The text of a manual · part 5 of 23
Bulletin 1771 Communication Controller Module (Cat. Nos. 1771-KE, -KF) User's Manual, pages 41 to 50
Pages 41 to 50 of 228
The original document is the PDF (9.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-KE
Page 41
Page 3-7
Installation Switch Assembly SW-2 SW-3 SW-4 ~ . ON || ON ‘a i” “~ rn of 2) Gl23) pl23 N N N OFF f 7 L J \ in - OFF |} OFF If you want Set switches If you want Set switches t t thi to set thi Paigit | No.1 No. 2 digit: | No.1 No. 2 No. 3 0 OFF OFF 0 OFF OFF OFF 1 OFF ON 1 OFF OFF ON 2 ON OFF 2 OFF ON OFF 3 ON ON 3 OFF ON ON 4 ON OFF OFF First Digit 5 ON OFF ON 6 ON ON OFF 7 ON ON ON Second and Third Digits Switch Setting Example: Station No. 037 Switch Assembly SW-2 SW-3 Sw-4 Station No. Digits 0 ‘ 3 7 Switch No. 1 2 1 2 3 1 2 3 Switch Setting OFF | OFF] OFF] ON ON | ON [| ON | ON 11692
Figure 3.4, Station Number
Page 42
Page 3-8 Installation
This section for the revision H module only
What to do next
3.1.3 Station Number
Switch 3 determines whether the module uses and recognizes the following handshaking signals, data set ready, request to send, clear to send, data carrier detect, and data terminal ready.
If you want the module’s RS-232-C port to: set switch 3: Use handshaking signals on Ignore handshaking signals off
Switch 4 determines whether or not the RS-232-C port of the KE/KF module can detect duplicate messages transmitted to it.
If you want your module to: set switch 4: detect and ignore duplicate messages on accept all messages regardless of duplication off
Now go to section 3.1.3 to learn about station numbers.
Switch groups SW-2, SW-3, and SW-4 are for setting the station number of the KE/KF module. The station number is an encoded 3-digit octal number that identifies the KE/KF module as a unique station on the Data Highway. Valid station numbers for the KE/KF module are 010 to 077 and 110 to 376 octal.
Figure 3.4 shows an example of how to set the KE/KF station number to 037 octal. The switches in group SW-2 set the first (left-most) digit of the station number, switch group SW-3 sets the middle digit, and switch group SW-4 sets the last (right-most) digit.
Station numbers play an important part in the polling scheme described in chapter 2. They can also influence the order in which mastership is transferred between Data Highway stations. Therefore, we recommend that you always begin numbering stations with the lowest possible number and continue with the next available number in sequence.
Page 43
Page 3-9 Installation
3.1.4 Switch assembly SW-5 lets you select the communication rate Data Highway Communication for the KE/KF module’s Data Highway port.
Rate NOTE: Set both switches ON for a communication rate on the
Data Highway of 57,600 bits per second. Be sure to set all Data Highway modules for this communication rate.
Switch assembly SW-5 a Va 012 N Both switches ON f orn switches or 0 “ - 57,600 bits per second F Laas
3.1.5 Switch assembly SW-6 lets you select the communication rate, RS-232-C Communication _ parity, and diagnostic commands for the KE/KF module’s Rate, Parity, and Diagnostic RS-232-C port. Commands
Switch assembly SW-6 qi 23 4
N
0
F
F
L Parity (revision A-G module) Diagnostic commands (revision H module)
Communication rate
Page 44
Page 3-10 Installation
Communication Rate
You set the communication rate switches the same for both the revisions A-G and H modules.
Bits per Set switch: second as: 1 2 3 110 OFF] OFF! OFF 300 ON | OFF | OFF 600 OFF] ON | OFF 1200 ON | ON | OFF
2400 OFF | OFF] ON
4800 ON | OFF} ON
9600 OFF] ON |] ON
19200 ON | ON] ON
NOTE: Any switch settings not shown above will give a communication rate of 9,600 bits per second.
Parity You can set parity switches only if you have revision A-G module. If you want your module to: set swlich 4: execute diagnostic commands on pass through diagnostic commands off
Diagnostic Commands
You can set diagnostic command switches only if you have revision H module.
If you want your module to have: set switch 4:
even parity on no parity off
Page 45
Page 3-11 Installation
3.1.6 Replacing a 1771-KC/KD Module with a KE/KF Module
If you have revision A-G module:
By setting the switches properly on the KE/KF module, you can use it to replace an older 1771-KC/KD module in an existing application without having to make any changes in your application programs.
In Set Switch Switch Assembly: | Number: Setting SW-1 1 off
2 Same setting as 1771-KC/KD switch (assembly SW-1, switch 1)
3 off off
Same setting as 1771-KC/KD switch (assembly SW-1, switch 5)
SW-2 1,2 Same setting as 1771-KC/KD switches (assembly SW-2, switches 1 and 2)
SW-3 1,2,3 Same setting as 1771-KC/KD switches (assembly SW-3, switches 1, 2, and 3)
SW-4 1,2,3 Same setting as 1771-KC/KD switches (assembly SW-4, switches 1, 2, and 3)
SW-5 1,2 Same setting as 1771-KC/KD switches (assembly
SW-5, switches 1 and 2)
sw-6 ll 1,2,3 | Samesetting as 1771-KC/KD switches (assembly SW-6, switches 1, 2, and 3)
4 off
NOTE: The RS-232-C port of the KE/KF module can communicate at a maximum rate of 19,200 bits per second. If your 1771-KC/KD module was set to communicate at a higher rate, then you might have to make some modifications to your RS-232-C link before installing the replacement KE/KF module.
Page 46
Page 3-12 Installation
If you have revision H module:
3.2 Mounting
3.2.1 1771-KE Module
In Set Switch Switch Assembly: | Number: Setting SW-1 1 off 2 Same setting as 1771-KC/KD switch (assembly SW-1, switch 1) 3 off off off SW-2 1,2 Same setting as 1771-KC/KD switches (assembly SW-2, switches 1 and 2) SW-3 1,2,3 Same setting as 1771-KC/KD switches (assembly SW-3, switches 1, 2, and 3) SW-4 1,2,3 Same setting as 1771-KC/KD switches (assembly SW-4, switches 1, 2, and 3) SW-5 1,2 Same setting as 1771-KC/KD switches (assembly SW-5, switches 1 and 2) SW-6 a 1,2,3 Same setting as 1771-KC/KD switches (assembly SW-6, switches 1, 2, and 3) 4 same setting as 1771-KC/KD switches (assembly SW-1 switch 5)
EENOTE: The RS-232-C port of the KE/KF module can communicate at a maximum rate of 19,200 bits per second. If your 1771-KC/KD module was set to communicate at a higher rate, then you might have to make some modifications to your RS-232-C link before installing the replacement KE/KF module.
The 1771-KE module differs from the 1771-KF in the way it is mounted. The 1771-KE module mounts in an Allen-Bradley Bulletin 1771 I/O rack, while the 1771-KF module is designed for stand-alone mounting.
In both cases, you must mount the KE/KF module within 100 cable feet of the Data Highway trunkline. If you are connecting the module directly to an RS-232-C device, you must also mount the module within 50 cable feet of that device. If the RS-232-C device is another Allen-Bradley communication module, you can mount the KE/KF module up to 7,000 away from it by using the longline connection (section 3.4). If you are using a modem link to connect the KE/KF module to the RS-232-C device, then the module and the device may be as far apart as the modem link will allow.
To install a 1771-KE module in an Allen-Bradley Bulletin 1771 I/O rack, follow these steps:
Step 1, Turn off all power to the I/O rack and to its controlling PC processor.
Step 2, Carefully slide the module into one of the slots in the I/O rack.
Step 3, Secure the module in the I/O rack by snapping down the latch on the top of the slot that contains the module.
Step 4, Turn on the power to the PC processor and I/O rack.
Page 47
Page 3-13 Installation
3.2.2 The 1771-KE module is keyed Keying to guard against installation in the wrong module slot. To implement this protection, insert keying bands supplied with your I/O chassis into
\
Keying Positions
You can change the positions of keying bands if subsequent system design requires the insertion of a different type of module in this slot.
WARNING: Remove system power before removing or installing your module in the 1771 I/O chassis. Failure to observe this warning could result in damage to module circuitry and/or undesired operation with possible injury to personnel.
Page 48
Page 3-14 Installation
3.2.3 1771-KF Module
3.3 Power Supply
The rear edge of the 1771-KF module contains a mounting bracket that allows you to mount the module almost anywhere. Figure 3.5 gives the mounting dimensions for the module. To protect the module from harmful environmental effects, enclose it in a standard industrial enclosure (NEMA type 12, or similar).
The KE/KF module requires +5V DC power for operation. The 1771-KE module obtains this power from the 1771 I/O rack in which it is mounted. The 1771-KF module needs an independent power suppy.
To provide power to a 1771-KF module, use an Allen-Bradley power supply (cat. no. 1771-P2) or equivalent. The power supply connects to a terminal strip at the bottom of the module (figure 3.6). Use an Allen-Bradley power cable (cat. no. 1770-CF) to make this connection.
Before connecting the 1771-KF module to its power supply, determine whether the supply issues a signal to indicate that its output power is enabled. Some power supplies issue a low-true enable signal, some issue a high-true signal, and
10.5”
@
' 18.75" ft yy] vt |
0.625”
10268
Figure 3.5, Mounting Dimensions for 1771-KF Module
Page 49
Page 3-15 Installation others issue no enable signal. The 1771-KF module contains a set of switches that can be set to accept either of these cases. The switches are set incorrectly if all 5 LEDs, come on. To set these switches, do the following:
Step 1, Lay the module down so that the white identification label is face down and the front edge of the module is to your right.
Step 2, Remove the screws from the corners of the metal cover plate (Figure 3.7).
oatA IGHWAY iW a! ime Terminal Barrier ras Strip
Cai we: oe is A
-, KA ai Se
\ \ OV DC Enable +5V DC Earth
Signal Ground
11694
Figure 3.6, Power Supply Connections for 1771-KF Module
Page 50
Page 3-16 Installation
Remove screws
Enabie signal switches
Remove screws
Enable signal switch settings
Lo True Hi True
(Shaded side is setting)
41695
Figure 3.7, Enable Signal Switches for 1771-KF Module
Step 3, Carefully remove the metal cover plate from the module.
Step 4, Locate the enable signal switches on the module circuit board. These switches are situated on the right side of the circuit board, between the indicator lights and the DATA HIGHWAY connector (figure 3.7).
Step 5, Set the switches for the type of enable signal issued by the power supply. Figure 3.7 shows the settings. Low-true