For the Allen-Bradley 1771-OZL

Page 1

%( ,- ,-

" # Relay contact output modules offer dry circuits, that is, circuits without leakage current. Leakage currents are present on solid-state outputs; these currents are capable of energizing highly sensitive output load devices such as low-power latching relays. Open contacts on output relays assure that no leakage currents occur in critical applications.

%$ %*)&*)( Allen-Bradley relay contact output modules offer either normally-open (Form A) or normally-closed (Form B) configurations. You can select the form configuration for four of the contact output modules, the 1771-OW, -OW16, -OWN, and -OX. The 1771-OW has eight selectable outputs. The 1771-OW16 has eight normally-open and eight selectable outputs. The 1771-OWN has 32 selectable outputs.The 1771-OX has four selectable outputs. Selectable–configuration means you can predetermine whether an output will be on or off when local power is lost to the control system or the output module. The 1771-OWNA has 32 non-selectable normally-open contacts.

- -

Page 2

1771 Digital I/O Relay Contact Output Modules

2

Isolation helps assure that a failure on one output circuit does not pull down another output circuit, thus increasing overall system integrity. This isolation also protects the backplane logic from line transients on the output circuits.

You can apply either ac or dc voltages to relay contact output circuits. The range of these voltages can be broad (within the module’s operating specifications) without impacting the module’s performance. Contacts on relays permit dc outputs to be sinking or sourcing as required by the devices being controlled. Solid-state outputs require specific compatibility with the load device as to current sinking or sourcing. You can use analog module inputs for different devices by switching circuits through relays. Analog signals are typically low voltage (+10V dc) and low current (4-20 mA). Contact resistance can be critical, and should be accounted for in low-impedance circuits.

This publication provides you with information about Allen-Bradley’s relay contact output modules. The publication is divided into two sections. The first section contains general information that pertains to all of the relay modules; the second section contains module-specific information. The following table lists the relay contact modules and the page number on which you can find information about each. Relay Contact Output Modules

1771-OW (8 outputs/selectable) 1771-OW16 (8 fixed, 8 selectable) 1771-OWN (32 outputs/selectable) 1771-OWNA (32 outputs) 1771-OX (4 outputs/power) 1771-OYL (24V/8outputs) 1771-OZL (24V/8outputs)

Publication 1771-2.181 - September 1997

15 15 17 19 21 23 25

Page 3

- - ,+(,+ *

3

Allen-Bradley relay contact output modules use one of the following relay types:

++

- - - - - -

-. -. -. -. -. - -. -.

Electromechanical relays contain the most economical design for power applications. These modules typically can handle line surges and noise through closed contacts. Electromechanical relays are not recommended for low voltage/low current applications. Electromechanical relays are generally slower than dry-reed relays. They are not recommended for use in environments with contaminants such as acid, ammonia, nitrogen, or chlorine (noxious environments) because they are not hermetically sealed. Allen-Bradley modules that use electromechanical relays include the 1771-OW, 1771-OW16, 1771-OWN, and 1771-OWNA modules.

Dry-reed relays are noted for their speed. These relays are well-suited for low-voltage, low-power applications. They are hermetically sealed and thus offer protection in noxious environments. Dry reeds, however, cannot handle surge currents due to their low-voltage design. Allen-Bradley modules that use dry-reed relays are the 1771-OYL and 1771-OZL modules.

The mercury-wetted relay is a power version of the dry-reed switch. These relays feature long life and high contact reliability because the mercury re-coats the contacts on every operation. Mercury-wetted relays are also hermetically sealed and have no bounce on outputs and offer a clean switch. Of the three types of relays, mercury-wetted relays are the slowest (10 ms). ATTENTION: The 1771-OX module contains mercury-wetted relays. At the end of the equipment's life, it should be collected separately from any unsorted municipal waste.

- - (+ ) -