Manual · Allen-Bradley
Installation Instructions: DC (24V) Isolated Output Module (Catalog Number 1771-OQ16 Series C)
Manual16 pagesPDF 228 KB
Installation instructions for the Allen-Bradley 1771-OQ16 Series C DC (24V) isolated output module, with wiring, fuse and specifications.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley installation instructions for the 1771-OQ16 Series C DC (24V) isolated output module for 1771 I/O chassis. It covers preinstallation considerations, calculating power requirements, module placement, keying the backplane connector, installing the module and field wiring arm, connecting output wiring, replacing the fuse, interpreting the status indicators, hazardous location approval and the module specifications.
Its parts
- Preinstallation Considerations
- Calculate Power Requirements
- Determine Module Placement in the Chassis
- Key the Backplane Connector
- Install the Module and Field Wiring Arm
- Connect Wiring to the Output Module
- Interpreting the Status Indicators
- Replacing the Fuse
- Hazardous Location Approval
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (November 2002) for the Allen-Bradley 1771-OQ16 Series C DC (24V) isolated output module. They cover power requirements, keying, installing the module and its field wiring arm, wiring the outputs, reading the status indicators and replacing a fuse. The last pages list the full specifications and a derating curve.
- Device
- Series C isolated dc output module with 16 outputs, for dc relays and other dc output devices p. 1, 4, 13
- Voltage rating
- 10 to 32V dc p. 13
- Output current
- 2.0A per output, 32.0A per module at 0-45°C; derate to 1.5A per output, 24A per module at 60°C p. 13
- Compatible chassis
- All 1771 I/O chassis except 1771-A1, A2 and A4; also 1771-AM1 and -AM2 p. 4
- Backplane current
- 400mA maximum from the +5V dc supply p. 4, 13
- Fuse
- 3A 2AG fast-acting, one per output, Littelfuse 225003 p. 11, 14
- Field wiring arm
- 1771-WN, shipped with the module; screw torque 7-9 pound-inches (0.8-1.0Nm) p. 7, 14
- Indicators
- 16 red output status indicators, green ACTIVE, red FUSE blown p. 10
- Keying
- Between 22 and 24, and between 32 and 34 p. 5, 14
- Operating temperature
- 32 to 140°F (0 to 60°C), see derating curve; storage -40 to 185°F (-40 to 85°C) p. 13
- Isolation
- 1500V channel to channel and channel to backplane, tested for 1s p. 13
- Power dissipation
- 13.0 Watts max, 2.0 Watts min; adjacent slot power dissipation 10.0 Watts p. 13
- Max cable length
- 1000 ft (304.8 m) p. 13
- Conductors
- 14 to 22 gauge stranded or solid copper rated 60°C or greater; one or two wires per terminal, same size p. 13, 14
What this manual walks you through
- Calculating backplane power requirements p. 4
- Keying the backplane connector p. 5
- Installing the module and the field wiring arm p. 6
- Wiring loads and the 24V dc supply to the field wiring arm p. 7, 8
- Driving a 1771-IQ16 input with an output to show status p. 9
- Reading the status indicators p. 10
- Replacing a blown fuse p. 11
- Derating output current with temperature p. 13, 15
Good to know
- The module is not compatible with the 1771-AL local I/O adapter. p. 4
- Do not place the module in the leftmost slot, which is reserved for processors or adapters. p. 5
- Wiring arm terminal numbers are not the same as the numbers of the bits that control the outputs. p. 7
- The fuse-blown circuit does not work when the channel voltage is above the minimum on-state voltage and the load current is 5mA or less. p. 10
- Limit adjacent slot power dissipation to 10W maximum. p. 6
Questions this manual answers
What fuse does the 1771-OQ16 use?
A 3A 2AG fast-acting fuse, Littelfuse part number 225003, one per output. p. 11, 14
What voltage and current can a 1771-OQ16 output switch?
10 to 32V dc, up to 2.0A per output (32.0A per module) at 0-45°C, less at higher temperatures. p. 13
Which chassis can the 1771-OQ16 go in?
Any 1771 I/O chassis except the 1771-A1, A2 and A4, plus the 1771-AM1 and -AM2, in any slot but the leftmost. p. 4, 5
Why is the FUSE light on the 1771-OQ16 lit?
A fuse has cleared or been removed and its channel was turned on. The light resets after the fuse is replaced and chassis power is cycled. p. 10
Can the 1771-OQ16 commons be tied together?
Yes. A shorting bar can connect the commons when channel-to-channel isolation is not needed. p. 8
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file


