The text of a spec sheet · part 3 of 6
1771 Digital I/O DC Input and Output Modules Product Data, pages 21 to 30
Pages 21 to 30 of 59
The original document is the PDF (987 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OQ16
Page 21
18
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-ICD Series B)
Status Indicators
Specifications (Cat. No. 1771-ICD/B) Inputs per Module
16
Module Location
1771-A1B thru -A4B or later I/O chassis
Input Voltage Range
20 to 60V dc
Minimum Input Current
2mA at 20V dc; 6mA at 60V dc
Minimum Off-state Current
1.2mA @ 12V dc
Maximum Off-state Voltage
12V dc
Minimum On-state Voltage
20V dc
Input Impedance
10K ohms maximum
Input Signal Delay
Low to high propagation delay 6ms( +2ms) High to low propagation delay 20ms (+1ms)
Power Dissipation
5.9 Watts (max.), 1.3 Watts (min.)
Thermal Dissipation
19.9 BTU/hr (max.), 4.3 BTU/hr (min.)
Backplane Current
250mA @ 5V dc +5%
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Wire Size Category
Keying
00 to 17 Status Indicators (red)
12237-I
Sample Connection Diagram Driving a 1771-ICD Module with a DC Input Module 1771-OC Module Cat. No. 1771-ICD A
Catalog Number 1771-WH
Wiring Arm Screw Torque
B
DC Output Module Cat. No. 1771-OC
7-9 inch-pounds
C D
• CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
+dc
A
Output 0
O
1771-5.29
Output 1
1
Output 2
2
06
Output 3
3
07
Output 4
4
Output 5
5
12
Output 6
6
14
Output 7
7 dc Common
8
Installation Instructions 1
ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17
Between 10 and 12 Between 18 and 20
Field Wiring Arm Agency Certification (when product or packaging is marked)
Module Active Indicator (green)
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
42-53V dc
00 01 02 03 04 05
10 11 13 15 16 17 E dc Return (Actual wiring runs in this direction.) 12238-I
Publication 1771-2.180 - July 1996
Not used Not used Not used Not used Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 dc Common
Page 22
1771 Digital I/O DC Input and Output Modules
19
TTL Input Module (Cat. No. 1771-IG)
Simplified Schematic
Customer +5V dc Supply
1k System Circuit
Input Filter
TTL Input
Opto Isolation 74132
Customer Common dc Supply
Input Indication LED (logic)
Application Notes
18553
Connection Diagram
Device Compatibility. You can use any TTL device that meets the output logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high). This module contains input filtering to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering is nominally 1ms. For maximum noise immunity, the output of the TTL device that is driving the input should have a pull-up resistor of 1k ohm (typical). If you add a pull-up resistor, be sure the TTL device maintains the low state requirement of -0.2 V dc to +0.8V dc with the increased load. Connection to Output Modules. Input terminals of the TTL Input Module may be directly driven by outputs of the TTL Output Module (Cat. No. 1771-OG). Status Indicators. The front panel contains eight indicator lights. Each indicator lights when its corresponding input terminal senses TTL voltages in the true state. Indicators may appear dim during rapid pulsing of input signals.
Customer Power Supply +5V dc
(See applicable codes and laws.)
-
+ +5V dc
A
Input 0
O
Input 1
1
Input 2
2
Input 3
3
Input 4
4
Input 5
5
Input 6
6
Input 7
7 dc Common
8
1 2
2
1
Ground cable shield at a single chassis mounting bolt. 1 TTL Devices must have open-collector outputs. 2 Internal or external pull-up resistor (1K ohm typical). (Actual wiring runs in this direction.) 10441-I
Module Application. You can select = True" or = True" logic operation using logic switches located on the module.
Publication 1771-2.180 - July 1996
Page 23
20
1771 Digital I/O DC Input and Output Modules
TTL Input Module (Cat. No. 1771-IG)
Specifications (Cat. No. 1771-IG) Inputs per Module
8
Module Location
Series A or B 1771 I/O chassis
Input Voltage Range HIGH = TRUE LOW = TRUE Customer Current Sink Requirements Customer Supply Voltage
ON; 2.4 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.4 to 5.25V dc 7mA (source per input) 0.8mA (sink per input) 5V dc (+0.25V) 50mV peak-to-peak ripple max.
Customer Supply Current per Module
500mA max.
Input Signal Delay
Less than 1ms
Power Dissipation
3.3 Watts (max.), 0.6 Watts (min.)
Thermal Dissipation
11.3 BTU/hr (max.), 2.0 BTU/hr (min.)
Backplane Current
122mA max.
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Conductors Wire Size Cable Category Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21 Between 4 and 6 Between 34 and 36 Catalog Number 1771-WC 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.9
You use this conductor-category information for planning conductor routing as described in the system-level installation manual.
Publication 1771-2.180 - July 1996
Status Indicators
HIGH = TRUE indicator Input 0 Input 1 Input 2 Input 3 Status Indicators Input 4 Input 5 Input 6 Input 7
10442-I
Page 24
1771 Digital I/O DC Input and Output Modules
21
DC Input Module (Cat. No. 1771-IGD)
Simplified Schematic Input Indication LED (logic) 1N4448
1k System Circuitry
Customer +5V dc Supply
.5 Amp Fuse
TTL Input
Opto Isolation 74LS132
MOV 14V dc
1N4448
Customer Common dc Supply
6V dc
18560
Application Notes Device Compatibility. This module must be used in a series B 1771 I/O chassis.You can use any TTL device that meets the output logic level specification of -0.2V dc to +0.8V dc (low), and 2.0V dc to 5.25V dc (high).This module contains input filtering to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering is nominally 50us. For maximum noise immunity, the output of the TTL device that is driving the input should have a pull-up resistor of 1k ohm (typical). If you add a pull-up resistor, be sure the TTL device maintains the low state requirement of -0.2V dc to +0.8V dc with the increased load. Connection to Output Modules. Input terminals of the TTL input module (cat. no. 1771-IGD) may be directly driven by the outputs of a TTL output module (cat. no. 1771-OGD). Connect the cable shield between modules at one end only. Status Indicators. The front panel contains 18 status indicators. The green active indicator is on when the fuse is good. The green bottom indicator, when on, indicates you selected high-true logic. When off, it indicates you selected low-true logic. Each of the 16 red status indicators light when their corresponding input terminal senses TTL voltages in the true state.
Connection Diagram (See applicable codes and laws.) +5V dc +5V dc +5V dc +5V dc Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17 dc Common
Customer Power Supply +5V dc +
A B C D 00 01 02 03 04 05 06 07 10 11 12 13
1 2
2
1
14 15 16 17 E
Ground cable shield at a single chassis mounting bolt. 1 TTL Devices must have open-collector outputs. 2 Internal or external pull-up resistor (1K ohm typical).
(Actual wiring runs in this direction.)
10450-I
Module Application. You can select = True" or = True" logic operation using logic switches located on the module.
Publication 1771-2.180 - July 1996
Page 25
22
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IGD)
Status Indicators
Specifications (Cat. No. 1771-IGD) Inputs per Module
16
Module Location
Series B 1771 I/O chassis
Input Voltage Range HIGH = TRUE LOW = TRUE
ON; 2.0 to 5.25V dc OFF: -0.2 to +0.8V dc ON: -0.2 to +0.8V dc OFF: 2.0 to 5.25V dc
Customer Current Sink Requirements
7mA maximum (source per input) 0.8mA maximum (sink per input)
Customer Supply Voltage
5.0V dc (+0.25V) 50mV peak-to-peak ripple max.
Customer Supply Current per Module
380mA max.
Input Signal Delay
Less than 1ms
Power Dissipation
2.7 Watts (max.); 0.4 Watts (min.)
Thermal Dissipation
9.2 BTU/hr (max.); 1.4 BTU/hr (min.)
Backplane Current
130mA max.
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Fuse Conductors
0.5A 250V normal blow Wire Size Cable Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1 the
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum Shielded (Belden 8761) 21 Between 16 and18 Between 24 and 26 Catalog Number 1771-WH 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.178
You use this conductor-category information for planning conductor routing as described in system-level installation manual.
Publication 1771-2.180 - July 1996
Module Active Indicator (green) ACTIVE 00 10 01 11 02 12 03 13 04 14 05 15 06 16 07 17 HIGH
00 to 17 Status Indicators (red)
Positive Logic Indicator (green) 10451-I
Page 26
1771 Digital I/O DC Input and Output Modules
23
DC Input Module (Cat. No.1771-IH)
Simplified Schematic 9.1k 1N4448 System Circuitry
Comparator
Input Filter
3.9k Input Indication LED (field)
Opto Isolation 3.9V
+dc Input
2.2k dc common
18554
Application Notes
Connection Diagram (Two-Wire Devices)
Device Compatibility. The 1771-IH module is compatible with the following two-wire devices: • pushbuttons • limit switches • float switches • selector switches
See Applicable Codes and Laws Not used
A
The off-state leakage current of your two-wire devices should not exceed 1mA.
Input 0
0
Input 1
1
Connection to Output Modules. Inputs on the DC (24-48V) Input module can be directly driven by outputs on dc output modules (cat. no. 1771-OB, -OBD, and -OC).
Input 2
2
Input 3
3
Input 4
4
Input 5
5
Input 6
6
Input 7
7 dc Common
B
Status Indicators. The front panel contains 8 red status indicators. The status indicators are provided for field side indication of individual inputs.
(Actual wiring runs in this direction.)
+ dc Power Supply -
12239-I
Publication 1771-2.180 - July 1996
Page 27
24
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No.1771-IH)
Specifications (Cat. No. 1771-IH) Inputs per Module
8
Module Location
1771 I/O chassis
Input Voltage Range
24 to 48V dc
Nominal Input Current
8.4mA at 24V dc 20mA at 48V dc
Minimum Off-state Current
1.0mA
Maximum Off-state Voltage
4.5V dc
Minimum On-state Voltage
2.5 to 3K ohms maximum (on-state) 5 to 6K ohms maximum (off-state)
Input Signal Delay
Low to high propagation delay 15ms+7ms High to low propagation delay 15ms+7ms
Power Dissipation
8.1 Watts (max.), 0.4 Watts (min.)
Thermal Dissipation
27.7 BTU/hr (max.), 1.3 BTU/hr (min.)
Backplane Current
74mA @ 5V dc +5%
Isolation Voltage
1500V ac rms
Conductors
Wire Size Category
Keying Field Wiring Arm Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Installation Instructions 1
Not used Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
10V dc
Input Impedance
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
Status Indicators
Status Indicators
12240-I
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF) 5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
Sample Connection Diagram Driving a 1771-IH Module with a 1771-OB Module
Between 4 and 6 Between 16 and 18 Catalog Number 1771-WA 7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives 1771-2.8
You use this conductor-category for planning conductor routing as described in the system-level installation manual.
DC Output Module Cat. No. 1771-OB
+dc 24-27V dc
DC Input Module Cat. No. 1771-IH
+dc
A
A
Not used
Input 0
0
0
Output 0
Input 1
1
1
Output 1
Input 2
2
2
Output 2
Input 3
3
3
Output 3
Input 4
4
4
Output 4
Input 5
5
5
Output 5
Input 6
6
6
Output 6
Input 7
7
7
Output 7 dc Common
B
B dc Common dc Common (Actual wiring runs in this direction.) 12241-I
Publication 1771-2.180 - July 1996
Page 28
1771 Digital I/O DC Input and Output Modules
25
DC Input Module (Cat. No. 1771-IQ Series B)
Simplified Schematic Customer Supply +dc
Input Indication LED (logic)
System Circuitry
Input Filter
Opto Isolation
Comparator
100k
On for Source
1.2k
47 Input
1.2k On for Sink
1N4448
Customer Supply -dc 18555
Application Notes Device Compatibility. Each of the eight inputs to this module are switch selectable for current sourcing or current sinking of your device. The module can be set for either high true or low true logic. The module has selectable delay times of 12ms nominal (5ms minimum; 26ms maximum) in normal or 1ms (maximum) in fast position. The switches must be set before you install the module.
Connection Diagram (See applicable codes and laws.) (+) 5-30V dc
A
Input 0
O
Input 1
1
Input 2
2
Input 3
3
Connection to Output Modules. The sinking inputs on the DC (5-30V) Input module (cat. no. 1771-IQ) can be directly driven by the sourcing outputs of the 24V dc output modules (cat. nos. 1771-OQ, -OQ16, -OB, -OBD and -OBN).
Input 4
4
Input 5
5
Input 6
6
Input 7
7
Status Indicators. The front panel contains eight status indicators. The indicators provide system logic side indication of individual inputs.
dc Common
8
Module Input Sink dc Current Source Device +
Module Input Source Module Input Source
3-Wire Current Sink Proximity Switch
Power Supply (Customer Supplied)
dc Current Sink Device
-
Conventional current flow
(Actual wiring runs in this direction.)
Publication 1771-2.180 - July 1996
Page 29
26
1771 Digital I/O DC Input and Output Modules
DC Input Module (Cat. No. 1771-IQ Series B)
Status Indicators
Specifications (Cat. No. 1771-IQ/B) Inputs per Module
8
Module Location
1771 I/O chassis
Nominal Input Current
5mA @ 5V dc; 25mA @ 30V dc
Input Voltage Range HIGH = TRUE
ON: > 40% of customer supply voltage OFF: < 20% of customer supply voltage ON: < 20% of customer supply voltage OFF: > 40% of customer supply voltage
LOW = TRUE Customer Supply Voltage
5V dc to 30Vdc
Customer Supply Current per Module
All inputs ON and connected for source capability: 100mA per module @ 5V dc 350mA per module @ 30V dc
Input Impedance
1.2K ohms nominal
Input Signal Delay
Fast: Less than 1ms Normal: 12ms typical (-7ms, +14ms)
Power Dissipation
6.8 Watts (max.), 0.8 Watts (min.)
Thermal Dissipation
23.2 BTU/hr (max.), 2.7 BTU/hr (min.)
Backplane Current
150mA max.
Isolation Voltage
1500V ac rms
Environmental Conditions Operational Temperature Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) -40o to 85oC (-40o to 185oF)
5 to 95% (without condensation) 14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 21
Conductors Wire Size Category Keying
Between 6 and 8 Between 24 and 26
Wiring Arm
Catalog Number 1771-WC
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
7-9 inch-pounds • CSA certified • CSA Class I, Division 2 Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Instructions 1
1771-2.24
You use this conductor-category for planning conductor routing as described in the system-level installation manual.
Empty Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
Status Indicators
11907-I
Sample Connection Diagram Driving a 1771-IQ Module with a 1771-OQ Module DC Output Module Cat. No. 1771-OQ +24V dc Not used +24V dc Output 0 Output 1
1 dc Common
5 dc Common Output 2 Output 3 +24V dc
6
A
24V dc
7
O
Input 0
8
1
Input 1
2
Input 2 Input 3
DC Input Module Cat. No. 1771-IQ
2 3 4
9
+24V dc
10
Output 4
11
3 4
Input 4
5
Input 5
Output 5
12 dc Common dc Common
13
Output 6 Output 7 +24V dc
15
6
Input 6
16
7
Input 7
8 dc Common
Not used
18
14
17 dc Common
(Actual wiring runs in this direction.) 12246-I
Publication 1771-2.180 - July 1996
Page 30
1771 Digital I/O DC Input and Output Modules
27
DC Input Module (Cat. No. 1771-IQ16 Series B)
Simplified Schematic Input LED Indication
System Circuitry
Input 38k
Opto Isolation
825Ω
6.2V
750k
30V
825Ω dc Common 12247-I
Application Notes Device Compatibility. This module must be used in a series B I/O chassis. The 1771-IQ16 is not compatible with the 1771-AL local I/O adapter.This module contains customer-selectable input filter times to limit the effects of voltage transients caused by contact bounce and/or radiated electrical noise. The delay due to filtering ranges from 0msec to 18.0ms for turning dc inputs on to off. Delay for turning dc inputs off to on is 1.0ms. The filter time is factory set to 1.0ms. This module is designed to operate with dc limit switches, float switches, selector switches, proximity switches and pushbutton switches.The module can be used as either a sink or source input based on the wiring configuration of the load. Connection to Output Modules. You can use an output of the dc (10-32V) output module (1771-OQ16) to drive an input of a dc (10-32V) input module (1771-IQ16) to indicate status of turning on a motor starter, for example. The configuration shown has the output of the 1771-OQ16 wired as a source, and the input on the 1771-IQ16 wired as a sink. Status Indicators. The module has 17 indicators, consisting of 16 input status indicators and an active indicator. The 16 status indicators are provided for system logic side indication of individual inputs. The active indicator will light when the module has successfully started up and initialized.
Connection Diagram dc Return
Switch sinks current
Gnd - 0 Gnd - 1 Gnd - 2 Gnd - 3 Not Used Gnd - 4 Gnd - 5 Gnd - 6 Gnd - 7 Not used Gnd - 10 Gnd - 11
2
Gnd - 12 Gnd - 13 Not used Gnd - 14 Gnd - 15 Gnd - 16 Gnd - 17
26
Not used
40
4 6 8 10 12 14 16 18 20 22 24 28 30 32 34 36 38
Input 0 Input 1 Input 2 Input 3 Not used Input 4 Input 5 Input 6 Input 7 Not used Input 10 Input 11 Input 12 Input 13 Not used Input 14 Input 15 Input 16 Input 17 Not used
Module sources current dc High
+
24V dc Supply
24V dc Supply
-
DC Return
(Actual wiring runs in this direction.)
Source Configuration
Alternate switch position - switch sources current; module sinks current. 10562-I
Publication 1771-2.180 - July 1996