Page 1
Installation Instructions dc (10…60V) Output Module
Catalog Number 1771-OBD Series C
Topic
Page
About This Publication
1
Important User Information
2
Before You Begin
4
Key the Backplane
5
Install the Module
6
Interpreting the LED Indicators
11
Replace the Fuse
12
Hazardous Location Approvals
13
Specifications
15
About This Publication Use this document as a guide when installing the 1771-OBD series C output module.
Publication 1771-IN054C-EN-P - November 2006
Page 2
2 dc (10…60V) Output Module
Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT ATTENTION
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard, and recognize the consequences.
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Publication 1771-IN054C-EN-P - November 2006
Page 3
dc (10…60V) Output Module
3
Environment and Enclosure ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see: • Industrial Automation Wiring and Grounding Guidelines, for additional installation requirements, Allen-Bradley publication 1770-4.1. • NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Preventing Electrostatic Discharge ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation, if available. • Store the equipment in appropriate static-safe packaging when not in use.
Publication 1771-IN054C-EN-P - November 2006
Page 4
4 dc (10…60V) Output Module
Before You Begin Before you begin, make sure that the following decisions are made.
Determining Module Placement in the I/O Chassis You can place your module in any I/O module slot of the I/O chassis, except for the extreme left slot. This slot is reserved for programmable controllers or adapters. Group your module to minimize adverse effects from radiated electrical noise and heat. We recommend the following: • Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise. • Do not place this module in the same module I/O group with a digital high-density I/O module when using two-slot addressing. This module uses a byte in both the input and output image tables for block transfer.
Important Preinstallation Considerations The 1771-OBD series C module is compatible with all 1771 universal I/O chassis except 1771-A1, 1771-A2, and 1771-A4. Make sure no other output module or single-slot block transfer module is placed in the same module group when using two-slot addressing.
Calculate Power Requirements Your module receives its power through the 1771 I/O chassis backplane from the chassis power supply. The module requires 400 mA from the output of this supply. To calculate the requirements for the backplane power supply, add 400 mA to the power requirements of all other modules in the I/O chassis. Calculating the requirements will prevent an overload to the chassis backplane and/or backplane power supply.
Publication 1771-IN054C-EN-P - November 2006
Page 5
dc (10…60V) Output Module
5
Key the Backplane Place your module in any slot in the chassis except the leftmost slot, which is reserved for processors or adapters. Position keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: - between 10 and 12 - between 22 and 24
I/O Chassis
You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.
1. Position the keying bands in the backplane connectors to correspond to the key slots on the module. 2. Place the keying bands: - between 10 and 12. - between 22 and 24. You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.
ATTENTION
Observe the following precautions when inserting or removing keys: • Insert or remove keys with your fingers. • Make sure that key placement is correct. Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.
Publication 1771-IN054C-EN-P - November 2006
Page 6
6 dc (10…60V) Output Module
Install the Module ATTENTION
Make certain that you do not install this module into a chassis slot keyed for a 1771-IAD series D input module.
Install the module and secure it in the chassis. 1. Position the module in the card guides for the chosen slot.
1771-A1B, 1771-A2B, 1771-A3B, 1771-A3B1, 1771-A4B I/O Chassis Locking Tab
2. Slide the module into the chassis and apply firm, even pressure to seat the module into its backplane connector.
Card Guides
3. Series A chassis: Snap the chassis latch lever over the top of the module to secure the module in the chassis. Series B chassis: Swing the locking bar down into place, making sure the locking bar pins are engaged to secure the module in the chassis.
Module
1771-A1B, 1771-A2B, 1771-A3B1, 1771-A4B Series B I/O Chassis
4. Attach the field wiring arm to the horizonal bar at the bottom of the chassisThe wiring arm pivots upward so you can install or remove the module without disconnecting the wires.
The 1771-OBD module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to the Universal I/O Chassis Installation Instructions, publication 1771-IN075, for detailed information on. acceptable chassis, along with proper installation and grounding requirements. Limit the adjacent slot power dissipation to 10 W maximum.
Card Guides
Module
1771-WH Wiring Arm
Remove Horizontal Bar
Publication 1771-IN054C-EN-P - November 2006
Locking Bar
Locking Bar Pin
Install
Page 7
dc (10…60V) Output Module
7
Connect Wiring Connect your I/O devices to the field wiring arm, 1771-WH, shipped with the module.
WARNING
WARNING
ATTENTION
When you connect or disconnect the wiring arm with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Permanent damage to the module may occur in applications where frequent overload or short circuit conditions are possible. To prevent module damage where these conditions exist, use the optional 1771-WHF or 1771-WHFB fused field-wiring arm instead of the 1771-WH field-wiring arm shipped with the module. Note that the optional 1771-WHF or 1771-WHFB fused field-wiring arms are not certified for use in Class I, Division 2, Groups A, B, C, and D environments. Remove power from the 1771 I/O chassis backplane before you install this module. Failure to remove power from the backplane could cause: • module damage or degradation of performance. • injury or equipment damage due to possible unexpected operation.
You can use an ac (24V) output module, 1771-OND series C, to directly drive terminals on an ac/dc (24V) input module, 1771-IND series C, as shown in the connection diagram on page 8.
Publication 1771-IN054C-EN-P - November 2006
Page 8
8 dc (10…60V) Output Module
Connection Diagram See applicable codes and laws. +dc +dc +dc +dc Output 00 Output 01 Output 02
A B C D 00
Output 03
01 02 03
Output 04
04
Output 05
05 06
Output 06 Output 07 Output 10 Output 11 Output 12
07 10 11 12
Output 13
13
Output 14
14
Output 15 Output 16
15
Output 17 -dc
17
16
+
+ dc Output Device
User dc Supply
_
_
The output device is sinking current from the module.
E Sourcing Configuration
Actual wiring runs in this direction.
11915
You must supply dc at terminals A through D on the wiring arm. You need four dc connections to accommodate the total required surge rating on the module without overstressing any single connection on the field wiring arm. Jumper all dc connections together to prevent module damage. Connect terminal E to dc common.
Publication 1771-IN054C-EN-P - November 2006
Page 9
dc (10…60V) Output Module
ATTENTION
IMPORTANT
9
Observe proper polarity, as indicated in the connection diagram on page 10 with dc power connections. Reverse polarity, or application of ac voltage, could damage the module.
You can use a dc (10…60V) output module (771-OBD series C) to directly drive terminals on the following modules: • dc (5…30V) input module (1771-IQ) • dc (10…30V) input module (1771-IBD, 1771-IBN) • dc (20…60V) input module (1771-ICD) • dc (12…24V) input module (1771-IB) • dc (24V) input module (1771-IQ16) • dc (48V) input module (1771-IC)
Refer to Driving an Input with an Output Module on page for direct connection to a 1771-ICD input module.
IMPORTANT
Use the same dc supply to power both modules to make sure that ground is at the same potential.
Publication 1771-IN054C-EN-P - November 2006
Page 10
10 dc (10…60V) Output Module
Driving an Input with an Output Module dc (10…60V) Output Module 1771-OBD dc (20…60V) Input Module 1771-ICD
22…60V dc +dc
Not Used
+dc
Not Used
+dc
Not Used
+dc
Not Used
Output 00
Input 00
Output 01
Input 01
Output 02
Input 02
Output 03
Input 03
Output 04
Input 04
Output 05
Input 05
Output 06
Input 06
Output 07
Input 07
Output 10
Input 10
Output 11
Input 11
Output 12
Input 12
Output 13
Input 13
Output 14
Input 14
Output 15
Input 15
Output 16
Input 16
Output 17
Input 17
-dc
Actual wiring runs in this direction. See applicable codes and laws.
Publication 1771-IN054C-EN-P - November 2006 dc Common
11916