Spec sheet · Allen-Bradley
1771 Digital I/O DC Input and Output Modules Product Data
Spec sheet59 pagesPDF 987 KB
Allen-Bradley product data for the 1771 digital DC input and output modules, with specifications and wiring for each module including the 1771-OQ16.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley's product data publication for the 1771 Universal I/O family of digital DC input and output modules. An overview explains addressing modes, fault mode jumpers, input filtering, surge suppression, fuses and agency certification; then each module (1771-IB through -IVN inputs and -OB through -OVN outputs, including the 1771-OQ16 Series B) gets a schematic, application notes, a connection diagram and a specifications table.
Its parts
- Overview
- DC Input Module (Cat. No. 1771-IB)
- DC Input Module (Cat. No. 1771-IBD Series B)
- DC Input Module (Cat. No. 1771-IBN Series C)
- DC Input Module (Cat. No. 1771-IC)
- DC Input Module (Cat. No. 1771-ICD Series B)
- TTL Input Module (Cat. No. 1771-IG)
- DC Input Module (Cat. No. 1771-IGD)
- DC Input Module (Cat. No. 1771-IH)
- DC Input Module (Cat. No. 1771-IQ Series B)
- DC Input Module (Cat. No. 1771-IQ16 Series B)
- Fast Response DC Input Module (Cat. No. 1771-IT)
- DC Input Module (Cat. No. 1771-IV)
- DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)
- DC Output Module (Cat. No. 1771-OB Series C)
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
Product data (publication 1771-2.180, July 1996) for the Allen-Bradley 1771 digital dc I/O modules: inputs 1771-IB, 1771-IBD, 1771-IBN, 1771-IC, 1771-ICD, 1771-IG, 1771-IGD, 1771-IH, 1771-IQ, 1771-IQ16, 1771-IT, 1771-IV and 1771-IVN, and outputs 1771-OB, 1771-OBD, 1771-OBN, 1771-OC, 1771-OG, 1771-OGD, 1771-OQ, 1771-OQ16 and 1771-OVN. The site files it under the 1771-OQ16, whose two pages give its specifications, application notes and wiring diagrams. The overview explains chassis compatibility, fault mode jumpers, surge suppression and replacement fuse kits.
- Device
- 1771-OQ16: Series B dc output module with 16 outputs, for dc relays and other dc output devices p. 52, 53
- Output voltage
- 1771-OQ16: 10 to 32V dc p. 53
- Output current
- 1771-OQ16: 2.0A per output, 32.0A per module; minimum 5mA p. 53
- Chassis
- 1771-OQ16: series B 1771 I/O chassis only p. 52, 53
- Backplane current
- 1771-OQ16: 400mA maximum p. 53
- Fuses
- 1771-OQ16: 3A 2AG fast-acting, one per output, Littelfuse P/N 225003 p. 53
- Indicators
- 1771-OQ16: 16 output status indicators, a fuse-blown indicator and an active indicator p. 52
- Signal delay
- 1771-OQ16: turn on 100usec max; turn off 300usec max p. 53
- On-state drop
- 1771-OQ16: 0.34V dc at 2A max; off-state leakage 0.5mA per output at 32V dc p. 53
- Isolation
- 1771-OQ16: 1500V channel-to-channel and channel to backplane p. 53
- Power dissipation
- 1771-OQ16: 13.0 Watts max; 2.0 Watts min p. 53
- Field wiring arm
- 1771-OQ16: 1771-WN; screw torque 7-9 inch-pounds p. 53
- Keying
- 1771-OQ16: between 22 and 24, and between 32 and 34 p. 53
- Max cable length
- 1771-OQ16: 1000 ft (304.8 m) p. 53
What this sheet walks you through
- Comparing the dc input and output modules: data table use, addressing and chassis compatibility p. 3, 4, 5
- Setting the fault mode jumper to last state or reset p. 3
- Adding surge suppression for inductive loads p. 6
- Choosing replacement fuse kits and fused wiring arms p. 6, 7
- Keying slots and totaling chassis power requirements p. 2
- Wiring the 1771-OQ16 and driving a 1771-IQ16 input with it p. 52, 53
- Finding the installation instruction sheet for each module p. 8
Good to know
- The 1771-OQ16 does not work with the 1771-AL local I/O adapter. p. 52
- The leftmost backplane connector is reserved for adapter or processor modules. p. 2
- No single suppression device suits every load; the choice depends on its impedance characteristic. p. 6
- 1771-OQ16: 14 gauge wire on all terminals may keep the field wiring arm cover from closing. p. 53
Questions this sheet answers
What fuse does the 1771-OQ16 take?
A 3A 2AG fast-acting fuse, one per output, Littelfuse P/N 225003. p. 53
Which chassis does the 1771-OQ16 need?
A series B 1771 I/O chassis. It is not compatible with the 1771-AL local I/O adapter. p. 52
What voltage and current can the 1771-OQ16 switch?
10 to 32V dc, up to 2.0A per output and 32.0A per module. p. 53
Can a 1771-OQ16 output drive a 1771-IQ16 input?
Yes. An output can drive an input of a 1771-IQ16 dc input module, for example to show that a motor starter turned on. p. 52
When does the 1771-OQ16 fuse-blown indicator reset?
After the fuse has been replaced and chassis power has been cycled. p. 52
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-2.180, 1771 Digital I/O DC Input andOutput Module Product Data1
- DC Input Module (Cat. No. 1771-IB)12
- DC Input Module (Cat. No. 1771-IBD Series B)14
- DC Input Module (Cat. No. 1771-IBN Series C)16
- DC Input Module (Cat. No. 1771-IC)18
- DC Input Module (Cat. No. 1771-ICD Series B)20
- TTL Input Module (Cat. No. 1771-IG)22
- DC Input Module (Cat. No. 1771-IGD)24
- DC Input Module (Cat. No. 1771-IH)26
- DC Input Module (Cat. No. 1771-IQ Series B)28
- DC Input Module (Cat. No. 1771-IQ16 Series B)30
- Fast Response DC Input Module (Cat. No. 1771-IT)32
- DC Input Module (Cat. No. 1771-IV)34
- DC (10-30V) Input Module (Cat. No. 1771-IVN Series C)36
- DC Output Module (Cat. No. 1771-OB Series C)38
- DC Output Module (Cat. No. 1771-OBD Series C)40
- DC Output Module (Cat. No. 1771-OBN Series B)42
- DC Output Module (Cat. No. 1771-OC Series C)44
- DC Output Module (Cat. No. 1771-OG)46
- DC Output Module (Cat. No. 1771-OGD Series B)48
- DC Output Module (Cat. No. 1771-OQ Series B)50
- DC Input Module (Cat. No. 1771-OQ16 Series B)52
- DC Output Module (Cat. No. 1771-OVN Series B)54
- Notes56
- Support Services58
- 1771-2.180, Back Cover59
The whole text · 6 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.