Installation Instructions: dc (10…60V) Output Module, Catalog Number 1771-OBD Series C, pages 11 to 20

Pages 11 to 20 of 20

The original document is the PDF (464 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OBD

Page 11

dc (10…60V) Output Module

11

Interpreting the LED Indicators The front panel of your module contains one green module active indicator, 16 red status indicators, and one red fuse blown indicator. The green module active indicator lights when the module is powered and the processor keyswitch is in RUN mode. The indicator light turns off when the processor resets the outputs.

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

Module Active Indicator (Green)

00…17 Status Indicators (Red)

The module active indicator must be on to properly interpret the red status indicators. The red status indicators are provided for indication of individual outputs. They indicate the state to which the transistor is commanded by the processor and are powered by circuitry within the module. The indicators will turn on and off as commanded by the processor. They do not indicate the presence or absence of dc power at an output terminal.

The module active indicator must be on to properly interpret the red status indicators. The red status indicators are provided for indication of individual outputs. They indicate the state to which the transistor is commanded by the processor and are powered by circuitry within the module. The indicators will turn on and off as commanded by the processor. They do not indicate the presence or absence of dc power at an output terminal. Fuse Blown Indicators (Red)

The fuse blown indicator turns on when the fuse is blown. When the fuse blown indicator is lit, check the fuse. After checking the fuse, make sure the field wiring arm is firmly in place. Do this before checking the status of the other indicators. Use this table to help you interpret the 1771-OBD status indicators and to troubleshoot module and system faults.

Troubleshooting Indicator Status

Description

Action

Module Active On (Green)

Normal indication.

None.

Module Active On (Green) and Output Status On (Red)

Check voltage at output point on swing arm.

If voltage is present, take no action. If no voltage is present, replace module.

Module Active On (Green) and Output Status Off

Output point not on in data table.

None.

Module failure.

Replace module.

Module Active Off and Output Status On or Off (Red)

Processor in Program mode.

None.

Module not functioning properly.

Check chassis power supply and processor. If they are okay, replace module.

Publication 1771-IN054C-EN-P - November 2006

Page 12

12 dc (10…60V) Output Module

Replace the Fuse An overload or short will cause the single onboard fuse to blow when the module output exceeds 10 A. The onboard fuse does not protect the individual output transistors. To replace the onboard fuse, do the following. 1. Turn off all power to the I/O chassis and all output device power to the field wiring arm.

ATTENTION

Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module. • Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

2. Remove the module from the chassis and replace the blown fuse with a 10 A, 250V rectifier fuse (1/4 x 1-1/4 inch), Littelfuse part number 322010. The fuse is accessible through the side of the module.

WARNING

Failure to use the specified replacement fuse may cause module damage, degradation of performance, or injury.

3. Replace the module in the chassis and attach the field wiring arm. 4. Turn system power on.

Publication 1771-IN054C-EN-P - November 2006

Page 13

dc (10…60V) Output Module

13

Hazardous Location Approvals North American Hazardous Location Approval The following information applies when operating this equipment in hazardous locations. Products marked CL I, DIV 2, GP A, B, C, D are suitable for use in Class I Division 2 Groups A, B, C, D, hazardous locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest T number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation. EXPLOSION HAZARD WARNING

Informations sur l’utilisation de cet équipement en environnements dangereux . Les produits marqués CL I, DIV 2, GP A, B, C, D ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d’équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l’installation. RISQUE D’EXPLOSION AVERTISSEMENT

•Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

•Couper le courant ou s’assurer que l’environnement est classé non dangereux avant de débrancher l'équipement.

•Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

•Couper le courant ou s'assurer que l’environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

•Substitution of components may impair suitability for Class I, Division 2.

•La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.

•If this product contains batteries, they must only be changed in an area known to be nonhazardous.

•S’assurer que l’environnement est classé non dangereux avant de changer les piles.

Publication 1771-IN054C-EN-P - November 2006

Page 14

14 dc (10…60V) Output Module

European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the EEx Marking.) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC. The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15.

IMPORTANT

Observe the following additional Zone 2 certification requirements: • This equipment is not resistant to sunlight or other sources of UV radiation. • This equipment must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments. • This equipment shall be used within its specified ratings defined by Allen-Bradley. • Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.

Publication 1771-IN054C-EN-P - November 2006

Page 15

dc (10…60V) Output Module

15

Specifications dc (10…60V) Output Module, 1771-OBD Series C Attribute

Value

Outputs per module

16 nonisolated

Module location

1771-A1B through 1771-A4B I/O chassis (Do not use this module with 1771-A4 I/O chassis)

User supply voltage

10…60V dc

Voltage, on-state output, nom

48V dc

Current rating (see Derating Curve)

2 A per output resistive, not to exceed 8 A per module 0.2 A per output pilot duty

Surge current, max

4 A per output for 10 ms, repeatable every 2 s 25 A per output for 10 ms, repeatable every 2 s

Load current, min

2.5 mA

On-state voltage drop (at rated current), max

1.5V dc

Off-state leakage current, max

0.5 mA

Output signal delay, max Off to on On to off

0.1 ms 0.2 ms

Power dissipation, max

15.6 W

Thermal dissipation, max

53.3 BTU/hr

Isolation voltage (continuous-voltage withstand rating)

60V (continuous), Basic Insulation Type Tested at 1000V ac for 60 s, I/O to system

Backplane current, max

400 mA @ 5V dc

Conductors wire size

Category(1)

0.34…2.5 mm2 (22…14 AWG) solid or stranded copper wire rated at 120 °C (248 °F) or higher 1.2 mm (3/64 in.) insulation max 2 - on signal ports

Temperature code, IEC

T3

Temperature code, North America

T3C

Field wiring arm

1771-WH 1771-WHF (3 A fused)(2) 1771-WHFB (1.5 A fused)(2)

Field wiring arm screw torque

1.0 Nm (9 lb-in)

Keying

Between 10 and 12 Between 22 and 24

(1)

Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

(2)

Not suitable for Class I Division 2 Groups A, B, C, and D Hazardous Locations.

Publication 1771-IN054C-EN-P - November 2006

Page 16

16 dc (10…60V) Output Module

Environmental Specifications Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): –40…85 °C (–40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

ESD immunity

IEC 61000-4-2: 4 kV indirect contact discharges

Radiated RF immunity

IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80% AM from 30…1000 MHz

EFT/B immunity

IEC 61000-4-4: ±1 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…30 MHz

Emissions

CISPR 11: Group 1, Class A (with appropriate enclosure)

Enclosure type rating

None (open style)

Publication 1771-IN054C-EN-P - November 2006

Page 17

dc (10…60V) Output Module

17

Certifications Certification (when product is

Value marked)(1) UL

UL Listed Industrial Control Equipment. See UL File E65584

CSA

CSA certified Process Control Equipment. See CSA file LR54689C.

CSA

CSA certified Process Control Equipment for Class I, Division 2, Groups A, B, C and D Hazardous locations. See CSA file LR69960C.

EEx

European Union 94/9/EC Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n (zone 2)

CE

European Union 89/336/EEC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity

C-Tick

Australian Radiocommunications Act compliant with AS/NZS CISPR 11, Industrial Emissions

(1)

See the Product Certification link at www.ab.com for Declarations of Conformity, certificates, and other certification details.

Publication 1771-IN054C-EN-P - November 2006

Page 18

18 dc (10…60V) Output Module

Derating Curve 9 8

Module Current - Amperes

7 6 5 4 3 2 1 0

0

10

20 30 Temperature (°C)

Publication 1771-IN054C-EN-P - November 2006

40

50

60

Page 19

dc (10…60V) Output Module

19

Notes:

Publication 1771-IN054C-EN-P - November 2006

Page 20

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running. United States

1.440.646.3223 Monday – Friday, 8am – 5pm EST

Outside United States

Please contact your local Rockwell Automation representative for any technical support issues.

New Product Satisfaction Return Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned. United States

Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for return procedure.

Allen-Bradley, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1771-IN054C-EN-P - November 2006 Supersedes Publication 1771-IN054B-EN-P - March 2003

PN 953030-37 Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.