Page 26

26

0-24V Relay Contact Output Module (Cat. No. 1771-OYL)

--" Outputs per Module

8 (4 groups of 2)

Module Location

1771 I/O chassis

Contact Configuration

4 Form A (N.O.), 4 Form B (N.C.)

Voltage Rating

0-24V ac rms; 0-24V dc

Current Rating1

100mA per output (maximum)

Surge Current

100mA maximum per output2 (at rated power)

Power Rating dc: 2.4W per output (resistive) ac (suppressed)2: 2.4W per output (resistive)

Minimum Contact Load dc: 1mA @ 0-24V ac: 1mA @ 0-24V

--"

0-24V Contact Output Module (Cat. No. 1771-OYL)

L1 ac High Output 0

1

Common

2

Output 1

3

Operate/Release Time

1ms maximum

Bounce Time

1ms maximum

Switching Frequency

10Hz maximum

Output 2

4

Power Dissipation

2.2 Watts (max.), 2 Watts (min.)

Common

5

Thermal Dissipation

7.6 BTU/hr (max.), 6.9 BTU/hr (min.)

Output 3

6

Backplane Current

420mA maximum

Output 4

7

Isolation Voltage

1000V between open contacts 1500V between coil and contact

Common

8

Output 5

9

Output 6

10

Common

11

Output 7

12

Conductors

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13

Wire Size Category

Environmental Conditions Operating Temperature Storage Temperature Relative Humidity

3

Input 00

5 to 95% (without condensation) Between 6 and 8 Between 16 and 18

Field Wiring Arm

1771-WD

Wiring Arm Screw Torque

1 2

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)

Keying

Agency Certification (when product or packaging is marked)

10-30V ac Input Module (Cat. No. 1771-IND)

L2 ac Low

4 5

01 02 03 04

6

05 06 07 10 11 12 13 14 15 16 17

10

7 8 9

11 12 13 14 15 16 17 18 19 20 21

7-9 inchĆpounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-2.184

1 Spikes, peaks, and surges must be within the power rating. Resistive loads only. ac or dc power = 2.4W maximum

2 Surge limiting circuitry is not provided in the module. For reliable operation, the use must ensure that surges do not exceed either the voltage or current rating of the module.

3 You use this conductor category information for planning conductor routing as described in the system level installation manual.

Publication 1771-2.181 - September 1997

10522-I

Page 27

0-24V Relay Contact Output Module (Cat. No. 1771-OZL)

27

0-24V Relay Contact Output Module (Cat. No. 1771-OZL)

+5V

Output Indicator

Backplane Logic Circuitry

Relay Driver

1771-OZL modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). The 1771-OZL module has 8 normallyĆopen (Form A) relays.The outputs are arranged in 4 groups of 2, each with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 100mA continuously, at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OZL module to drive an ac input module up to 24V ac. The 1771-OYL module can drive an input of the following dc modules: 1771-IB, ĆIBD, ĆIBN, ĆIG, ĆIGD,ĆIH, ĆIN, ĆIND, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel.The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.

+

Common

-

Normally open Output

To next output (next output is normally open)

10523-I

Internal circuits

Field connections +12V ac L2

L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7

Output Device

1 2 3 4 5 6 7 8 9

Output Device

10 11 12

Common

+24V dc +dc

(Actual wiring runs in this direction.) 10524-I

Publication 1771-2.181 - September 1997

Page 28

28

0-24V Relay Contact Output Module (Cat. No. 1771-OZL)

--" Outputs per Module

8 (4 groups of 2)

Module Location

1771 I/O chassis

Contact Configuration

8 Form A (N.O.)

Voltage Rating

0-24V ac rms 0-24V dc

Current Rating1

100mA per output (maximum)

Surge Current

100mA maximum per output2 (at rated power)

Power Rating dc: 2.4W per output (resistive) ac (suppressed)2: 2.4W per output (resistive)

Minimum Contact Load dc: 1mA @ 0-24V ac: 1mA @ 0-24V

Operate/Release Time

1ms maximum

Bounce Time

1ms maximum

Switching Frequency

--"

0-24V Contact Output Module (Cat. No. 1771-OZL)

L1 ac High Output 0

1

Common

2

Output 1

3

Output 2

4

10Hz maximum

Common

5

Power Dissipation

2.2 Watts (max.), 2 Watts (min.)

Output 3

6

Thermal Dissipation

7.6 BTU/hr (max.), 6.9 BTU/hr (min.)

Output 4

7

Backplane Current

420mA maximum

Common

8

Isolation Voltage

1000V between open contacts 1500V between coil and contact

Output 5

9

Output 6

10

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13

Common

11

Output 7

12

Conductors

Wire Size Category

Environmental Conditions Operating Temperature Storage Temperature Relative Humidity

5 to 95% (without condensation) Between 6 and 8 Between 16 and 18

Field Wiring Arm

1 2 3

Input 00

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)

Keying

L2 ac Low

4 5

01 02 03 04

6

05 06 07 10 11 12 13 14 15 16 17

10

7 8 9

11 12 13 14 15 16 17 18 19 20 21

1771-WD

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

10-30V ac Input Module (Cat. No. 1771-IND)

7-9 inchĆpounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-2.129

1 Spikes, peaks, and surges must be within the power rating. Resistive loads only.

ac or dc power = 2.4W max

2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure that surges do not exceed either the voltage or current rating of the module.

3 You use this conductor category information for planning conductor routing as described in the system level installation manual.

Publication 1771-2.181 - September 1997

10525-I

Page 29

Related Publications

29

You can refer to the following publications for more information about Allen-Bradley relay contact modules and other Allen-Bradley discrete I/O modules:

- -

1771-OW module

Selectable Contact Output Module (cat. no. 1771-OW) Installation Data

1771-2.110

1771-OW16 module

Selectable Contact Output Module (cat. no. 1771-OW16) Installation Data

1771-2.206

1771-OWN module

Contact Output Module (cat. no. 1771-OWN) Installation Data

1771-5.37

1771-OWNA module

Contact Output Module (cat. no. 1771-OWNA) Installation Data

1771-5.38

1771-OX module

Power Contact Output Module (cat. no. 1771-OX) Installation Data

1771-2.43

1771-OYL module

0-24V Contact Output Module (cat. no. 1771-OYL) Installation Data

1771-2.134

1771-OZL module

0-24V Contact Output Module (cat. no. 1771-OZL) Installation Data

1771-2.129 all Allen-Bradley 1771 digital I/O modules

1771 Universal Discrete I/O Modules Selection Guide

1771-1.25

Allen-Bradley dc solid state digital I/O modules

1771 Digital dc Solid State I/O Modules Product Data

1771-2.180

Allen-Bradley ac solid state digital I/O modules

1771 Digital ac Solid State I/O Modules Product Data

1771-2.182

Allen-Bradley analog I/O modules

1771 Analog I/O Modules Product Data

1771-2.183

Publication 1771-2.181 - September 1997

Page 30 read from a scan by OCR; it may hold reading errors

30 Notes

Notes

Publication 1771-2.181 - September 1997

Page 31

Support Services

-

31

At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:

- - • • • •

SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services

• • • • application engineering assistance integration and start-up assistance field service maintenance support

- • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis

• • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support

Page 32

PLC is a registered trademark of Allen-Bradley Company, Inc. PLC-2 is a trademark of Allen-Bradley Company, Inc. PLC-3 is a trademark of Allen-Bradley Company, Inc. PLC-5 is a trademark of Allen-Bradley Company, Inc. SLC is a trademark of Allen-Bradley Company, Inc.

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.

Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia

Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 1771-2.181 - September 1997 Supersedes Publication 1771-2.181 - March 1993

Copyright 1997 Allen-Bradley Company, Inc. Printed in USA