Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 5 of 6

1771 Digital I/O DC Input and Output Modules Product Data, pages 41 to 50

Pages 41 to 50 of 59

The original document is the PDF (987 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OQ16

Page 41

38

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OBD Series C)

Specifications (Cat. No. 1771-OBD/C) Outputs per Module

16

Module Location

Series B 1771 I/O chassis

Output Voltage Range

10 to 60V dc

Minimum Output Current

2.5mA per output

Maximum Output Current

2A per output 8A per module

Surge Current (maximum)

0.5mA per output @ 24V dc, 25oC

On-state Voltage Drop (max.)

0.3V at 2A

Power Rating (maximum)

3 Watts per output

Output Signal Delay

1.0ms on or off

Power Dissipation

14 Watts (max.), 2 Watts (min.)

Thermal Dissipation

47.8 BTU/hr (max.), 6.9 BTU/hr (min.)

Backplane Current

400mA @ 5V dc +5%

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum

Conductors Wire Size

3/64 inch (1.2mm) insulation maximum 11

Category Fuse

10A, 250V rectifier fuse (1/4 x 1-1/4 inch)

Keying

Between 10 and 12 Between 22 and 24 Standard Optional

Cat. No. 1771-WH Cat. No. 1771-WHF (fused - 3A)2 Cat. No. 1771-WHFB (fused - 1.5A)3

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 FUSE

4A per output for 10ms, repeatable every 2s 25A per module for 10ms, repeatable every 2s

Off-state Leakage Current (maximum)

Field Wiring Arm

Status Indicator

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

Fuse Blown Indicator (red) 12250-I

Connecting Diagram Driving a 1771-ICD Module with a 1771-OBD Module DC (10-60V) Output Module (Cat. No. 1771-OBD)

DC (20-60V) Input Module (Cat. No. 1771-ICD) 20-60V dc

+dc +dc +dc +dc Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 -dc

Not used Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 dc Common

1771-2.76

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual. 2 With a customer supply voltage of 30V dc or less, the field wiring arm fuses protect the individual output circuits from damage during a short circuit condition while controlling a resistive load with a continuous current that does not exceed 2A. 3 With a customer supply voltage of 30V dc or less, the field wiring arm fuses protect the individual output circuits from damage during a short circuit condition while controlling a resistive load with a continuous current that does not exceed 1A.

Publication 1771-2.180 - July 1996

00 to 17 Status Indicators (red)

20-60V dc Return (Actual wiring runs in this direction)

(See Applicable Codes and Laws) 12251-I

Page 42

1771 Digital I/O DC Input and Output Modules

39

DC Output Module (Cat. No. 1771-OBN Series B)

Simplified Schematic

Fuse Blown Indication LED (logic)

Opto Isolation 470

Output Indication LED (logic)

1N4007

+dc Supply (1 of 4)

Fuse 4 Amp Output

System Circuitry

Opto Isolation 15k

Power SIP

1N4007 dc Supply Common (1 of 4)

18569

Application Notes Device Compatibility. The 1771-OBN dc output module has sourcing outputs and requires sinking inputs. You must use this module in a series B 1771 I/O chassis. Do not place this module in the same I/O chassis as the 1771-IX thermocouple module. You can use this module in the same chassis as the 1771-IXE thermocouple module. Connection to Input Modules. A 1771-OBN module can directly drive terminals on a 1771-IBN input module. Use the same dc supply to power both modules to ensure that ground is at the same potential.

Status Indicators. The module has 32 status indicators. These are provided for system logic side indication of individual outputs. An additional indicator is provided to indicate a blown-fuse condition.

Connection Diagram Output 0

2

Output 2 Output 4 Output 6 Common 0 Output 10 Output 12 Output 14

4

Output 16 Common 1 Output 0 Output 2 Output 4 Output 6 Common 2 Output 10 Output 12 Output 14 Output 16 Common 3

18

6 8 10 12 14 16 20 22 24 26 28 30 32 34 36 38 40

+ dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17 + dc Output 1 Output 3 Output 5 Output 7 + dc Output 11 Output 13 Output 15 Output 17

Note: Terminals on the left are even numbered (2 thru 40) , and terminals on the right are odd numbered (1 thru 39). + dc Output Device + dc Supply -

(See applicable codes and laws.) (Actual wiring runs in this direction.)

12252-I

Publication 1771-2.180 - July 1996

Page 43

40

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OBN Series B)

Status Indicators

Specifications (Cat. No. 1771-OBN/B) Outputs per module

32 (4 groups of 8)

Module Location

1771-A1B thru -A4B I/O Chassis

Output Voltage Range

10 to 30V dc

Maximum Output Current

0.5A per output 2A per output group 8A per module

Maximum Surge Current

2A per output for 10ms; repeatable every 2s 5A per group for 10ms.;repeatable every 2s 20A per module for 10ms.; repeatable every 2s

Maximum On-state Voltage Drop

1.0mA per output @ 30V dc, 55oC

Maximum Off-state Leakage Current Maximum Power Rating

0.75W per output

Output Signal Delay

On to off propagation delay 2.0ms Off to on propagation delay 0.1ms

Power Dissipation

13.7W (max); 1.7W (min)

Thermal Dissipation

46.7 BTU/hr (max); 5.7 BTU/hr (min)

Backplane Current

330mA @ 5V dc maximum

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded (max)1 3/64 inch (1.2mm) insulation (max) 12

Conductors Wire Size Category Fuses

Four 4.0A, 250V normal blow fuses (1 per group)

Keying

Between 14 and 16 Between 20 and 22

Field Wiring Arm

1771-WN

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions 1

00 10 00 10 01 11 01 11 02 12 02 12 03 13 03 13 04 14 04 14 05 15 05 15 06 16 06 16 07 17 07 17 FUSE

1.5V dc at 0.5A

1771-5.34

14 gauge wire connected to all terminals may not allow the cover on the field wiring arm to close. A smaller gauge wire may be used.

2

You use this conductor-category information for planning conductor routing as described in the system-level installation manual.

Fuse Blown Indicator 12253-I

Sample Connection Diagram Driving a 1771-IBN Module with a 1771-OBN Module DC Output Module Cat. No. 1771-OBN

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

DC Input Module Cat. No. 1771-IBN +dc 10-30V dc dc Common

(Actual wiring runs in this direction.)

Publication 1771-2.180 - July 1996

Status Indicators (red)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

12254-I

Page 44

1771 Digital I/O DC Input and Output Modules

41

DC Output Module (Cat. No. 1771-OC Series C)

Simplified Schematic 1N4448

System Circuitry

2 Amp Fuse

+dc Supply

10k

Opto Isolation

3.3k 1.1k 1N4002

10k

Output 15k

5.62k

280

3.3k

Output Indication LED (field) Fuse Blown Indication LED (field)

1N4002 13V dc Supply Common 18564

Application Notes Device Compatibility. The 1771-OC module can control the following output devices: • dc motor starters • indicators • solenoids Connection to Input Modules. You can directly drive terminals on a dc (48V) input module (cat. no. 1771-IC) from terminals on the dc (48V) output module (cat. no. 1771-OC). Use the same dc power source to power both modules to ensure that ground is at the same potential. Status Indicators. The module has nine red status indicators. The top indicator is the fuse-blown indicator. It illuminates when a fuse has blown in the module. The remaining eight status indicators are provided for field side indication of individual outputs.

Connection Diagram See Applicable Codes and Laws +dc

A

Output 0

0

Output 1

1

Output 2

2

Output 3

3

Output 4

4

Output 5

5

Output 6

6

Output 7

7 dc Common

B

+ dc Output Device -

+ dc Power Supply -

11394

(Actual wiring runs in this direction.)

Publication 1771-2.180 - July 1996

Page 45

42

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OC Series C)

Status Indicator

Specifications (Cat. No. 1771-OC/C) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range

42 to 53V dc

Maximum Output Current

1.5A per output; 8A per module

Maximum Surge Current

4A for 1ms, repeatable every 1s per output

Maximum Off-state Leakage Current

1mA per output @ 53V dc, 25oC

Maximum On-state Voltage Drop

2V dc @ 1.5A

Maximum Power Rating

3W per output

Output Signal Delay

10msec on or off

Power Dissipation

16.9 Watts (max.), 0.9 Watts (min.)

Thermal Dissipation

57.6 BTU/hr (max.), 3.0 BTU/hr (min.)

Backplane Current

165mA @ 5V dc +5%

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Category

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21

Fuses

2A 8AG (one per output)

Keying

Between 4 and 6 Between 20 and 22

Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions

Catalog Number 1771-WA 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.175

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Blown Fuse Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7

Status Indicators

12255-I

Connection Diagram Driving a 1771-IC Module with a 1771-OC Module DC Output Module (Cat. No. 1771-OC)

DC (48V) Input Module (Cat. No. 1771-IC)

42-53V DC +dc

A

A

Not used

Output 0

0

0

Input 0

Output 1 Output 2

1

1

2

2

Input 1 Input 2

Output 3

3

3

Input 3

Output 4

4

4

Input 4

Output 5

5

5

Input 5

Output 6

6

6

Input 6

Output 7

7

7

Input 7 dc Common

B

B dc Common dc Return (Actual wiring runs in this direction.)

(See Applicable Codes and Laws) 12256-I

Publication 1771-2.180 - July 1996

Page 46

1771 Digital I/O DC Input and Output Modules

43

DC Output Module (Cat. No. 1771-OG) 4.7k

Simplified Schematic Output Indication LED (logic)

System Circuitry

Open - Low = True Closed - High = True

Open - Disable LED Closed - Enable LRD

1k

Opto Isolation

Customer +5V dc Supply

680

TTL Output

Customer Common dc Supply 18665

Application Notes Device Compatibility. You can use any TTL device that meets the input logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high). A switch on the module allows selection of High = True or Low = True logic. Connection to Input Modules. Output terminals of the TTL output module (cat. no. 1771-OG) may directly drive inputs of a TTL input module (cat. no. 1771-IG). Connect the cable shield between modules at one end only. Status Indicators. The module has nine status indicators. The red top indicator is labeled = True." When on, it indicates you selected high-true logic. When off, it indicates you selected low-true logic. Each of the lower eight indicators light when their corresponding output terminal delivers TTL voltages in the true state. Indicators may appear dim during rapid pulsing of output signals. Module Application. You can select the operating logic of the module using the logic switches located in the module. Choose between = True" or = True" logic.

Connection Diagram (See applicable codes and laws.)

+5V dc Output 0 Output 1

A

Output 2 Output 3 Output 4

2

Output 5

5

Output 6

6

Output 7 dc Common

7

Customer Power Supply +5V dc +

O 1

1

3 4

+

1

-

8

Ground cable shield at a single chassis mounting bolt. 1 Add a pull-up resistor (1K ohm typical) if not internal to the device. (Actual wiring runs in this direction.) The outputs of the 1771-OG are open-collector with internal 1K pull-up (up to 5V) resistors.

10447-I

Publication 1771-2.180 - July 1996

Page 47

44

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OG)

Status Indicator

Specifications (Cat. No. 1771-OG) Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range HIGH = TRUE LOW = TRUE

ON; 2.0 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.0 to 5.25V dc

Maximum Output Current

Source: 1mA; Sink: 20mA

Customer Supply Voltage

5V dc (+0.25V) 50mV peak-to-peak ripple max.

Customer Supply Current per Module

250mA max.

Output Signal Delay

Less than 1ms

Power Dissipation

2.2 Watts (max.); 0.8 Watts (min.)

Thermal Dissipation

7.5 BTU/hr (max.); 2.7 BTU/hr (min.)

Backplane Current

168mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

Wire Size Cable Category

Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Installation Instructions

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21 Between 6 and 8 Between 10 and 12 Catalog Number 1771-WC 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.177

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.180 - July 1996

HIGH = TRUE indicator Output 0 Output 1 Output 2 Output 3 Status Indicators Output 4 Output 5 Output 6 Output 7

12257-I

Page 48

1771 Digital I/O DC Input and Output Modules

45

DC Output Module (Cat. No. 1771-OGD Series B)

Simplified Schematic Output Indication LED (logic)

System Circuitry

Customer +5V dc Supply

.5 Amp Fuse

1k

1N4448

1N4448

6V

TTL Output

Opto Isolation 7438 High/Low Logic Select

Application Notes Device Compatibility. The TTL output module must be used in a series B 1771 I/O chassis.You can use any TTL device that meets the input logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high). Connection to Input Modules. Output terminals of the TTL output module (cat. no. 1771-OGD) may directly drive the inputs of the TTL input module (cat. no. 1771-IGD). Connect the cable shield between modules at one end only. Status Indicators. The module has 18 status indicators. The green top indicator, labeled is on when the fuse is good. The green bottom indicator, when on, indicates you selected high-true logic. When off, it indicates you selected low-true logic. Each of the 16 red status indicators light when their corresponding output terminal delivers TTL voltages in the true state. Module Application. You can select the operating logic of the module using the logic switches located in the module. Choose between = True" or = True" logic.

Customer Common dc Supply

MOV 14V dc

18568

Connection Diagram (See applicable codes and laws.) +5V dc +5V dc +5V dc +5V dc Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 Output 16 Output 17 dc Common

A B C D 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 E

Customer Power Supply +5V dc

-

+

1

1

Ground cable shield at a single chassis mounting bolt. 1 Add a pull-up resistor if not internal to the device.

(Actual wiring runs in this direction.)

The outputs of the 1771-OGD module are open collector with internal 1K ohm pull-up (to 5V) resistors. 10444-I

Publication 1771-2.180 - July 1996

Page 49

46

1771 Digital I/O DC Input and Output Modules

DC Output Module (Cat. No. 1771-OGD Series B)

Specifications (1771-OGD/B) Outputs per Module

16

Module Location

Series B 1771 I/O chassis

Output Voltage Range HIGH = TRUE

ON; 2.0 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.0 to 5.25V dc

LOW = TRUE Maximum Output Current

Source: 1mA; Sink: 20mA

Customer Supply Voltage

5V dc (+0.25V) 50mV peak-to-peak ripple max.

Customer Supply Current per Module

310mA max.

Output Signal Delay

Less than 1ms

Power Dissipation

2.8 Watts (max.); 1.0 Watts (min.)

Thermal Dissipation

9.5 BTU/hr (max.); 3.4 BTU/hr (min.)

Backplane Current

230mA max.

Isolation Voltage

1500V ac rms

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors

0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21

Wire Size Cable Category

Fuse

0.5A 250V Normal Blow

Keying

Between 16 and 18 Between 26 and 28

Field Wiring Arm

Catalog Number 1771-WH

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Status Indicators

7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Instructions

1771-2.176

1 You use this conductor-category for planning conductor routing as described in the system-level installation manual.

Publication 1771-2.180 - July 1996

ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 HIGH

Module Active Indicator (green) 00 to 17 Status Indicators (red) Positive Logic Indicator (green) 10445-I

Page 50

1771 Digital I/O DC Input and Output Modules

47

DC Output Module (Cat. No. 1771-OQ Series B)

Simplified Schematic

2.5 Amp Fuse 10k

System Circuitry

Opto Isolation

+dc Supply

1N4005

2.35k

Output 12k Output Indication LED (field)

1N4005

15V

JPR

10 µF dc Supply Common

1N4005

Application Notes

18666

Connection Diagram

Device Compatibility. An output from this module can drive dc motor starters, indicators, and solenoids.

(See applicable codes and laws.)

Output 6 Output 7 +24V dc Not used

+ + dc Output Device -

+ dc - Output Device + +

+ dc Output Device -

+ dc - Output Device

1 2

Setting Jumper Configuration. This module contains soldered jumpers that limit the effects of noise. They must be removed when using certain output devices, such as solenoids. These jumpers are not reusable. Make certain that you will not be using a particular output for other uses before clipping the jumper. Use the figure below to locate the jumper.

Output 4 Output 5 dc Common dc Common

3 4 5 6 7 8

Status Indicators. The module has eight red status indicators. Each status indicator provides field side indication of individual outputs. When an indicator is illuminated, the corresponding output circuit is closed.

dc Common dc Common Output 2 Output 3 +24V dc +24V dc

9 10 11 12

Not used +24V dc Output 0 Output 1

13 14 15 16 17 18

Connection to Input Modules. The 1771-OQ module can drive a 24V dc input module (cat. no. 1771-IB) if you have not removed the jumpers on the 1771-OQ.

+ dc Output Device -

+

User 24V dc Supply -

-

User 24V dc Supply dc Output Device - dc Output Device -

+

+

User 24V dc Supply -

-

User 24V dc Supply dc Output Device -

+

Black Band

Clip leads here. Jumper 1 - corresponds to output 0 Jumper 2 - corresponds to output 1 Jumper 3 - corresponds to output 2 Jumper 4 - corresponds to output 3 Jumper 5 - corresponds to output 4 Jumper 6 - corresponds to output 5 Jumper 7 - corresponds to output 6 Jumper 8 - corresponds to output 7

Field Wiring Arm Cat. No. 1771-WF (Actual wiring runs in this direction.)

12259-I

11066-I

Publication 1771-2.180 - July 1996