For the Allen-Bradley 1771-OW
Page 4
1771 Digital I/O Relay Contact Output Modules
4
The following table lists the Allen-Bradley relay contact output modules and shows compatibility and use of data table for each. System Compatibility and Use of Data Table
1771-OW 1771-OW16 1771-OWN 1771-OWNA
A B A A
1771-OX
A
1771-OYL 1771-OZL
A A
8 16 32 32 8 (4 actual outputs) 8 8
---
Y R N N
Y Y R R
Y Y Y Y
A,B B B B
Y
Y
Y
A,B
Y Y
Y Y
Y Y
A,B A,B
A = Compatible with superseded chassis (1771-A1, ĆA2, ĆA4) B= Compatible with current chassis (1771-A1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B, ĆAM1, ĆAM2) Y = Compatible without restriction N = Not compatible R = Conditional module placement; you must use an input module and an output module in an odd/even pair of slots of the I/O chassis beginning with slot 0.
!
Publication 1771-2.181 - September 1997
Relay contact output modules receive power through the 1771 I/O chassis backplane from the chassis power supply. Refer to the module specifications on pages 11 through 24 for the current required from the power supply (in mA) to operate the module. You should total the current requirements for all the modules in the chassis to avoid overloading the power supply or the I/O chassis backplane.
Plastic keying bands shipped with each I/O chassis let you configure your I/O slots to accept only one type of module. You can configure any backplane connector in an I/O chassis to receive your contact output module except for the leftmost connector, which is reserved for adapter or processor modules. Since mixed voltages are often used on relay modules, most of the contact output relay modules all have the same keying slots. Refer to the module specifications for specific keying positions.
Status indicators on the front of each module show the system logic side status of the output relays. Each module has one indicator per output. When the indicator is on, it means the output relay coil is energized; when the indicator is off, it means the output relay coil is not energized. You can quickly isolate many types of external hardware-related faults by comparing these indicators with their corresponding output devices, and the control program.
Page 5
1771 Digital I/O Relay Contact Output Modules
-
5
When using relay contact output modules, you must consider the following:
Relays have a finite number of operations during their life. This varies depending on the current loads and voltages you apply relative to the relay’s design specifications. A relay that is always operating at the same load conditions has a very predicatable life. A low power load delivers longer contact life when the minimum load conditions are met. Varying load conditions can drastically shorten contact life. Do not operate a contact at low current or voltage conditions after operating the same relay under high power conditions. Operate at low power first, then at high power. Electromechanical relays typically have a longer life than dry-reed relays. When selecting a relay type, we recommend that you consider the number of operations expected over time and the load placed on the relay. The switching frequency of a relay is limited by its mechanical characteristics. To obtain maximum relay life, do not exceed the maximum switching frequency of the module.
All types of relay outputs have a specified time in which contact is made or broken (pull-in or drop-out times). Dry-reed relays are notably faster than electromechanical. Electromechanical and dry-reed relays have contact bounce. Mercury-wetted relays do not have bounce.
-
All wiring between the module and the load creates a certain amount of capacitive loading for the relay contacts. This capacitance is discharged during contact closure. The resulting peak current flow causes additional wear of the contact. Avoid this effect by keeping your cable lengths as short as possible, and, if possible, insert a resistor in series with your load. Locate the resistor as near as possible to the field wiring arm. Size the resistor properly.
Publication 1771-2.181 - September 1997
Page 6
6
1771 Digital I/O Relay Contact Output Modules
Many loads (relays, coils, motor starters, solenoids, motors, etc.) contain a certain amount of inductance. This inductance does not allow an instantaneous change of current when the relay contacts open. As a result, the voltage across the contacts rises to a very high level, and causes arcing between the contacts. This arcing reduces the life of the contacts.We recommend you use a resistor-capacitor (RC) network (also called a “snubber”) across the contacts in all circuits. ATTENTION: Failure to use a resistor-capacitor (RC) network across the relay contacts can result in generation of electromagnetic noise which could disrupt nearby electrical equipment, including the 1771 I/O chassis.
!
The best location for the RC network is across the relay contact terminals on the field wiring arm. This location suppresses the noise where it is generated, and does not let the noise radiate along the wiring going to the load. The 1771-OW, -OW16, -OWN, -OWNA, -OYL, and -OZL modules are not approved by UL/CSA for use with reactive loads. The 1771-OX module is designed with selectable dc surge protection circuitry. The formula necessary to determine the appropriate values for the RC network is shown below. Use a capacitor with an ac voltage rating greater than the maximum voltage seen across the contacts. Use a 5%, 1 Watt carbon composition resistor. Resistor-Capacitor Network Calculation of Values
I
R
C = I2/10 in µF R = V/(10Ia) in ohms
V C
Publication 1771-2.181 - September 1997
Where: I = Amps V = Volts a = 1 + (50/V)