The text of a manual · part 5 of 6

1771 Digital I/O Relay Contact Output Modules, pages 19 to 25

Pages 19 to 25 of 32

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OW

Page 19

Selectable Relay Contact Output Module (Cat. No. 1771-OWN)

-

19

+5V Common Normally closed Output Indicator

Backplane Logic Circuitry

Output Normally open

Relay Driver To next output

10512-I

1771-OWN modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OWN module are arranged in 4 groups of 8, each group with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 32 outputs to separate loads, with a maximum of 12A per module. Each output can conduct a maximum load of 1.0A continuously at 30W maximum. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OWN module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OWN module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current. When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting. All outputs are individually selectable for either normallyĆopen or normallyĆclosed operation. They are preset for normallyĆopen operation at the factory. See next page for relay output jumper settings.

Common 0 Output 1 3

Output 0 2

2

4 6

6

5

8

7

Not used

10

10

12

12 14

14 16

16

15

18

17

Not used 0 2 4

20

26

6

5

28

7

Not used

30

10

32

12

34

14 16 Not used

36

15

38

17

4

22 24

Common 1 11 13

Common 2 1 3

Common 3 11 13

40

Note: Terminals on the left are even numbered, and terminals on the right are odd numbered. (Actual wiring runs in this direction.) Note: Contacts shown in N.O. configuration for simplicity.

10513-I

Publication 1771-2.181 - September 1997

Page 20

20

Selectable Relay Contact Output Module (Cat. No. 1771-OWN)

# Outputs per module

32 (4 groups of 8)

Module Location

1771-A1B thru -A4B, 1771-AM1, ĆAM2 Chassis

Voltage Rating

24 - 138V ac rms; 24 - 125V dc

Current Rating1 Max. per output Max. per module Max. per group

1A derate linearly .033A/°C above 45°C 12A derate linearly .4A/°C above 45°C 4A derate linearly .133A/°C above 45°C

Surge Current

1A (max) per output (at rated power)2

Power Rating dc: 30W per output (resistive) maximum ac: 30W per output (resistive) maximum

Minimum Contact Load

10mA

Operate/Release Time

5ms (+1ms) typical

Bounce Time

1ms (max)

Switching Frequency

10Hz (max)

Power Dissipation

All relays off: 15mW; All relays on: 12.5W (max.)

Thermal Dissipation

All relays off: 0.05 BTU/hr; All relays on: 42.75 BTU/hr (max.)

Backplane Current

2.5A maximum; 1.8A nominal

Isolation Voltage

1000V between open contacts 1500V between coil and contact

Interconnect Cable Length

1000 ft. (304.8 meters) max

Category

14 gauge (2mm2) stranded (max) 3/64 inch (1.2mm) insulation (max) 13

Environmental Conditions Operational Temp. Storage Temperature Relative Humidity

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)

Conductors Wire Size

Keying

Between 6 and 8 Between 16 and 18

0 2 4 6 Not used 10 12 14 16 Not used 0 2 4 6 Not used 10 12 14 16 Not used

Common 0 1 3 5 7 Common 1 11 13 15K ohms 2W 15 17 Common 2 1 3 5 7 Common 3 11 13 15 17

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

120V ac Input Module (Cat. No. 1771-IAD)

2 3

Input 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

L2 ac Low 10514-I

& $# N.C.

RY1

L-06

L-04

L-02

L-00

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

N.O.

7-9 inchĆpounds

Installation Data

L1 ac High

1

1771-WN

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

Selectable Contact Output Module (Cat. No. 1771-OWN)

RY2

N.C.

Field Wiring Arm

- $#

N.O.

Normally Open

1771-5.37

1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.

2 Surge limiting circuitry is not provided in the module. For reliable operation, the user

N.C.

must ensure that surges do not exceed either the voltage or current rating of the module.

3 You use this conductor category information for planning conductor routing as described in the system level installation manual.

RY9

$#

Outputs 00 - 07

L-00 - L-07

Outputs 10 - 17

L-10 - L-17

Outputs 20 - 27

H-00 - H-07

Outputs 30 - 37

H-10 - H-17

RY10

N.O.

Normally Closed

Printed Circuit Board 10554-I

Publication 1771-2.181 - September 1997

Page 21

Relay Contact Output Module (Cat. No. 1771-OWNA)

21

+5V

Normally open Output

Output Indicator Backplane Logic Circuitry

Common Relay Driver To next output 10515-I

1771-OWNA modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OWNA module are arranged in 4 groups of 8, each group with its own common. The module can simultaneously switch all 32 outputs to separate loads, with a maximum of 12A per module. Each output can conduct a maximum load of 1.0A continuously at 30W maximum. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OWNA module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OWNA module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.

(showing internal circuits only)

Output 0 2

2 4

Common 0 1 3

4 6

6

5

8

7

Not used

10

10

12

12 14

14 16

16

15

18

17

Not used 0 2 4

20

26

6

5

28

7

Not used

30

10

32

12

34

14 16 Not used

36

15

38

17

22 24

Common 1 11 13

Common 2 1 3

Common 3 11 13

40

Note: All contacts are N.O, nonĆselectable. (Actual wiring runs in this direction.) 10516-I

Publication 1771-2.181 - September 1997

Page 22

22

Relay Contact Output Module (Cat. No. 1771-OWNA)

Outputs per module

32 (4 groups of 8)

Module Location

1771-A1B thru -A4B, and 1771-AM1, ĆAM2 I/O Chassis

Voltage Rating

24 - 138V ac rms 24 - 125V dc

Current Rating1 Max. per output Max. per module Max. per group

1A derate linearly .033A/°C above 45°C 12A derate linearly .4A/°C above 45°C 4A derate linearly .133A/°C above 45°C

Surge Current

1A (max) per output (at rated power)2

Power Rating dc: 30W per output (resistive) maximum ac: 30W per output (resistive) maximum

Minimum Contact Load

10mA

Operate/Release Time

5ms (+1ms) typical

Bounce Time

1ms (max)

Switching Frequency

10Hz (max)

Power Dissipation

All relays OFF: 15mW; All relays ON: 12.5W (max.)

Thermal Dissipation

All relays OFF: 0.05 BTU/hr; All relays ON: 42.75 BTU/hr (max.)

Backplane Current

2.5A maximum; 1.8A nominal

Isolation Voltage

1000V between open contacts 1500V between coil and contact

Interconnect Cable Length Conductors Wire Size Category Environmental Conditions Operating Temperature Storage Temperature Relative Humidity

1000 ft. (304.8 meters) max 14 gauge (2mm2) stranded (max) 3/64 inch (1.2mm) insulation (max) 13 0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)

Keying

Between 6 and 8 Between 16 and 18

Field Wiring Arm

Cat. No. 1771-WN

Wiring Arm Screw Torque

7-9 inchĆpounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-5.38

1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.

2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure that surges do not exceed either the voltage or current rating of the module.

3 You use this conductor category information for planning conductor routing as described in the system level installation manual.

Publication 1771-2.181 - September 1997

Contact Output Module (Cat. No. 1771-OWNA)

0 2 4 6 Not used 10 12 14 16 Not used 0 2 4 6 Not used 10 12 14 16 Not used

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

Common 0 1 3 5 7 Common 1 11 13 ohms 15 15K2W 17 Common 2 1 3 5 7 Common 3 11 13 15 17

120V ac Input Module (Cat. No. 1771-IAD) L1 ac High 1 2 3

Input 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

L2 ac Low 10517-I

Page 23

Power Relay Contact Output Module (Cat. No. 1771-OX)

23

+5V

Output Indicator

Common +

N.C. Jumpers Backplane Logic Circuitry

1K .47µF

Relay Driver

Surge Suppressor Jumper

N.O. Jumpers

MOV 275V

Output N.O./N.C. -

7A Fuse

10518-I

-

The 1771-OX module contains mercuryĆwetted relays. Handle the module carefully and avoid excessive vibration. This can cause damage to the glass bulb which houses the mercury and contacts. Failure to observe this caution may cause damage to the module's circuitry. The power contact output module be mounted within 30° of vertical for the mercuryĆwetted relays to function. After installation, wait 3 minutes, or manually operate the relays 16 times, before powering up the module in an actual application. The 1771-OX module includes a selectable RC network for switching dc voltages. When switching these voltages, include the onĆboard surge suppression. When switching inductive ac voltages, you must supply an external rc network as close as possible to the load terminals. These are listed below. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.

0 1

2

3 4

-%

120V ac

2-5

68

0.1

8mA

RG 1782-4

240V ac

2-5

270

0.027

4.5mA

120V ac

2-5

68

0.1

8mA

240V ac

2-5

270

0.027

4.5mA

120V ac

2-3

68

0.1

8mA

RG 1782-4

120V ac

4-5

47

0.1

8mA

RG 1782-3

240V ac

2-3

270

0.027

4.5mA

240V ac

4-5

180

0.047

7.5mA

120V ac

2-3

47

0.1

8mA

RG 1782-4

Internal circuits

Common 0+ NO/NC 0-

Field connections

A

User Power Supply

0

Common 1+ NO/NC 1-

1 2

Not used

3

Not used

4

Common 2+ NO/NC 2Common 3+ NO/NC 3-

Load

5 6 7 B

Note: Contacts shown in N.O. configuration for simplicity. (Actual wiring runs in this direction.) 10519-I

RG 1782-3

240V ac

2-3

150

0.047

8mA

240V ac

4-5

100

0.1

16mA

RG 1782-6

240V ac

2-3

100

0.1

16mA

RG 1782-6

Publication 1771-2.181 - September 1997

Page 24

24

Power Relay Contact Output Module (Cat. No. 1771-OX)

Outputs per Module

4 N.O/N.C.

Module Location

1771 I/O chassis

Voltage Rating

0-250V ac rms; 0-175V dc

Current Rating

2A (maximum)

Surge Current (Repeatable every 10 seconds)

5.5A ac peak for 5 seconds 6A dc for 5 seconds 15A dc for 500ms

Power Rating

200VA

On-state Contact Resistance

0.25 ohms maximum

Operate/Release Time

10ms maximum

Power Dissipation

2.9 Watts (max.), 2.6 Watts (min.)

Thermal Dissipation

9.9 BTU/hr (max.), 8.9 BTU/hr (min.)

Backplane Current

550mA maximum

Isolation Voltage Conductors

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11

Category Environmental Conditions Operating Temperature Storage Temperature Relative Humidity

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)

NO

NO

JPR 4 JPR 5

JPR 9 JPR 10

DC

DC

JPR 6

AC

JPR 11

AC

K1 Output 0

JPR 15 JPR 16

JPR 20 JPR 21

NC

NC

NO

NO

JPR 17 JPR 18

JPR 22 JPR 23

DC

DC

JPR 19

AC

K4 Output 3

JPR 24

AC

K3 Output 2

5 to 95% (without condensation)

Keying

Between 6 and 8 Between 16 and 18

Fuse

7A, 250V Type 3AG Slo Blow (1 per circuit) Bussman MSL 7.0; Littelfuse 313007

Field Wiring Arm

10555-I

-

1771-WC

Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)

JPR 7 JPR 8 NC

K2 Output 1

2500V ac rms Wire Size

JPR 2 JPR 3 NC

7-9 inchĆpounds

0

11

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-2.43

1 You use this conductor category information for planning conductor routing as described in the system level installation manual.

The power contact output module ! be mounted within 30° of vertical for the mercuryĆwetted relays to function. After installation, wait 3 minutes, or manually operate the relays 16 times, before powering up the module in an actual application.

Publication 1771-2.181 - September 1997

1

6

2

24

3

19

0

JPR 8, 10

JPR 7, 9

1

JPR 3, 5

JPR 2, 4

2

JPR 21, 23

JPR 20, 22

3

JPR 16, 18

JPR 15, 17

Page 25

0-24V Relay Contact Output Module (Cat. No. 1771-OYL)

25

0-24V Relay Contact Output Module (Cat. No. 1771-OYL)

+5V

Output Indicator

Backplane Logic Circuitry

Relay Driver

1771-OYL modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). The 1771-OYL module has 4 normallyĆopen (Form A) and 4 normallyĆclosed (Form B) relays. Outputs are arranged in 4 groups of 2, each group with its own common. Each output is is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 100mA continuously at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OYL module to drive an ac input module up to 24V ac. The 1771-OYL module can drive an input of the following dc modules: 1771-IB, ĆIBD, ĆIBN, ĆIG, ĆIGD,ĆIH, ĆIN, ĆIND, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.

+

Common

-

Normally open Output

To next output (next output is normally closed)

10520-I

Internal circuits

Field connections +24V ac L2

L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7

Output Device

1 2 3 4 5 6 7 8 9

Output Device

10 11 12

Common

+24V dc +dc

(Actual wiring runs in this direction.) 10521-I

Publication 1771-2.181 - September 1997