The text of a manual · part 6 of 6
1771 Digital I/O Relay Contact Output Modules, pages 26 to 32
Pages 26 to 32 of 32
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OZL
Page 26
26
0-24V Relay Contact Output Module (Cat. No. 1771-OYL)
--" Outputs per Module
8 (4 groups of 2)
Module Location
1771 I/O chassis
Contact Configuration
4 Form A (N.O.), 4 Form B (N.C.)
Voltage Rating
0-24V ac rms; 0-24V dc
Current Rating1
100mA per output (maximum)
Surge Current
100mA maximum per output2 (at rated power)
Power Rating dc: 2.4W per output (resistive) ac (suppressed)2: 2.4W per output (resistive)
Minimum Contact Load dc: 1mA @ 0-24V ac: 1mA @ 0-24V
--"
0-24V Contact Output Module (Cat. No. 1771-OYL)
L1 ac High Output 0
1
Common
2
Output 1
3
Operate/Release Time
1ms maximum
Bounce Time
1ms maximum
Switching Frequency
10Hz maximum
Output 2
4
Power Dissipation
2.2 Watts (max.), 2 Watts (min.)
Common
5
Thermal Dissipation
7.6 BTU/hr (max.), 6.9 BTU/hr (min.)
Output 3
6
Backplane Current
420mA maximum
Output 4
7
Isolation Voltage
1000V between open contacts 1500V between coil and contact
Common
8
Output 5
9
Output 6
10
Common
11
Output 7
12
Conductors
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13
Wire Size Category
Environmental Conditions Operating Temperature Storage Temperature Relative Humidity
3
Input 00
5 to 95% (without condensation) Between 6 and 8 Between 16 and 18
Field Wiring Arm
1771-WD
Wiring Arm Screw Torque
1 2
0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)
Keying
Agency Certification (when product or packaging is marked)
10-30V ac Input Module (Cat. No. 1771-IND)
L2 ac Low
4 5
01 02 03 04
6
05 06 07 10 11 12 13 14 15 16 17
10
7 8 9
11 12 13 14 15 16 17 18 19 20 21
7-9 inchĆpounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-2.184
1 Spikes, peaks, and surges must be within the power rating. Resistive loads only. ac or dc power = 2.4W maximum
2 Surge limiting circuitry is not provided in the module. For reliable operation, the use must ensure that surges do not exceed either the voltage or current rating of the module.
3 You use this conductor category information for planning conductor routing as described in the system level installation manual.
Publication 1771-2.181 - September 1997
10522-I
Page 27
0-24V Relay Contact Output Module (Cat. No. 1771-OZL)
27
0-24V Relay Contact Output Module (Cat. No. 1771-OZL)
+5V
Output Indicator
Backplane Logic Circuitry
Relay Driver
1771-OZL modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). The 1771-OZL module has 8 normallyĆopen (Form A) relays.The outputs are arranged in 4 groups of 2, each with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 100mA continuously, at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OZL module to drive an ac input module up to 24V ac. The 1771-OYL module can drive an input of the following dc modules: 1771-IB, ĆIBD, ĆIBN, ĆIG, ĆIGD,ĆIH, ĆIN, ĆIND, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel.The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.
+
Common
-
Normally open Output
To next output (next output is normally open)
10523-I
Internal circuits
Field connections +12V ac L2
L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7
Output Device
1 2 3 4 5 6 7 8 9
Output Device
10 11 12
Common
+24V dc +dc
(Actual wiring runs in this direction.) 10524-I
Publication 1771-2.181 - September 1997
Page 28
28
0-24V Relay Contact Output Module (Cat. No. 1771-OZL)
--" Outputs per Module
8 (4 groups of 2)
Module Location
1771 I/O chassis
Contact Configuration
8 Form A (N.O.)
Voltage Rating
0-24V ac rms 0-24V dc
Current Rating1
100mA per output (maximum)
Surge Current
100mA maximum per output2 (at rated power)
Power Rating dc: 2.4W per output (resistive) ac (suppressed)2: 2.4W per output (resistive)
Minimum Contact Load dc: 1mA @ 0-24V ac: 1mA @ 0-24V
Operate/Release Time
1ms maximum
Bounce Time
1ms maximum
Switching Frequency
--"
0-24V Contact Output Module (Cat. No. 1771-OZL)
L1 ac High Output 0
1
Common
2
Output 1
3
Output 2
4
10Hz maximum
Common
5
Power Dissipation
2.2 Watts (max.), 2 Watts (min.)
Output 3
6
Thermal Dissipation
7.6 BTU/hr (max.), 6.9 BTU/hr (min.)
Output 4
7
Backplane Current
420mA maximum
Common
8
Isolation Voltage
1000V between open contacts 1500V between coil and contact
Output 5
9
Output 6
10
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13
Common
11
Output 7
12
Conductors
Wire Size Category
Environmental Conditions Operating Temperature Storage Temperature Relative Humidity
5 to 95% (without condensation) Between 6 and 8 Between 16 and 18
Field Wiring Arm
1 2 3
Input 00
0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)
Keying
L2 ac Low
4 5
01 02 03 04
6
05 06 07 10 11 12 13 14 15 16 17
10
7 8 9
11 12 13 14 15 16 17 18 19 20 21
1771-WD
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
10-30V ac Input Module (Cat. No. 1771-IND)
7-9 inchĆpounds • CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-2.129
1 Spikes, peaks, and surges must be within the power rating. Resistive loads only.
ac or dc power = 2.4W max
2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure that surges do not exceed either the voltage or current rating of the module.
3 You use this conductor category information for planning conductor routing as described in the system level installation manual.
Publication 1771-2.181 - September 1997
10525-I
Page 29
Related Publications
29
You can refer to the following publications for more information about Allen-Bradley relay contact modules and other Allen-Bradley discrete I/O modules:
- -
1771-OW module
Selectable Contact Output Module (cat. no. 1771-OW) Installation Data
1771-2.110
1771-OW16 module
Selectable Contact Output Module (cat. no. 1771-OW16) Installation Data
1771-2.206
1771-OWN module
Contact Output Module (cat. no. 1771-OWN) Installation Data
1771-5.37
1771-OWNA module
Contact Output Module (cat. no. 1771-OWNA) Installation Data
1771-5.38
1771-OX module
Power Contact Output Module (cat. no. 1771-OX) Installation Data
1771-2.43
1771-OYL module
0-24V Contact Output Module (cat. no. 1771-OYL) Installation Data
1771-2.134
1771-OZL module
0-24V Contact Output Module (cat. no. 1771-OZL) Installation Data
1771-2.129 all Allen-Bradley 1771 digital I/O modules
1771 Universal Discrete I/O Modules Selection Guide
1771-1.25
Allen-Bradley dc solid state digital I/O modules
1771 Digital dc Solid State I/O Modules Product Data
1771-2.180
Allen-Bradley ac solid state digital I/O modules
1771 Digital ac Solid State I/O Modules Product Data
1771-2.182
Allen-Bradley analog I/O modules
1771 Analog I/O Modules Product Data
1771-2.183
Publication 1771-2.181 - September 1997
Page 30
30 Notes
Notes
Publication 1771-2.181 - September 1997
Page 31
Support Services
-
31
At Allen-Bradley, customer service means experienced representatives at Customer Support Centers in key cities throughout the world for sales service and support. Our value-added services include:
- - • • • •
SupportPlus programs telephone support and 24-hour emergency hotline software and documentation updates technical subscription services
• • • • application engineering assistance integration and start-up assistance field service maintenance support
- • • • • lecture and lab courses self-paced computer and video-based training job aids and workstations training needs analysis
• • • • your only “authorized” source current revisions and enhancements worldwide exchange inventory local support
Page 32
PLC is a registered trademark of Allen-Bradley Company, Inc. PLC-2 is a trademark of Allen-Bradley Company, Inc. PLC-3 is a trademark of Allen-Bradley Company, Inc. PLC-5 is a trademark of Allen-Bradley Company, Inc. SLC is a trademark of Allen-Bradley Company, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the world's leading technology companies.
Worldwide representation. Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic • Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Ireland • Israel • Italy • Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • Netherlands • New Zealand • Norway • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico • Qatar • Romania • Russia-CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-2.181 - September 1997 Supersedes Publication 1771-2.181 - March 1993