For the Allen-Bradley 1771-OZL
Page 19
Selectable Relay Contact Output Module (Cat. No. 1771-OWN)
-
19
+5V Common Normally closed Output Indicator
Backplane Logic Circuitry
Output Normally open
Relay Driver To next output
10512-I
1771-OWN modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OWN module are arranged in 4 groups of 8, each group with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 32 outputs to separate loads, with a maximum of 12A per module. Each output can conduct a maximum load of 1.0A continuously at 30W maximum. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OWN module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OWN module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current. When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting. All outputs are individually selectable for either normallyĆopen or normallyĆclosed operation. They are preset for normallyĆopen operation at the factory. See next page for relay output jumper settings.
Common 0 Output 1 3
Output 0 2
2
4 6
6
5
8
7
Not used
10
10
12
12 14
14 16
16
15
18
17
Not used 0 2 4
20
26
6
5
28
7
Not used
30
10
32
12
34
14 16 Not used
36
15
38
17
4
22 24
Common 1 11 13
Common 2 1 3
Common 3 11 13
40
Note: Terminals on the left are even numbered, and terminals on the right are odd numbered. (Actual wiring runs in this direction.) Note: Contacts shown in N.O. configuration for simplicity.
10513-I
Publication 1771-2.181 - September 1997
Page 20
20
Selectable Relay Contact Output Module (Cat. No. 1771-OWN)
# Outputs per module
32 (4 groups of 8)
Module Location
1771-A1B thru -A4B, 1771-AM1, ĆAM2 Chassis
Voltage Rating
24 - 138V ac rms; 24 - 125V dc
Current Rating1 Max. per output Max. per module Max. per group
1A derate linearly .033A/°C above 45°C 12A derate linearly .4A/°C above 45°C 4A derate linearly .133A/°C above 45°C
Surge Current
1A (max) per output (at rated power)2
Power Rating dc: 30W per output (resistive) maximum ac: 30W per output (resistive) maximum
Minimum Contact Load
10mA
Operate/Release Time
5ms (+1ms) typical
Bounce Time
1ms (max)
Switching Frequency
10Hz (max)
Power Dissipation
All relays off: 15mW; All relays on: 12.5W (max.)
Thermal Dissipation
All relays off: 0.05 BTU/hr; All relays on: 42.75 BTU/hr (max.)
Backplane Current
2.5A maximum; 1.8A nominal
Isolation Voltage
1000V between open contacts 1500V between coil and contact
Interconnect Cable Length
1000 ft. (304.8 meters) max
Category
14 gauge (2mm2) stranded (max) 3/64 inch (1.2mm) insulation (max) 13
Environmental Conditions Operational Temp. Storage Temperature Relative Humidity
0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)
Conductors Wire Size
Keying
Between 6 and 8 Between 16 and 18
0 2 4 6 Not used 10 12 14 16 Not used 0 2 4 6 Not used 10 12 14 16 Not used
Common 0 1 3 5 7 Common 1 11 13 15K ohms 2W 15 17 Common 2 1 3 5 7 Common 3 11 13 15 17
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
120V ac Input Module (Cat. No. 1771-IAD)
2 3
Input 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
L2 ac Low 10514-I
& $# N.C.
RY1
L-06
L-04
L-02
L-00
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
N.O.
7-9 inchĆpounds
Installation Data
L1 ac High
1
1771-WN
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
Selectable Contact Output Module (Cat. No. 1771-OWN)
RY2
N.C.
Field Wiring Arm
- $#
N.O.
Normally Open
1771-5.37
1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.
2 Surge limiting circuitry is not provided in the module. For reliable operation, the user
N.C.
must ensure that surges do not exceed either the voltage or current rating of the module.
3 You use this conductor category information for planning conductor routing as described in the system level installation manual.
RY9
$#
Outputs 00 - 07
L-00 - L-07
Outputs 10 - 17
L-10 - L-17
Outputs 20 - 27
H-00 - H-07
Outputs 30 - 37
H-10 - H-17
RY10
N.O.
Normally Closed
Printed Circuit Board 10554-I
Publication 1771-2.181 - September 1997
Page 21
Relay Contact Output Module (Cat. No. 1771-OWNA)
21
+5V
Normally open Output
Output Indicator Backplane Logic Circuitry
Common Relay Driver To next output 10515-I
1771-OWNA modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OWNA module are arranged in 4 groups of 8, each group with its own common. The module can simultaneously switch all 32 outputs to separate loads, with a maximum of 12A per module. Each output can conduct a maximum load of 1.0A continuously at 30W maximum. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OWNA module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OWNA module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.
(showing internal circuits only)
Output 0 2
2 4
Common 0 1 3
4 6
6
5
8
7
Not used
10
10
12
12 14
14 16
16
15
18
17
Not used 0 2 4
20
26
6
5
28
7
Not used
30
10
32
12
34
14 16 Not used
36
15
38
17
22 24
Common 1 11 13
Common 2 1 3
Common 3 11 13
40
Note: All contacts are N.O, nonĆselectable. (Actual wiring runs in this direction.) 10516-I
Publication 1771-2.181 - September 1997
Page 22
22
Relay Contact Output Module (Cat. No. 1771-OWNA)
Outputs per module
32 (4 groups of 8)
Module Location
1771-A1B thru -A4B, and 1771-AM1, ĆAM2 I/O Chassis
Voltage Rating
24 - 138V ac rms 24 - 125V dc
Current Rating1 Max. per output Max. per module Max. per group
1A derate linearly .033A/°C above 45°C 12A derate linearly .4A/°C above 45°C 4A derate linearly .133A/°C above 45°C
Surge Current
1A (max) per output (at rated power)2
Power Rating dc: 30W per output (resistive) maximum ac: 30W per output (resistive) maximum
Minimum Contact Load
10mA
Operate/Release Time
5ms (+1ms) typical
Bounce Time
1ms (max)
Switching Frequency
10Hz (max)
Power Dissipation
All relays OFF: 15mW; All relays ON: 12.5W (max.)
Thermal Dissipation
All relays OFF: 0.05 BTU/hr; All relays ON: 42.75 BTU/hr (max.)
Backplane Current
2.5A maximum; 1.8A nominal
Isolation Voltage
1000V between open contacts 1500V between coil and contact
Interconnect Cable Length Conductors Wire Size Category Environmental Conditions Operating Temperature Storage Temperature Relative Humidity
1000 ft. (304.8 meters) max 14 gauge (2mm2) stranded (max) 3/64 inch (1.2mm) insulation (max) 13 0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)
Keying
Between 6 and 8 Between 16 and 18
Field Wiring Arm
Cat. No. 1771-WN
Wiring Arm Screw Torque
7-9 inchĆpounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-5.38
1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.
2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure that surges do not exceed either the voltage or current rating of the module.
3 You use this conductor category information for planning conductor routing as described in the system level installation manual.
Publication 1771-2.181 - September 1997
Contact Output Module (Cat. No. 1771-OWNA)
0 2 4 6 Not used 10 12 14 16 Not used 0 2 4 6 Not used 10 12 14 16 Not used
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
Common 0 1 3 5 7 Common 1 11 13 ohms 15 15K2W 17 Common 2 1 3 5 7 Common 3 11 13 15 17
120V ac Input Module (Cat. No. 1771-IAD) L1 ac High 1 2 3
Input 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
L2 ac Low 10517-I
Page 23
Power Relay Contact Output Module (Cat. No. 1771-OX)
23
+5V
Output Indicator
Common +
N.C. Jumpers Backplane Logic Circuitry
1K .47µF
Relay Driver
Surge Suppressor Jumper
N.O. Jumpers
MOV 275V
Output N.O./N.C. -
7A Fuse
10518-I
-
The 1771-OX module contains mercuryĆwetted relays. Handle the module carefully and avoid excessive vibration. This can cause damage to the glass bulb which houses the mercury and contacts. Failure to observe this caution may cause damage to the module's circuitry. The power contact output module be mounted within 30° of vertical for the mercuryĆwetted relays to function. After installation, wait 3 minutes, or manually operate the relays 16 times, before powering up the module in an actual application. The 1771-OX module includes a selectable RC network for switching dc voltages. When switching these voltages, include the onĆboard surge suppression. When switching inductive ac voltages, you must supply an external rc network as close as possible to the load terminals. These are listed below. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.
0 1
2
3 4
-%
120V ac
2-5
68
0.1
8mA
RG 1782-4
240V ac
2-5
270
0.027
4.5mA
120V ac
2-5
68
0.1
8mA
240V ac
2-5
270
0.027
4.5mA
120V ac
2-3
68
0.1
8mA
RG 1782-4
120V ac
4-5
47
0.1
8mA
RG 1782-3
240V ac
2-3
270
0.027
4.5mA
240V ac
4-5
180
0.047
7.5mA
120V ac
2-3
47
0.1
8mA
RG 1782-4
Internal circuits
Common 0+ NO/NC 0-
Field connections
A
User Power Supply
0
Common 1+ NO/NC 1-
1 2
Not used
3
Not used
4
Common 2+ NO/NC 2Common 3+ NO/NC 3-
Load
5 6 7 B
Note: Contacts shown in N.O. configuration for simplicity. (Actual wiring runs in this direction.) 10519-I
RG 1782-3
240V ac
2-3
150
0.047
8mA
240V ac
4-5
100
0.1
16mA
RG 1782-6
240V ac
2-3
100
0.1
16mA
RG 1782-6
Publication 1771-2.181 - September 1997
Page 24
24
Power Relay Contact Output Module (Cat. No. 1771-OX)
Outputs per Module
4 N.O/N.C.
Module Location
1771 I/O chassis
Voltage Rating
0-250V ac rms; 0-175V dc
Current Rating
2A (maximum)
Surge Current (Repeatable every 10 seconds)
5.5A ac peak for 5 seconds 6A dc for 5 seconds 15A dc for 500ms
Power Rating
200VA
On-state Contact Resistance
0.25 ohms maximum
Operate/Release Time
10ms maximum
Power Dissipation
2.9 Watts (max.), 2.6 Watts (min.)
Thermal Dissipation
9.9 BTU/hr (max.), 8.9 BTU/hr (min.)
Backplane Current
550mA maximum
Isolation Voltage Conductors
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 11
Category Environmental Conditions Operating Temperature Storage Temperature Relative Humidity
0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF)
NO
NO
JPR 4 JPR 5
JPR 9 JPR 10
DC
DC
JPR 6
AC
JPR 11
AC
K1 Output 0
JPR 15 JPR 16
JPR 20 JPR 21
NC
NC
NO
NO
JPR 17 JPR 18
JPR 22 JPR 23
DC
DC
JPR 19
AC
K4 Output 3
JPR 24
AC
K3 Output 2
5 to 95% (without condensation)
Keying
Between 6 and 8 Between 16 and 18
Fuse
7A, 250V Type 3AG Slo Blow (1 per circuit) Bussman MSL 7.0; Littelfuse 313007
Field Wiring Arm
10555-I
-
1771-WC
Wiring Arm Screw Torque Agency Certification (when product or packaging is marked)
JPR 7 JPR 8 NC
K2 Output 1
2500V ac rms Wire Size
JPR 2 JPR 3 NC
7-9 inchĆpounds
0
11
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-2.43
1 You use this conductor category information for planning conductor routing as described in the system level installation manual.
The power contact output module ! be mounted within 30° of vertical for the mercuryĆwetted relays to function. After installation, wait 3 minutes, or manually operate the relays 16 times, before powering up the module in an actual application.
Publication 1771-2.181 - September 1997
1
6
2
24
3
19
0
JPR 8, 10
JPR 7, 9
1
JPR 3, 5
JPR 2, 4
2
JPR 21, 23
JPR 20, 22
3
JPR 16, 18
JPR 15, 17
Page 25
0-24V Relay Contact Output Module (Cat. No. 1771-OYL)
25
0-24V Relay Contact Output Module (Cat. No. 1771-OYL)
+5V
Output Indicator
Backplane Logic Circuitry
Relay Driver
1771-OYL modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). The 1771-OYL module has 4 normallyĆopen (Form A) and 4 normallyĆclosed (Form B) relays. Outputs are arranged in 4 groups of 2, each group with its own common. Each output is is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 100mA continuously at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OYL module to drive an ac input module up to 24V ac. The 1771-OYL module can drive an input of the following dc modules: 1771-IB, ĆIBD, ĆIBN, ĆIG, ĆIGD,ĆIH, ĆIN, ĆIND, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.
+
Common
-
Normally open Output
To next output (next output is normally closed)
10520-I
Internal circuits
Field connections +24V ac L2
L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7
Output Device
1 2 3 4 5 6 7 8 9
Output Device
10 11 12
Common
+24V dc +dc
(Actual wiring runs in this direction.) 10521-I
Publication 1771-2.181 - September 1997