Page 55

54

1771 Digital I/O AC Input and Output Modules

Protected AC Output Module (Cat. No. 1771-OP) Specifications (Cat. No. 1771-OP)

Status Indicators

Outputs per Module

4

Module Location

1771 I/O chassis

Output Voltage Range

92 to 138V ac @ 47 - 63Hz

Output Current Rating (maximum)

2A per output

Surge Current (maximum) per Output and Module

20A for 60ms, repeatable every 2 seconds

Load Current (minimum)

80mA per output @ 120V ac, 60Hz

On-State Voltage Drop (max.)

2V ac at 100mA

Off-State Leakage Current (max.)

6mA per output @ 120V ac

Signal Delay

1.0ms 8.3ms at 60Hz

Power Dissipation

13.9 Watts (max.), 1.8 Watts (min.)

Thermal Dissipation

47.2 BTU/hr (max.), 6.1 BTU/hr (min.)

Backplane Current

350mA @ 5V dc + 5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% without condensation 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Category Keying

Between 6 and 8 Between 26 and 28

Fuses

0.5A Bussmann GLD1/2 5A Bussmann 250V Normal Littelfuse 312005 5A

Field Wiring Arm Wiring Arm Screw Torque

Sample Connection Diagram Driving a 1771-IA Module with a 1771-OP Module Protected AC (120V) Output Module Cat. No. 1771-OP

AC (120V) Input Module Cat. No. 1771-IA L1

A ac High

A

O

O

1

1

2

2

3

3

4

4

5

5

Catalog Number 1771-WA

6

7-9 inch-pounds

7

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 1

Note: The Triac Fail indicator illuminates when one of the output triacs has shorted and caused the output fuse to open. If the light is on,the module should be returned to Allen-Bradley for repair.

11893-I

Off to On On to Off

Agency Certification (when product or packaging is marked)

Triac Fail Fuse Blown Output 0 Output 1 Output 2 Output 3 Not used Not used Not used not to exceed 6A per module

B

2.5K Ohm 10 Watt

6 L2 ac low

7 B

1771-2.23

You use this conductor-category information for planning conductor routing as described in the system-level installation manual. 11892-I

Publication 1771-2.182 - July 1996

Page 56

1771 Digital I/O AC Input and Output Modules

55

Isolated AC Output Module (Cat. No. 1771-OR Series B)

Simplified Schematic +5V

1.2k

Output Status Indicator

LED

Backplane Circuitry

Opto Isolation

470K

Indication (fuse blown)

470K

100 Rect & Filter Circuit

L1 5.0 Amp Fuse

0.047µF 22

MOV 100 Output 18497

Application Notes Device Compatibility. An output from this module can drive an Allen- Bradley size 5 motor starter provided its supply voltage does not drop below 184V ac. Minimum/ Maximum Load Current. The maximum load current the module can handle is 2A per output not to exceed 6A per module. The triac needs a minimum load current of 60mA to stay on. Connection to Input Modules. You can use an isolated ac (220V) output module (cat. no.1771-OR) to directly drive terminals on an ac input module (cat. no. 1771-IM or -IMD). However, you must connect a 3.3K ohm, 20W resistor between the output terminal and L2 (common). Status Indicators. The front panel has 12 status indicators. The top six indicators show the state of each output and are driven by the logic circuitry on the controller side of the module. An indicator lights when the corresponding output is energized. The bottom six indicators indicate a fuse-blown condition at the respective output.

Connection Diagram

Output 0A

1

Output 0B

2

Output 1A

3

Output 1B

4

Output 2A

5

Output 2B

6

Output 3A

7

Output 3B

L1 ac high

220V ac Supply

L2 ac low

Output Device

8

Output 4A

9

Output 4B

10

Output 5A

11

Output 5B

12

(Actual wiring runs in this direction.)

11382-I

Publication 1771-2.182 - July 1996

Page 57

56

1771 Digital I/O AC Input and Output Modules

Isolated AC Output Module (Cat. No. 1771-OR Series B) Specifications (Cat. No. 1771-OR/B) Outputs per Module

6

Module Location

1771 I/O chassis

Nominal Output Voltage

220V ac, 50/60Hz

Output Voltage Range

184 to 276V ac @ 47 - 63Hz

Output Current Rating

2A per output - not to exceed 6A per module

Surge Current (maximum) per Output and Module

15A for 100ms, repeatable every 2 seconds

Load Current (minimum)

2V at 100mA

On-state Leakage Current (max.)

10mA per output @ 276V ac

Off to On On to Off

13.2 Watts (max.), 1.2 Watts (min.)

Thermal Dissipation

45.1 BTU/hr (max.), 4.1 BTU/hr (min.)

Backplane Current

255mA @ 5V dc + 5%

Isolation Voltage

Isolation meets or exceeds UL Standard 508, and CSA Standard C22.2 No. 142.

Conductors

Wire Size Category

Keying

Fuse

Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions 1

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

12216-I

Sample Connection Diagram Driving a 1771-IM Module with a 1771-OR Module (220V) ac input module Cat. No. 1771-IM

Isolated (220V) ac output module Cat. No. 1771-OR L1 ac high

220V ac Supply

L2 ac low

Output 0A

1

Output 0B

2

A

Output 1A

3

O

Output 1B

4

1

5A, 250V 3AG Normal Blow (1 per output) Littelfuse 312005 Bussman Fuse AGC-5

Output 2A

5

2

Output 2B

6

3

Output 3A

7

4

Catalog Number 1771-WD

Output 3B

8

Output 4A

9

Between 4 and 6 Between 30 and 32 Between 34 and 36

7-9 inch-pounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Output 4B 10 Output 5A 11

3.3K Ohms 20 Watt Resistor

5 6 7 B

Output 5B 12

1771-2.40

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.182 - July 1996

Fuse Blown Indicators (clear)

1.0ms 8.3ms @ 60Hz

Power Dissipation

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

Output Status Indicators (red)

60mA per output @ 220V ac, 60Hz

On-state Voltage Drop (max.) Signal Delay

Status Indicators

11389

Page 58

1771 Digital I/O AC Input and Output Modules

57

Notes

Publication 1771-2.182 - July 1996

Page 59

58

1771 Digital I/O AC Input and Output Modules

Notes

Publication 1771-2.182 - July 1996

Page 60

Support Services

Support Services

59

At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:

Technical Support • • • •

SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services

Engineering and Field Services • • • • application engineering assistance integration and start-up assistance field service maintenance support

Technical Training • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis

Repair and Exchange Services • • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support

Publication 1771-2.182 - July 1996

Page 61

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 1771-2.182 - July 1996 Supersedes Publication 1771-2.182 - March 1994