Page 1 of Installation Instructions: Contact Output Module (Catalog Number 1771-OWNA)

Manual · Allen-Bradley

Installation Instructions: Contact Output Module (Catalog Number 1771-OWNA)

Manual16 pagesPDF 224 KB

Installation instructions for the Allen-Bradley 1771-OWNA series B 32-output contact output module for the 1771 I/O system.

What this file really is

The old site listed this file as “Install Manual” for the Allen-Bradley 1771-OW. Linked as the 1771-OW install manual, but it is the installation instructions for the 1771-OWNA series B contact output module and does not name the 1771-OW.

Download the PDF224 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

Rockwell Automation's installation instructions for the Allen-Bradley 1771-OWNA series B contact output module. It covers preinstallation considerations, power supply requirements, keying the backplane connector, installing the module and the 1771-WN field wiring arm, wiring connections with a terminal table, driving a 120V ac input module from an output, reading the status indicators, hazardous location approval and specifications.

Its parts

  1. Important User Information
  2. Preinstallation Considerations
  3. Power Supply Requirements
  4. Key the Backplane Connector
  5. Install the Module and Field Wiring Arm
  6. Connect Wiring to the Field Wiring Arm
  7. Interpreting the Status Indicators
  8. Hazardous Location Approval
  9. Specifications

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Installation instructions (publication 1771-IN038B-EN-P) for the Allen-Bradley 1771-OWNA series B contact output module, a 32-output relay module for the 1771 I/O system. The document names only the 1771-OWNA, not the 1771-OW the site files it under. It walks through keying, installing the module and its 1771-WN field wiring arm, wiring, the status indicators and the specifications.

What it is
1771-OWNA series B contact output module for the 1771 I/O system p. 1
Outputs
32, in 4 groups of 8, each group with its own common; contacts N.O. p. 4, 8
Voltage rating
24 to 138V ac rms; 24 to 125V dc p. 13
Current rating
1.0A continuous per output; 12A per module p. 4
Contact power
30W per output (resistive) max at 45°C, 15W at 60°C p. 13
Chassis
1771-A1B through -A4B or later, 1771-AM, -AM1 I/O chassis p. 13
Field wiring arm
1771-WN; screw torque 9 pound-inches (1.0Nm) p. 14
Backplane current
2.5A maximum; 1.8A nominal p. 13
Keying
Between 6 and 8; between 16 and 18 p. 14
Minimum contact load
10mA p. 13
Operating temperature
0 to 60°C (32 to 140°F) p. 13
Conductors
14-22 AWG (2.5-0.5mm2) stranded copper rated 60°C or greater; 3/64 inch (1.2mm) insulation max p. 13
Interconnect cable
1000 ft. (304.8 meters) max p. 4
Operate/release time
5ms (+1ms) typical p. 13

What this manual walks you through

  • Keying the backplane connector p. 5
  • Wiring the outputs to the field wiring arm p. 7, 8, 9
  • Driving a 120V ac input module from an output p. 10
  • Reading the status indicators p. 11
  • What the manual states about use in hazardous locations p. 12
  • Specifications p. 13, 14

Good to know

  • The module has no surge limiting and is for resistive loads only, not inductive or capacitive loads. p. 4
  • Do not wire two or more outputs in parallel to raise the current or wattage rating. p. 10
  • The leftmost chassis slot is reserved for processors or adapters. p. 5
  • Wiring arm terminal numbers are not the same as the bit numbers that control the outputs. p. 8
  • Limit power dissipation in the adjacent slot to 10W maximum. p. 6

Questions this manual answers

Which chassis does the 1771-OWNA fit?

The specifications list 1771-A1B through -A4B or later I/O chassis and the 1771-AM and -AM1 chassis. p. 13

Can the 1771-OWNA switch inductive loads?

The instructions say to use it for resistive loads only; it is not recommended for inductive or capacitive loads. p. 4

What wiring arm goes with the 1771-OWNA?

The 1771-WN field wiring arm, which lets the module be removed without disconnecting the wiring. p. 7

What do the lights on the 1771-OWNA mean?

Each of the 32 indicators lights when its output is energized, and one more indicator shows a blown fuse condition. p. 11

How much backplane current does the 1771-OWNA draw?

Up to 2.5A with all relay coils energized; 1.8A nominal. p. 4

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16

The file

Revision and size

Part no.1771-IN038B-EN-P
RevisionAugust 2002