What is in it
Allen-Bradley product data for the 1771 digital I/O relay contact output modules. A general section explains the benefits of relay outputs, the three relay types (electromechanical, dry-reed and mercury-wetted), system compatibility, power supply requirements, keying, status indicators, application considerations, output module loading and certifications. A second section gives module-specific information for the 1771-OW, -OW16, -OWN, -OWNA, -OX, -OYL and -OZL.
Its parts
- Benefits
- Using This Publication
- Relay Types
- System Compatibility
- Power Supply Requirements
- Keying
- Status Indicators
- Application Considerations
- Output Module Loading
- Compliance to European Union Directives
- Agency Certification
- Module Information
- Support Services
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Allen-Bradley publication 1771-2.181 on 1771 digital I/O relay contact output modules: the 1771-OW, -OW16, -OWN, -OWNA, -OX, -OYL and -OZL. A general section explains relay types, chassis compatibility, keying, snubbers and relay life, and each module then has its own pages with a schematic, wiring and specifications. The module facts here come from the 1771-OZL pages.
- What it is
- 1771-OZL: 0-24V relay contact output module with 8 normally-open (Form A) dry-reed relays p. 3, 27
- Outputs
- 1771-OZL: 8, in 4 groups of 2, each with its own common p. 27
- Voltage rating
- 1771-OZL: 0-24V ac rms; 0-24V dc p. 28
- Current rating
- 1771-OZL: 100mA per output (maximum) p. 28
- Power rating
- 1771-OZL: 2.4W per output (resistive), dc and suppressed ac p. 28
- Minimum contact load
- 1771-OZL: dc 1mA @ 0-24V; ac 1mA @ 0-24V p. 28
- Backplane current
- 1771-OZL: 420mA maximum p. 28
- Isolation voltage
- 1771-OZL: 1000V between open contacts; 1500V between coil and contact p. 28
- Timing
- 1771-OZL: operate/release 1ms maximum; bounce 1ms maximum p. 28
- Power dissipation
- 1771-OZL: 2.2 Watts (max.), 2 Watts (min.) p. 28
- Driving inputs
- 1771-OZL: can drive an ac input module up to 24V ac p. 27
- Installation data
- 1771-OZL: publication 1771-2.129 p. 28, 29
- Relay type
- Dry-reed in the 1771-OYL and -OZL; electromechanical in the -OW, -OW16, -OWN and -OWNA; mercury-wetted in the -OX p. 3
- Snubber parts
- 5%, 1 Watt carbon composition resistor; capacitor ac rating above the maximum voltage across the contacts p. 6
What this manual walks you through
- Choosing between electromechanical, dry-reed and mercury-wetted relays p. 3
- Chassis compatibility, power supply loading and keying p. 4
- Relay life, response time and capacitive loading of long cables p. 5
- Sizing an RC snubber network across the contacts p. 6
- Derating for incandescent lamp loads p. 7
- Wiring the 1771-OZL outputs p. 27
- Driving a 1771-IND ac input module with the 1771-OZL p. 27, 28
Good to know
- The 1771-OZL has no surge limiting and is for resistive loads only, such as lamps, indicators and heating elements. p. 27
- Do not wire outputs in parallel to raise the current or wattage rating. p. 27
- The 1771-OW, -OW16, -OWN, -OWNA, -OYL and -OZL are not UL/CSA approved for reactive loads. p. 6
- Dry-reed relays cannot handle surge currents. p. 3
- Relays can run below the minimum current and voltage, but not reliably. p. 7
Questions this manual answers
What voltage and current can the 1771-OZL switch?
0-24V ac rms or 0-24V dc, up to 100mA per output. p. 28
What is the difference between the 1771-OYL and 1771-OZL?
The 1771-OYL has 4 normally-open and 4 normally-closed relays; the 1771-OZL has 8 normally-open relays. p. 25, 27
Can the 1771-OZL switch motor starters or solenoids?
No. It is recommended for resistive loads only, not inductive or capacitive loads such as motor starters, solenoids or relays. p. 27
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1771-2.181, Digital I/O Relay Contact Output Modules1
- Benefits2
- Using This Publication2
- Relay Types3
- System Compatibility4
- Power Supply Requirements4
- Keying4
- Status Indicators4
- Application Considerations5
- Output Module Loading7
- Compliance to European Union Directives12
- Agency Certification12
- Module Information13
- Support Services31