat. no. 1772-LV, -LS, -LSP; 1772-LN1, -LN2, -LN3)

Station Dropline

System Power Supply Connection for Programming Terminal

Data Highway Processor Cable (cat. no. 1771-CN.-CO)

Communication Adapter Module (cat. no. 1771-KA)

12327

As these figures illustrate, the term “station” combines both the communication adapter module and its connected programmable controller processor. (When specifying only the individual processor or communication adapter module at a station, the terms “station processor” or “station communication adapter module” are used.) The following sections describe the functions and compatibility of each station hardware component. Communication Adapter Module

2-2

A communication adapter module (cat. no. 1772-KA2) provides the interface between all PLC-2 family PCs and other stations on the Data Highway. (Refer to Figure 2.3). The module has sockets for cable

Page 13

Chapter 2 Station Hardware connection, switches for enabling or disabling specific module operations, and indicators to aid in monitoring module behavior and in troubleshooting. Subsequent sections describe each of these parts of the module and other aspects of module hardware that are significant in its set-up and installation. Each communication adapter module in a Data Highway installation must have a unique station number. This station number is used to address commands to the module from other stations.

Figure 2.3 Communication Adapter Module (cat. no. 1771-KA2)

(Side view)

Indicator

Connectors

10862-I

Switch Cover

Connectors The front of a 1772-KA2 module has 3 cable connectors labeled: DATA HIGHWAY PROGRAM INTERFACE PROCESSOR See Figure 2.4. 2-3

Page 14

Chapter 2 Station Hardware

Figure 2.4 Module Connection Summary

Data Highway Cable (User-Assembled)

Program Panel Interconnect Cable (Cat. no. 1772-TC) “Program Panel” or “Interface” Socket on Processor

Data Highway Processor Cable (cat.no. 1771-CN, -CO, -CR)

Industrial Terminal System (cat. no. 1770-T1 and T2) 10863-I

Data Highway Connector The upper connector of the module accepts the 15-pin Data Highway dropline cable. Through this connection, a single KA2 module can communicate with as many as 63 other Data Highway stations. Module transmitting and receiving circuitry on this channel are transformer-coupled to the Data Highway link. This design permits differential transmission of data with high common-mode noise immunity. Electrically, transformer coupling provides isolation between module logic circuitry and the Data Highway cable. Program Interface Connector The middle outlet on the module connects to an industrial terminal system (cat. no. 1770-T1, -T3), or to a second KA2, or to a 1771-KG series B module. 2-4

Page 15

Chapter 2 Station Hardware

To connect any programming terminal to the PROGRAM INTERFACE connector, use a program panel interconnect cable (cat. no. 1772-TC). With a 1772-KA2 module installed, the PROGRAM INTERFACE connector substitutes for the PROGRAM PANEL connector on PLC-2/20 or PLC-2/30 processors or the INTERFACE socket on the Mini-PLC-2, Mini-PLC-2/05, or Mini-PLC-2/15. This means that all interaction between the processor and the programming terminal is controlled through the communication adapter module. This interaction includes program entry and any functions that involve peripheral devices except cassette loads--including report generation, contact histograms, and generation of program copies on paper or on punched tape. The communication rate over this channel is 9600 baud. Optical-electrical isolation is provided between receiving circuitry on this channel and module logic circuitry. NOTE: The PROGRAM INTERFACE connector need not connect to a programming terminal for the module to operate. This connector serves as a programming terminal connection whenever such a device is needed for program entry, editing or monitoring. Processor Connector The lower connector of the module connects to the station PLC-2/20 or PLC-2/30 processor, or Mini-processor module. (Refer to Figure 2.1 and Figure 2.2) A Data Highway/Processor cable, described in section titled “Cables,” is used for this connection. Indicators There are 5 LED indicators on the front of the module, as seen in Figure 2.5. These indicators are useful for monitoring module activity and for troubleshooting. Three green indicators show module status during normal receiving and transmitting of messages. Two red indicators show the status of module diagnostics.

2-5

Page 16

Chapter 2 Station Hardware

Figure 2.5 Module Indicators

COMM ADAPTER Transmitting Receiving Message Ready Program Status Processor Link Status

XMTG RCVG RDY PROG PROC

XMTG The green transmitting indicator turns on when the module is current master of the Data Highway. When this indicator is on, therefore, the communication adapter module is transmitting messages on the Data Highway communication link, or it is polling. RCVG The receiving indicator turns on when the module is receiving a message addressed to it. Otherwise, RCVG is off. When both the RCVG and XMTG indicators are on, the module is current master of the Data Highway and is polling. (The section titled “Polling,” in chapter 8, describes polling procedure.) RDY The green message ready indicator turns on when the module has messages ready to transmit. With this indicator on, the module is ready to assume mastership when it is polled.

2-6

Page 17

Chapter 2 Station Hardware

PROG The red program status indicator tells you the status of module checks on the communication zone rungs of the user program. (The section titled “Overall Format,” chapter 5, describes these rungs.) The module first checks these rungs at power-up. When it locates the header rung of this zone, the module turns the PROG indicator on. After it checks the rungs, provided no errors are found, the module turns the PROG indicator OFF. However, if the module detects any programming error in the communication zone of the program, this indicator remains ON. In this event, the module cannot function. You must check the communication zone of the program and correct any errors. (Start-up procedures are described in chapter 9.) PROC The red processor link status indicator gives the status of error-checking diagnostics for communication adapter/processor communication. The PROC indicator is normally off. Should the 1771-KA2 module detect an error in data transmission with the processor, it turns the PROC indicator on. This may mean one of the following: Disconnection of the Data Highway/Processor cable between the communication adapter and the processor Fault in processor operation Incorrect selection of processor link communication rate on the module (Refer to section titled “Write Option Switch Assembly,” chapter 3). The section titled “Module Indicators,” in chapter 9, describes the use of indicators in troubleshooting. Switches There are 3 sets of switches on the 1771-KA2 module circuit board. These switches are beneath the small switch cover plate on the component-side cover of the module. (Refer to Figure 2.3). The programmer selects the settings of these switches for each communication adapter module, based upon such variables as station number, command capabilities, and type of station processor. Switch settings are a part of module installation, described in chapter 3. 2-7

Page 18

Chapter 2 Station Hardware

Module Specification Summary Table 2.A lists operating specifications for a 1771-KA2 module.

Table 2.A Operating Specifications Function • Interface entire PLC-2 family programmable controller to the Data Highway

Compatible Power Supplies • System power supply (cat. no. 1771-P1) •

Auxiliary power supply (cat. no. 1772-P2)

Location • Bulletin 1771 I/O Chassis (any slot except furthest left)

•

System power supply module (cat. no. 1772-P1, series B or later)

Communication Channels • To Data Highway

•

Auxiliary power supply (cat. no. 1772-P2 series B or later)

•

To programming terminal or second module in daisy chain

•

Power supply module 1771-P3

•

•

Power supply module 1771-P4

To processor or first module in daisy chain

•

Power supply module 1771-P5

Communication Rates • To Data Highway: 57.6k baud (Recommended)

Ambient Temperature Rating • 32o to 140oF (0o to 60oC) (operational) • -40o to 185oF (-40o - 85oC) (storage)

•

To programming terminal or second module: 9.6k buad

Humidity Rating • 5% to 95% (without condensation)

•

To processor: 91.2k baud for processor (except PLC-2, cat. no. 1772-LR); 9.6k baud for first communication module or PLC-2family processor.

Keying • Module slotted for I/O chassis keying band positioning. •

Positions 4-6, 22-24

Power Supply Requirement • +5V DC at 1.2A (max.)

Processor

This manual uses the term “processor” as a general term for any of the PLC-2 family processors. Individual processors are specified only when some distinction must be made. The normal operating sequence of the station processor is not changed by a communication adapter module, that is, the processor carries out its scan of input and output modules and execution of the user program as though the communication adapter module weren’t there.

2-8

Page 19

Chapter 2 Station Hardware

The interaction between a KA2 module and its station processor occurs in memory control. The station KA2 can read data from and write data into processor memory, based on various user-programmed commands. Commands that originate at a station communication adapter module can control only data table areas of processor memory. Commands generated by a computer that is connected to the Data Highway through a communication controller module (cat. no. 1771-KE/KF) can control both data table and user program memory areas. Note that the processor continues to execute the user program and to control output devices, whether or not the station communication adapter module is in operation. Thus, disconnection of the Data Highway cable or faulted operation of the communication adapter module does not cause shutdown of the station processor. I/O Chassis

A-B designed the 1771-KA2 module to fit in a Bulletin 1771 I/O chassis assembly (cat. no. 1771-A1,-A2,-A4). This chassis houses Mini-PLC-2, Mini-PLC-2/05 and Mini-PLC-2/15 programmable controllers. With one of these controllers, you can use any unoccupied I/O slot for communication adapter modules. With PLC-2/20 and PLC-2/30 programmable controllers, use a Bulletin 1771 I/O chassis as an I/O rack. In this case, the 1771-KA2 module can be installed in any chassis slot except the one furthest left. This left-most slot must be occupied by a PLC-2 I/O adapter module (cat. no. 1771-AL or 1771-AS), shown in Figure 2.6, or a backplane jumper board assembly (cat. no. 1771-EY). A Bulletin 1771 I/O chassis is usually mounted within an enclosure. We recommend proper grounding of this enclosure because it minimizes the effect of noise from the surrounding industrial environment. (Grounding procedures for the Bulletin 1771 I/O chassis are described in publication 1772-6.6.3).

2-9

Page 20

Chapter 2 Station Hardware

Figure 2.6 1771-AL Adapter Module

PLC-2 I/O ADAPTER

10864-I

Power Supply

A 1771-KA2 module gets its power from the backplane. It requires +5V DC at 1.2 amperes (max.). The following power supplies are compatible: System power supply (cat. no. 1771-P1) Auxiliary power supply (cat. no. 1771-P2) PLC-2 system power supply module (cat. no. 1772-P1, series B or later) PLC-2 auxiliary power supply (cat. no. 1777-P2, and 1777-P4 series B or later) Modular power supplies (cat. no. 1771-P3, -P4, -P5) You must connect one of these supplies to the I/O chassis that contains the KA2 communication adapter module. In a Mini-PLC-2, or a Mini-PLC-2/15 this is the system power supply, shown in Figure 2.7. In a Mini-PLC-2/05, you must use a 1771-P3, -P4, or P5 power supply.

2-10