Page 1

Installation Instructions

DC (24V) Isolated Output Module (Catalog Number 1771–OQ16 Series C)

To the Installer

This document provides information on: For information on: Important User Information Preinstallation Considerations

4

Calculate Power Requirements Determine Module Placement in the Chassis

4 4

Key the Backplane Connector

5

Install the Module and Field Wiring Arm

6

Connect Wiring to the Output Module

7

Replacing the Fuse

11

For this reference information Intepreting the Status Indicators Hazardous Location Approval Specifications

Important User Information

See page 1

See page 10 12 13

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.

Publication 1771-IN057B-EN-P - November 2002

Page 2

2

DC (24V) Isolated Output Module

Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication. Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard. WARNING

! ATTENTION

Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.

! Identifies information that is critical for IMPORTANT successful application and understanding of the product.

Publication 1771-IN057B-EN-P - November 2002

Page 3

DC (24V) Isolated Output Module

ATTENTION

!

3

Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.

Publication 1771-IN057B-EN-P - November 2002

Page 4

4

DC (24V) Isolated Output Module

ATTENTION

!

Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:

• Touch a grounded object to discharge potential • • • • •

PreĆinstallation Considerations static. Wear an approved grounding wriststrap. Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. If available, use a static–safe workstation. When not in use, keep modules in appropriate static–safe packaging.

This module is designed to operate with dc relays and other dc output devices. This module can be used in all 1771 I/O chassis except 1771-A1, A2 and A4 chassis. It can also be used in the 1771-AM1 and -AM2 chassis. This module is not compatible with the 1771-AL local I/O adapter.

Calculate Power Requirements

Determine Module Placement in the Chassis

The isolated output module is powered by the power supply connected to the I/O chassis backplane. The module requires a maximum current of 400mA from the +5V dc output of this supply. Total the current requirements of this module with the other modules in the I/O chassis to avoid overloading the supply or the I/O chassis backplane.

Group your modules to minimize adverse effects from radiated electrical noise and/or heat. We recommend the following:

• Group analog input and low voltage dc modules away from ac modules or high voltage dc modules to minimize electrical noise interface. • Place analog input modules and other I/O modules sensitive to heat away from slot power supplies to minimize adverse heat effects.

Publication 1771-IN057B-EN-P - November 2002

Page 5

DC (24V) Isolated Output Module

Key the Backplane Connector

ATTENTION

! Place your module in any slot in the chassis except the leftmost slot, which is reserved for processors or adapters.

ATTENTION

!

5

A module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Use keying bands to prevent damage to the module.

Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: - between 22 and 24 - between 32 and 34

Observe the following precautions when inserting or removing keys:

• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.

I/O chassis

Upper Connector You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.

11022-I

Publication 1771-IN057B-EN-P - November 2002

Page 6

6

DC (24V) Isolated Output Module

Install the Module and Field Wiring Arm

WARNING

! ATTENTION

!

When you insert or remove the module while backplane power is on, or you connect or disconnect the wiring arm with field power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure power is removed or the area is nonhazardous before proceeding. Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.

• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis

1771-A1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis locking tab locking bar locking bar pin card guides card guides module

Snap the chassis latch over the top of the module to secure it.

module

Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.

19809 wiring arm

Attach the wiring arm (1771-WN) to the horizontal bar at the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.

1771-WN remove horizontal bar install

17643

The 1771–OQ16 series C module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 10W maximum.

Publication 1771-IN057B-EN-P - November 2002

Page 7

DC (24V) Isolated Output Module

Connect Wiring to the Output Module

7

Make wiring connections to terminals on the field wiring arm (cat. no. 1771-WN) shipped with the module. Attach the wiring arm to the pivot bar on the bottom of the I/O chassis. The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires. 1. Make certain all power is removed from the module before making wiring connections. 2. Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into position. 3. Make connections to the field wiring arm as shown in the connection diagram below. (Use the label on the front of the wiring arm to identify your wiring.) ATTENTION

!

The field wiring arm terminal identification number is not the same as the number of the bit which controls that output. You should identify the labels on the wiring arm with the name or number of the device connected at each terminal.

Publication 1771-IN057B-EN-P - November 2002

Page 8

8

DC (24V) Isolated Output Module

Connection Diagram for the 1771–OQ16 Series C Isolated Output Module

Alternate Load Location

Load

+dc - 0 +dc - 1

2

Output 0

4

Output 1

+dc - 2

6

Output 2

+dc - 3 Not Used

8

+dc - 4

12

+dc - 5

14

+dc - 6

16

+dc - 7 Not used

18

+dc - 10

22

+dc -11

24

+dc - 12 +dc - 13

26

Output 3 Not used Output 4 Output 5

10

Output 6 Output 7

20

Output 11 Output 12 Output 13

28

Not used

30

+dc - 14

32

+dc - 15

34

+dc - 16

36

+dc - 17

38

Not used

40

Load

Not used Output 10

Not used Output 14 Output 15 Output 16 Output 17 Not used

(Actual wiring runs in this direction.) dc High +

ATTENTION

24V dc Supply dc Return -

Use copper wires suitable for 35oC above surrounding ambient.

! Note: A shorting bar can be used to connect the commons if no channel-to-channel isolation is required. You should identify the labels on the wiring arm with the name or number of the device connected at each terminal.

Publication 1771-IN057B-EN-P - November 2002