Installation Instructions
Contact Output Module (Catalog Number 1771–OWNA) Contents
Use this document as a guide when installing the catalog number 1771-OWNA series B contact output module. To
Important User Information Preinstallation Considerations
See page 1 4
Power Supply Requirements Key the Backplane Connector
4 5
Install the Module and Field Wiring Arm
6
Connect Wiring to the Field Wiring Arm
7
For this reference information Interpreting the Status Indicators Hazardous Location Approval Specifications
Important User Information
See page 11 12 13
Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Rockwell Automation be responsible or liable for indirect or consequential damage resulting from the use or application of these products. Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication. Allen–Bradley publication SGI–1.1, Safety Guidelines for Application, Installation, and Maintenance of Solid–State Control (available from your local Rockwell Automation office), describes some important differences between solid–state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Publication 1771-IN038B-EN-P - August 2002
Page 2
2
Contact Output Module
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited. Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard.
WARNING
! ATTENTION
!
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information about practices or circumstances that may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for IMPORTANT successful application and understanding of the product.
Publication 1771-IN038B-EN-P - August 2002
Page 3
Contact Output Module
ATTENTION
!
3
Environment and Enclosure This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664–1), at altitudes up to 2000 meters without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as “open type” equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present, and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosures. Also, see the appropriate sections in this publication, as well as the Allen–Bradley publication 1770–4.1, (“Industrial Automation Wiring and Grounding Guidelines”), for additional installation requirements pertaining to this equipment.
Publication 1771-IN038B-EN-P - August 2002
Page 4
4
Contact Output Module
ATTENTION
!
PreĆinstallation Considerations
Preventing Electrostatic Discharge This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • If available, use a static–safe workstation. • When not in use, keep modules in appropriate static–safe packaging.
This module must be used in a 1771-A1B through -A4B or later I/O chassis.This module does not contain surge limiting circuitry. Use this module for switching resistive loads only. It is not recommended for inductive or capacitive loads. The outputs are arranged in 4 groups of 8, each group with its own common. The module can simultaneously switch all 32 outputs to separate loads, with a maximum of 12A per module. Each output can conduct a maximum load of 1.0A continuously at 30W at 45oC, and 15W at 60oC maximum. Ac loads switched by the modules should have a power factor (PF) of 1.0. Maximum interconnect cable length for this module is 1000 ft. (304.8 meters).
Power Supply Requirements
Publication 1771-IN038B-EN-P - August 2002
The controller or I/O chassis power supply, connected through the backplane of the I/O chassis, powers the logic circuitry of the contact output modules. This supply also provides the necessary power to energize the coils of the module relays. The maximum current drawn from this supply when all coils are energized is 2.5A. Nominal backplane current is 1.8A.
Page 5
5
Contact Output Module
Key the Backplane Connector
Position the keying bands in the backplane connectors to correspond to the key slots on the module. Place the keying bands: - between 6 and 8 - between 16 and 18
Place your module in any slot in the chassis except the leftmost slot which is reserved for processors or adapters. ATTENTION Observe the following
!
precautions when inserting or removing keys:
• insert or remove keys with your fingers • make sure that key placement is correct Incorrect keying or the use of a tool can result in damage to the backplane connector and possible system faults.
Upper Connector
I/O chassis
You can change the position of these bands if subsequent system design and rewiring makes insertion of a different type of module necessary.
11022-I
Publication 1771-IN038B-EN-P - August 2002
Page 6
6
Contact Output Module
Install the Module and Field Wiring Arm
Remove power from the 1771 I/O chassis backplane before you install the module. Failure to remove power from the backplane could cause:
ATTENTION
!
• module damage • degradation of performance • injury or equipment damage due to possible unexpected operation When you insert or remove the module with field power applied, or connect or disconnect the field wiring arm with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.Be sure that power is removed or the area is nonhazardous before proceeding.
WARNING
!
the module in the card guides on the top and bottom of the chassis 1 Place that guide the module into position.
Important: Apply firm even pressure on the module to seat it into its backplane connector.
1771-A1B, ĆA2B, ĆA3B, ĆA4B I/O chassis
1771-A1B, ĆA2B, ĆA4B Series B I/O chassis Swing the chassis locking bar down into place to secure the modules. Make sure the locking pins engage.
Snap the chassis latch over the top of the module to secure it.
the wiring arm (1771-WN) to the horizontal bar at the 2 Attach bottom of the I/O chassis.
The wiring arm pivots upward and connects with the module so you can install or remove the module without disconnecting the wires.
1771-WN remove horizontal bar install
The 1771–OWNA module is a modular component of the 1771 I/O system requiring a properly installed system chassis. Refer to publication 1771–IN075 for detailed information on acceptable chassis, proper installation and grounding requirements. Limit the maximum adjacent slot power dissipation to 10W maximum.
Publication 1771-IN038B-EN-P - August 2002
Page 7
Contact Output Module
Connect Wiring to the Module
7
Make wiring connections to the module through the field wiring arm (cat. no. 1771-WN). The arm pivots on the I/O chassis to connect with terminals on the front of the module and acts as a terminal strip. The wiring arm allows the module to be removed from the chassis without disconnecting wiring. WARNING
!
When you connect or disconnect the field wiring arm with field power applied, or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION
!
Remove power from the 1771 I/O chassis backplane and field wiring arm before removing or installing an I/O module.
• Failure to remove power from the backplane or wiring arm could cause module damage, degradation of performance, or injury. • Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.
1. Make certain all power is removed from the module before making wiring connections. 2. Swing the wiring arm up into position on the front of the module. The locking tab on the module will secure it into place.
Publication 1771-IN038B-EN-P - August 2002
Page 8
8
Contact Output Module
3. Make your connections to the field wiring arm as shown in the connection diagram and Table A. (Use the label on the front of the wiring arm to identify your wiring.) The field wiring arm terminal identification IMPORTANT number is not the same as the number of the bit which controls that output.
Connection Diagram for the 1771-OWNA DC Output Module
Output 0 Output 2
2
Output 4 Output 6 Not used
6
Output 10
12
Output 12
14
Output 14
16
Common 0 Output 1 Output 3 Output 5
4 8
Output 7
10
Output 16
18
Not used
20
Output 0
22
Output 2
24
Output 4
26
Output 6 Not used Output 10
28
Output 12
34
Output 14
36
Output 16
38
Not used
40
Common 1 Output 11 Output 13 Output 15 Output 17 Common 2 Output 1 Output 3 Output 5 Output 7 Common 3
30 32
Output 11 Output 13 Output 15 Output 17
Note: All contacts are N.O., nonselectable.
Note: Terminals on the left are even numbered, and terminals on the right are odd numbered. (Actual wiring runs in this direction.)
If multiple power supplies are used, do not exceed the maximum isolation voltage.
ATTENTION
! Publication 1771-IN038B-EN-P - August 2002
Miswiring or shorting the output terminals will cause permanent damage to this module.
10539-I