Summary
What is in it
Rockwell Automation's installation instructions for the Allen-Bradley 1771-OWNA series B contact output module. It covers preinstallation considerations, power supply requirements, keying the backplane connector, installing the module and the 1771-WN field wiring arm, wiring connections with a terminal table, driving a 120V ac input module from an output, reading the status indicators, hazardous location approval and specifications.
Its parts
- Important User Information
- Preinstallation Considerations
- Power Supply Requirements
- Key the Backplane Connector
- Install the Module and Field Wiring Arm
- Connect Wiring to the Field Wiring Arm
- Interpreting the Status Indicators
- Hazardous Location Approval
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation instructions (publication 1771-IN038B-EN-P) for the Allen-Bradley 1771-OWNA series B contact output module, a 32-output relay module for the 1771 I/O system. The document names only the 1771-OWNA, not the 1771-OW the site files it under. It walks through keying, installing the module and its 1771-WN field wiring arm, wiring, the status indicators and the specifications.
- What it is
- 1771-OWNA series B contact output module for the 1771 I/O system p. 1
- Outputs
- 32, in 4 groups of 8, each group with its own common; contacts N.O. p. 4, 8
- Voltage rating
- 24 to 138V ac rms; 24 to 125V dc p. 13
- Current rating
- 1.0A continuous per output; 12A per module p. 4
- Contact power
- 30W per output (resistive) max at 45°C, 15W at 60°C p. 13
- Chassis
- 1771-A1B through -A4B or later, 1771-AM, -AM1 I/O chassis p. 13
- Field wiring arm
- 1771-WN; screw torque 9 pound-inches (1.0Nm) p. 14
- Backplane current
- 2.5A maximum; 1.8A nominal p. 13
- Keying
- Between 6 and 8; between 16 and 18 p. 14
- Minimum contact load
- 10mA p. 13
- Operating temperature
- 0 to 60°C (32 to 140°F) p. 13
- Conductors
- 14-22 AWG (2.5-0.5mm2) stranded copper rated 60°C or greater; 3/64 inch (1.2mm) insulation max p. 13
- Interconnect cable
- 1000 ft. (304.8 meters) max p. 4
- Operate/release time
- 5ms (+1ms) typical p. 13
What this manual walks you through
- Keying the backplane connector p. 5
- Wiring the outputs to the field wiring arm p. 7, 8, 9
- Driving a 120V ac input module from an output p. 10
- Reading the status indicators p. 11
- What the manual states about use in hazardous locations p. 12
- Specifications p. 13, 14
Good to know
- The module has no surge limiting and is for resistive loads only, not inductive or capacitive loads. p. 4
- Do not wire two or more outputs in parallel to raise the current or wattage rating. p. 10
- The leftmost chassis slot is reserved for processors or adapters. p. 5
- Wiring arm terminal numbers are not the same as the bit numbers that control the outputs. p. 8
- Limit power dissipation in the adjacent slot to 10W maximum. p. 6
Questions this manual answers
Which chassis does the 1771-OWNA fit?
The specifications list 1771-A1B through -A4B or later I/O chassis and the 1771-AM and -AM1 chassis. p. 13
Can the 1771-OWNA switch inductive loads?
The instructions say to use it for resistive loads only; it is not recommended for inductive or capacitive loads. p. 4
What wiring arm goes with the 1771-OWNA?
The 1771-WN field wiring arm, which lets the module be removed without disconnecting the wiring. p. 7
What do the lights on the 1771-OWNA mean?
Each of the 32 indicators lights when its output is energized, and one more indicator shows a blown fuse condition. p. 11
How much backplane current does the 1771-OWNA draw?
Up to 2.5A with all relay coils energized; 1.8A nominal. p. 4