Communication Adapter Module (cat. no. 1771-KA2) User's Manual, pages 21 to 30

Pages 21 to 30 of 144

The original document is the PDF (2.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-KA2

Page 21

Chapter 2 Station Hardware

Figure 2.7 1771-P1 System Power Supply

Battery Low DC ON

ALLEN-BRADLEY

10865-I

When using the PLC-2/20 or PLC-2/30 processor, any of these supplies can power the I/O chassis so long as core memory is not being used. (Refer to processor manuals.) An auxiliary power supply (cat. no. 1771-P2) closely resembles the system power supply shown in Figure 2.7. PLC-2 power supply module (cat. no. 1772-P1) is not a separate unit, but is enclosed within the metal chassis of the PLC-2/20 or PLC-2/30 processor. PLC-2 power supplies must be series B or later for communication adapter module compatibility. On both of these supplies, a label on the front edge of the circuit board identifies the series level. To locate this label, remove AC power from the supply and remove the metal front plate that covers the module. If the label shows the catalog number but not the series level, the module is series A. Otherwise, series B or later is indicated.

2-11

Page 22

Chapter 2 Station Hardware

Figure 2.8 PLC-2 Power Supplies

PLC 2/30

AC FUSE

10236-I a. PLC-2 System Power Supply Module

AC FUSE

10236a-I b. PLC-2 Auxiliary Power Supply

2-12

Page 23

Chapter 2 Station Hardware

Cables

A 1771-KA2 module requires the following cables for installation: Data Highway/Processor cable (cat. no. 1771-CN,-CO,-CR) User-assembled Data Highway cable Figure 2.1 and Figure 2.2 show the connections made with these cables. You can order Data Highway/Processor cables in 3 lengths: 1.5 ft. (cat. no. 1771-CN) 3.5 ft. (cat. no. 1771-CO) 10.5 ft. (cat. no. 1771-CR) The 2 shorter cables are intended for connection to a Mini-PLC-2, Mini-PLC-2/05, or Mini-PLC-2/15 module. A 10.5 ft. cable is used with PLC-2, PLC-2/20 or PLC-2/30 processors. You must assemble and install your own Data Highway cable, dropline and trunkline segments. A separate publication, Data Highway Cable, Assembly and Installation Manual, publication 1770-6.2.1, gives information on layout, make-up, and installation of the cable.

Other Optional Equipment

In addition to the components shown in Figure 2.1 and Figure 2.2, you can install your own equipment at or near the Data Highway station. The chief purpose of additional components is to provide diagnostic or monitoring information. Such devices as alarms, displays and indicators can be controlled from output modules of the programmable controller to provide operating or fault information to plant personnel. Minimally, a single indicator should be installed to alert your personnel to a REMOTE or LOCAL FAULT condition that prevents normal message transfer. The significance of REMOTE/LOCAL FAULT bits, and the recommended programming to monitor these bits, is described in chapter 7.

Chapter Summary

This chapter told you the: Components of an A-B Data Highway system Role of a 1771-KA2, its connectors, switches, and indicators Specs of a 1771-KA2 Where a KA2 resides and how it is connected to its station Optional equipment possibilities at a Data Highway station In chapter 3 you will read about KA2 switches and installation. 2-13

Page 24

Chapter 2 Station Hardware

2-14

Page 25

Chapter

3

Module Installation

General

This chapter outlines procedures for preparation, installation, and connection of a 1771–KA2 module. Before performing these procedures, you should check component compatibility and the station set–up recommendations in chapter 2.

Switch Settings

There are 3 sets of switches on a 1771–KA2 circuit board: Write option switch assembly Station no. switch group Data Highway baud rate switch assembly Refer to Figure 3.1. The switches at each station communication adapter module must be set as the programmer specifies. To access these switches, loosen the two screws that hold the small cover plate to the side of the module. Then, rotate this cover plate to expose the switches.

Figure 3.1 Module Switches

Write Option Switch Assembly

O1 2 3 4 5 6 N

O1 2 N

O1 2 3 N

O1 2 3 N

O1 2 N

O F F

O F F

O F F

O F F

O F F

Station Number Switch Group

Data Highway Baud Rate Switch Assembly

12329

3-1

Page 26

Chapter 3 Module Installation

Use the tip of a ball–point or other pointed instrument to set these switches. Do not use a pencil, as lead could jam the switch. For troubleshooting purposes, we recommend that the programmer document the required switch settings for each 1771–KA2. Use form 5030, in chapter 10, to record switch settings for the module at each station. That way, should replacement of the module be required, switches on the replacements can be set quickly. Write Option Switch Assembly The first rocker switch assembly from the left is the write option switch assembly. (Refer to Figure 3.2). In this assembly, switches numbered 1 through 5 enable or disable different types of write and bit write commands from being received by, or sent from, the communication adapter module. (Note that the unprotected read command is not affected by any of these switch settings.) Switch no. 6 enables and disables daisy chain operation. See FIRST/SECOND MODULE at end of this section.

Figure 3.2 Write Option Switch Assembly Shutdown / Auto Restart* • On–Shutdown • Off–Auto Restart

Execute Unprotected Write Commands

Received Priviledged Write

Receive Protected Commands O 1 N O F F Send Unprotected Commands

2

3

4

5

6

Enable/Disable • On–First Module • Off–Second Module

* After revision D, the name and function of switch 3 changed to ”Execute download in RUN program.”

12330

The following paragraphs describe settings for these switches. RECEIVE PROTECTED COMMAND SWITCH Switch no. 1 of the write options switch assembly determines whether the module is enabled to receive and execute protected write and bit write commands from other stations. Set this switch as follows: 3-2

Page 27

Chapter 3 Module Installation

ON – Enables execution of received protected commands. OFF – Disables received protected commands. Note that both an ON setting of this switch and a memory access rung are required to allow execution of received protected commands. (Memory Access rungs are described in chapter 5.) This switch does not prevent the module from receiving and executing unprotected commands from another station. (A separate switch, described subsequently, enables or disables execution of received unprotected commands.) EXECUTE UNPROTECTED WRITE COMMANDS SWITCH Switch 2 determines whether the module can receive and execute unprotected write and bit write commands from other stations. Set this switch as follows: ON – Enables received unprotected write and bit write commands to be executed. OFF – Disables the module from executing received unprotected write and bit write commands Note that this switch does not disable unprotected read commands from being received and executed by the module. SHUTDOWN/AUTOMATIC RESTART SWITCH On modules before revision D, switch 3 presents the option, after a hard error, of restarting the 1771–KA2, or shutting it down. ON – Shuts down the module OFF – Automatically restarts itself When a hard error occurs it normally indicates fairly severe communication problems that should be corrected before starting. Such errors usually involve bad cabling or noise. REVISION D The third switch in the Write Option Switch assembly on the 1771–KA2 module (formerly the Shutdown/Automatic Restart Switch) will change function for revision D and become the Execute Download in Run Program switch. 3-3

Page 28

Chapter 3 Module Installation

RECEIVE PRIVILEGED WRITE SWITCH Switch 4 determines whether the module can execute received privileged write commands. These commands can be issued only from a computer connected through a communication controller module (cat. no. 1771–KE/KF). These commands give the computer the capability to alter the user program memory of the station processor. Set this switch as follows: ON – Enables a 1771–KA2 to execute received privileged write commands OFF – Disables the 1771–KA2 from executing received privileged write commands. SEND UNPROTECTED COMMANDS SWITCH Switch 5 determines whether the module can send unprotected write or bit write commands to another station. Set this switch as follows: ON – Enables the module to send unprotected write and bit write commands OFF – Disables the module from sending unprotected write and bit write commands This switch does not prevent unprotected read commands from being sent by a communication adapter module. FIRST/SECOND MODULE Use switch 6 for first/second module selection. Set switch: ON – Use this setting when connected directly to any compatible processor except PLC–2 (1772–LR). OFF – Use this setting when the KA2 module is connected to a PLC–2 (1772–LR), a 1771–KG series B module, or another KA2 module. Station No. Switch Group You must designate a unique station number for each communication adapter module on a Data Highway. This designation is made by the programmer and switch–selected on the station number switch group of the module. 3-4

Page 29

Chapter 3 Module Installation

The station number switch group comprises 3 switch assemblies (SW2, SW3, SW4) on the module circuit board, as Figure 3.3 indicates. These switches determine the station number of each communication adapter module. The station number is a 3–digit octal number from 0108–0778 or 1108–3768. Each of the 3 switch assemblies in this group is set to represent an individual digit of this station number. Figure 3.3 shows the combination of switch settings for each digit.

Figure 3.3 Station Number Switch Settings

O 1 N

O 1 N

2

3

O 1 N

O F F

O F F

O F F

SW2

SW3

SW4

SWITCH SETTING

2

3 ON OFF

SWITCH SETTING

DIGIT

ON

ON OFF

No. 2

No. 3

0

OFF

OFF

OFF

0

1

OFF

OFF

ON

1

OFF

2

OFF

ON

OFF

2

ON

3

No. 2

OFF

OFF

OFF

ON

ON ON

OFF

DIGIT

No. 1

No. 1 a. First Digit

2

OFF

ON

ON

3

ON

OFF

OFF

4

ON

OFF

ON

5

ON

ON

OFF

6

ON

ON

ON

7 12331 b. Second and Third Digits

3-5

Page 30

Chapter 3 Module Installation

In this binary–coded octal numbering arrangement, each switch has an associated binary value: 1, 2, or 4 if set ON, 0 if set OFF. The value of each individual digit of the station number is the sum of the binary values in its corresponding switch assembly. Table 3.A gives an example for the settings of this switch group.

Table 3.A Switch Setting Example: Station No. 037 STATION NO. DIGITS

0

3

7

SWITCH NO.

1

2

1

2

3

1

2

3

SWITCH SETTING

OFF

OFF

OFF

ON

ON

ON

ON

ON

Note that the switches allow a range of station numbers from 0008 to 3778 (256 possible numbers). However, there are practical reasons for using the the range 0108 –0778 and 1108 –3768. These station numbers are addressable from any station using an industrial terminal. PLC–2 family programmable controllers cannot address 0008 to 0078 or 1008 to 1078. Also, station 3778 is an illegal address on the Data Highway. To optimize response times, use consecutive station numbers beginning with 0108. Data Highway Baud Rate Switch Assembly The switch assembly labeled SW5 on the module circuit board is the data highway baud rate switch assembly. (Refer to Figure 3.4). The switches in this assembly must be set for the baud rate being used on the Data Highway communication link.

Figure 3.4 Data Highway Baud Rate Switch Assembly

O 1 N O F F

3-6

2 Both switches ON for 57.6K Baud Rate