Manual · Allen-Bradley
1771 Digital I/O Relay Contact Output Modules
Manual32 pagesPDF 1.3 MB
Product data for the Allen-Bradley 1771 relay contact output modules, including the 1771-OW with eight selectable outputs.
Covers · 1 model
The models it covers
Summary
What is in it
Allen-Bradley product data publication for the 1771 relay contact output modules: 1771-OW, -OW16, -OWN, -OWNA, -OX, -OYL and -OZL. A general section covers relay types, chassis compatibility, power supply requirements, keying, status indicators, application considerations such as contact life, RC snubbers and lamp loads, output loading graphs, EU directives and agency certification. A second section gives module-specific information for each model, including the 1771-OW.
Its parts
- Benefits
- Using This Publication
- Relay Types
- System Compatibility
- Power Supply Requirements
- Keying
- Status Indicators
- Application Considerations
- Output Module Loading
- Compliance to European Union Directives
- Agency Certification
- Module Information
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Allen-Bradley publication 1771-2.181 on 1771 digital I/O relay contact output modules: the 1771-OW, -OW16, -OWN, -OWNA, -OX, -OYL and -OZL. A general section explains relay types, chassis compatibility, keying, snubbers and the operating range graphs, and each module then has its own pages with a schematic, wiring and specifications. The module facts here come from the 1771-OW pages.
- What it is
- 1771-OW: relay contact output module with eight outputs, each set N.O. or N.C. by a jumper, preset N.O. at the factory p. 1, 15
- Outputs
- 1771-OW: 8, in 4 groups of 2, each group with its own common p. 15
- Voltage rating
- 1771-OW: 24 - 138V ac rms; 24 - 125V dc p. 16
- Current rating
- 1771-OW: 1A per output (maximum) p. 16
- Power rating
- 1771-OW: 30W per output (resistive), dc and suppressed ac p. 16
- Field wiring arm
- 1771-OW: 1771-WD; screw torque 7-9 inch-pounds p. 16
- Backplane current
- 1771-OW: 700mA maximum p. 16
- Isolation voltage
- 1771-OW: 1000V between open contacts; 1500V between coil and contact p. 16
- Switching
- 1771-OW: 10Hz maximum; bounce time 1ms maximum p. 16
- Minimum load
- 1771-OW: at least 10mA for reliable operation p. 15
- Relay type
- Electromechanical in the 1771-OW, -OW16, -OWN and -OWNA; dry-reed in the -OYL and -OZL; mercury-wetted in the -OX p. 3
- Inputs it can drive
- 1771-OW: ac inputs 1771-IA, -IA2, -IAD, -IAN, -ID, -ID16, -IN, -IND; dc inputs 1771-IB, -IBD, -IBN, -IH, -IQ, -IQ16, -IT, -IV, -IVN p. 15
- Snubber parts
- 5%, 1 Watt carbon composition resistor; capacitor ac rating above the maximum voltage across the contacts p. 6
- Installation data
- 1771-OW: publication 1771-2.110 p. 29
What this manual walks you through
- Choosing between electromechanical, dry-reed and mercury-wetted relays p. 3
- Chassis compatibility, power supply loading and keying p. 4
- Relay life, response time and capacitive loading of long cables p. 5
- Sizing an RC snubber network across the contacts p. 6
- Derating for incandescent lamp loads p. 7
- Checking a load against the operating range graphs p. 7, 8
- Setting the 1771-OW output jumpers for N.O. or N.C. p. 15
- Driving an input module with a 1771-OW output p. 15, 16
- European Union directives the modules are tested to p. 12
Good to know
- The 1771-OW has no surge limiting and is for resistive loads only, such as lamps, indicators and heating elements. p. 15
- Do not wire outputs in parallel to raise the current or wattage rating. p. 15
- The 1771-OW, -OW16, -OWN, -OWNA, -OYL and -OZL are not UL/CSA approved for reactive loads. p. 6
- Electromechanical relays are not sealed and are not recommended where acid, ammonia, nitrogen or chlorine are present. p. 3
- Do not run a contact at low current or voltage after running it at high power; run low power first. p. 5
Questions this manual answers
Can 1771-OW outputs be normally closed?
Yes. Each output is set N.O. or N.C. by its own jumper; they come preset normally open. p. 15
What wiring arm does the 1771-OW use?
The 1771-WD field wiring arm, with a screw torque of 7-9 inch-pounds. p. 16
How much current can a 1771-OW output switch?
Up to 1A per output; keep at least 10mA of load current for reliable operation. p. 15, 16
What is the difference between the 1771-OW and the 1771-OWNA?
The 1771-OW has eight selectable outputs; the 1771-OWNA has 32 non-selectable normally-open contacts. p. 1
Do I need a snubber on a 1771 relay output?
The manual recommends an RC network across the contacts in all circuits, placed at the field wiring arm terminals. p. 6
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-2.181, Digital I/O Relay Contact Output Modules1
- Benefits2
- Using This Publication2
- Relay Types3
- System Compatibility4
- Power Supply Requirements4
- Keying4
- Status Indicators4
- Application Considerations5
- Output Module Loading7
- Compliance to European Union Directives12
- Agency Certification12
- Module Information13
- Support Services31
- Back Cover32
The whole text · 6 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file