Manual · Allen-Bradley
0-24V Contact Output Module, Cat. No. 1771-OZL, Installation Data
Manual8 pagesPDF 74 KB
Installation data for the Allen-Bradley 1771-OZL 0-24V contact output module: keying, wiring, status indicators and specifications.
Covers · 1 model
The models it covers
Summary
What is in it
Installation data for the Allen-Bradley 1771-OZL 0-24V contact output module, an 8-relay output module for 1771 I/O chassis. It covers pre-installation considerations (resistive loads only, no surge limiting), power supply requirements, handling, keying the chassis, inserting the module, wiring through the 1771-WD field wiring arm with connection diagrams, reading the status indicators, and the full specifications.
Its parts
- To The Installer
- Pre-installation Considerations
- Installing the Module
- Interpreting the Status Indicators
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Installation data (publication 1771-2.129) for the Allen-Bradley 1771-OZL 0-24V contact output module, an 8-relay output module for the 1771 I/O chassis. It covers handling, keying, inserting the module, wiring through the 1771-WD field wiring arm, the status indicators and the specifications.
- What it is
- 0-24V contact output module with 8 Form A (N.O.) relays p. 1, 8
- Outputs
- 8, in 4 groups of 2, each group with its own common and isolated from module logic p. 1
- Voltage rating
- 0-24V AC RMS; 0-24V DC p. 8
- Current rating
- 100mA per output (maximum) p. 8
- Power rating
- 2.4W per output (resistive), DC and suppressed AC p. 8
- Chassis
- 1771 Series A or B I/O chassis p. 8
- Field wiring arm
- 1771-WD p. 3, 8
- Backplane current
- 420mA maximum with all coils energized; 37mA per energized relay p. 1
- Keying
- Between 6 and 8; between 16 and 18 p. 2
- Minimum contact load
- DC: 10mA @ 24V; AC: 10mA @ 24V p. 8
- Timing
- Operate/release 1msec max; bounce 1msec max; switching 10Hz max p. 8
- Isolation voltage
- 1000V open contacts; 1500V coil to contacts p. 8
- Interconnect cable
- 1000 ft. (304.8 meters) max p. 1
- Power dissipation
- 2.2 Watts (max.), 2 Watts (min.) p. 8
What this manual walks you through
- Handling the module to avoid electrostatic damage p. 2
- Keying the I/O chassis p. 2
- Inserting the module into the chassis p. 3
- Wiring the outputs to the field wiring arm p. 3, 4
- Driving a 1771-IND 10-30V AC input module p. 5
- Reading the status indicators p. 6
- Specifications p. 8
Good to know
- No surge limiting; for resistive loads only, not inductive or capacitive loads. p. 1
- Do not wire outputs in parallel to raise the current or wattage rating. p. 5
- Remove power from the chassis backplane and wiring arm before removing or installing the module. p. 2
- The leftmost connector is reserved for adapter or processor modules. p. 2
- Wiring arm terminal numbers are not the same as the output bit numbers. p. 3
Questions this manual answers
What voltage can the 1771-OZL switch?
It is rated 0-24V AC RMS and 0-24V DC. p. 8
How much current per output on the 1771-OZL?
Up to 100mA continuously per output, with a minimum contact load of 10mA at 24V. p. 1, 8
Can the 1771-OZL drive solenoids or motor starters?
No. It has no surge limiting and is recommended for resistive loads only, not inductive or capacitive loads. p. 1
Which wiring arm fits the 1771-OZL?
The 1771-WD field wiring arm. p. 8
What do the lights on the 1771-OZL show?
There are 8 status indicators; each lights when its relay is energized. p. 6