Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 4 of 6

1771 Digital I/O Relay Contact Output Modules, pages 12 to 18

Pages 12 to 18 of 32: Compliance to European Union Directives; Module Information; Support Services; Back Cover

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-OZL

Page 12

12

1771 Digital I/O Relay Contact Output Modules

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111

Individual discrete I/O modules can also comply with various other agency requirements when product or packaging is so marked. Agency Certification • CSA certified (when product or packaging is • CSA Class I, Division 2, Groups A, B, C, D certified marked) • UL listed • CE marked for all applicable directives

Publication 1771-2.181 - September 1997

Page 13

1771 Digital I/O Relay Contact Output Modules

13

Refer to the following pages for detailed information about each Allen-Bradley relay contact output module. This information includes:

• • • • • • simplified schematic application notes connection diagram driving an input module with an output module switch and jumper settings specifications

-

1771-OW (8 outputs/selectable)

15

1771-OW16 (8 fixed, 8 selectable)

15

1771-OWN (32 outputs/selectable)

17

1771-OWNA (32 outputs)

19

1771-OX (4 outputs/power)

21

1771-OYL (24V/8outputs)

23

1771-OZL (24V/8outputs)

25

Publication 1771-2.181 - September 1997

Page 14

14

1771 Digital I/O Relay Contact Output Modules

Publication 1771-2.181 - September 1997

Page 15

Selectable Relay Contact Output Module (Cat. No. 1771-OW)

-

15

+5V

Output Indicator

+ Normally closed

Output

Normally open Backplane Logic Circuitry

Relay Driver

Common To next output

1771-OW modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OW module are arranged in 4 groups of 2, each group with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 1.0A continuously, at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OW module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OW module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.

10509-I

(internal circuits on left; external circuits on right.) 120V ac L2

L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7

1 2

Output Device

3 4 5 6 7 8 9 10 11 12

Output Device 24V dc

(Actual wiring runs in this direction.) When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting. All outputs are individually selectable for either normallyĆopen or normallyĆclosed operation. They are preset for normallyĆopen operation at the factory. See next page for relay output jumper setting.

Note: Contacts are shown in N.O. configuration for simplicity. Placement of each relay's jumper sets N.O. or N.C. operation. 10510-I

Publication 1771-2.181 - September 1997

Page 16

16

Selectable Relay Contact Output Module (Cat. No. 1771-OW)

# Outputs per Module

- $#

8 (4 groups of 2)

Module Location

1771 I/O chassis

Voltage Rating

24 - 138V ac rms 24 - 125V dc

Selectable Contact Output Module (Cat. No. 1771-OW)

Current Rating1

1A per output (maximum)

Surge Current

1A maximum per output (at rated power)2

Power Rating dc: 30W per output (resistive) ac (suppressed)2: 30W per output (resistive)

Minimum Contact Load Operate/Release Time

1

Output 0

4

2

Bounce Time

1ms maximum

Common

Switching Frequency

10Hz maximum

3

Power Dissipation

3.7 Watts (max.); 3.3 Watts (min.)

Thermal Dissipation

12.6 BTU/hr (max.); 11.3 BTU/hr (min.)

4 Common

Backplane Current

700mA maximum

Isolation Voltage

1000V between open contacts 1500V between coil and contact Wire Size Category

14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13

Environmental Conditions Operating Temperature Storage Temperature Relative Humidity

5

01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

15K 2W

5 6 Common 7

0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)

Keying

L1 ac High

3

1

5ms(+1ms) typical

Conductors

2

Input 00

Common dc: 10mA @ 24V ac: 10mA @ 24V

120V ac Input Module (Cat. No. 1771-IAD)

6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

L2 ac Low

Between 6 and 8 Between 16 and 18

Field Wiring Arm

1771-WD

Wiring Arm Screw Torque

10511-I

7-9 inchĆpounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-2.110

& $#

N.O.2 N.C.2

K2

N.O.3 N.C.3

K4

N.O.1 N.C.1

1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.

2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure

Normally Open that surges do not exceed either the voltage or current rating of the module.

3 You use this conductor category information for planning conductor routing as described in the system level installation manual.

$#

$#

0

K1

4

K5

1

K2

5

K6

2

K3

6

K7

3

K4

7

K8

N.O.1 N.C.1 N.O.1 N.C.1

K1

N.O.4 N.C.4

K3

Normally Closed

Printed Circuit Board 10553-I

Publication 1771-2.181 - September 1997

Page 17

Selectable Relay Contact Output Module (Cat. No. 1771-OW16 Series B)

17

Output Indicator

Backplane Logic Circuitry

Relay Driver

+5V Outputs 00-07

Normally open

Output Common

+5V

Outputs 10-17

Normally closed Output Common

Relay Driver

Normally open Output 10512-I

1771-OW16 modules do not contain surge limiting circuitry. With properly chosen surge limiting devices, this module can be used to switch resistive (e.g., lamps, indicators, heating elements), capacitive and inductive loads (e.g., motor starters, solenoids, relays). When driving inductive or high current loads, a resistorĆcapacitor network should be placed across the module's relay contacts at the field wiring arm. This will help reduce the generation of electromagnetic noise created by the contacts when changing state. Outputs on the 1771-OW16 module are arranged in 2 groups of 8. Each output has a separate common and is electrically isolated from module logic circuitry. The first group of outputs are arranged as normallyĆopen contacts. The second group of outputs are selectable normallyĆopen or normallyĆclosed. The module can simultaneously switch all 16 outputs to separate loads. Each output can conduct a maximum load of 2.0A continuously at 500VA for ac loads, and 80W maximum for dc loads, but the total output power of the module cannot exceed 1440VA or 1280W. You can use the 1771-OW16 module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OW16 module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current. When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting.

Output 01 Common 01

2 4

Output 03

6

Common 03

8

Output 05

10

Common 05

12

Output 07

14

Common 07

16 18

Output 11 Ć NC Output 11 Ć NO

20

Common 11

22

Output 13 Ć NC Output 13 Ć NO Common 13 Output 15 Ć NC Output 15 Ć NO

24

Output 00 Common 00 Output 02 Common 02 Output 04 Common 04 Output 06 Common 06 Output 10 Ć NC Output 10 Ć NO Common 10 Output 12 Ć NC Output 12 Ć NO

26

Common 12

28

Output 14 Ć NC

30

Output 14 Ć NO

32

Common 14

34

Output 16 Ć NC

36

Output 16 Ć NO

Output 17 Ć NC Output 17 Ć NO

38

Common 16

Common 17

40

Common 15

If the output relay is not energized: = normally open contacts - = normally closed contacts 10513-I

Publication 1771-2.181 - September 1997

Page 18

18

Selectable Relay Contact Output Module (Cat. No. 1771-OW16 Series B)

%$( % - Outputs per module

16

Module Location

1771-A1B thru ĆA4B I/O Chassis; 1771-AM1 or ĆAM2

Voltage Rating

24-250V ac (rms), 47-63Hz; 24-150V dc

Power Rating1 dc: 80 Watts per output (max); 1280 Watts per module (max.) ac: 500 VA per output (max); 1440 VA per module (max.) Φ

Current Rating (maximum per channel)2 ac: 2A per output at rated power dc: 2A per output up to 40V; 1A per output at 50V 0.5A per output at 100V; 0.25A per output at 150V

Maximum Surge Current dc: 2A maximum per output (at rated power); ac: Refer to Table A below

Minimum Contact Load

10mA

Operate/Release Time

10ms maximum; 5ms (+1ms) typical

Bounce Time Maximum

4ms

Switching Frequency Maximum

1/3Hz @ maximum load

Expected Life of Electrical Contacts

300K operations @ 25oC Φ =

Power Dissipation

All relays off: 0.015 Watts; All relays on: 6.55 Watts

Thermal Dissipation

All relays off: 0.05 BTU/hr; All relays on: 22.24 BTU/hr

Backplane Current

1.3A maximum

Maximum Cable Length

1000ft (304.8m) 1500V ac for 1 second customer side to system side; 1500V ac for 1 second channel to channel; relay rated 4000V coil to contact

Isolation Voltage Conductors

14 gauge (2mm2) stranded maximum3

Wire Size

3/64 inch (1.2mm) insulation maximum 14

Category Environmental Conditions Operational Temp. Storage Temperature Relative Humidity

0o to 60oC (32o to 140oF) Ć40o to 85oC (Ć40o to 185oF)

5 to 95% (without condensation) Between 2 and 4 Between 32 and 34

Keying Field Wiring Arm

Catalog Number 1771-WN

Wiring Arm Screw Torque

7-9 inchĆpounds

Agency Certification (when product or packaging is marked)

• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives

Installation Data

1771-2.206

1 An individual output should not be subjected to high power loads and then be required to run low power loads. 2 Output current maximum per module is limited by the maximum output power rating. 3 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller wire size may be required.

4 You use this conductor category information for planning conductor routing as described in the systemĆlevel installation manual.

#*# #*#

%$) $*%*(

#*#

120

30

3

2

3600

360

240

15

1.5

2

3600

360

Publication 1771-2.181 - September 1997

%$ - +

Selectable Contact Output Module (Cat. No. 1771-OW16 120V ac Input Module Series B) (Cat. No. 1771-IAD Series B) L1 ac High

2 4 6

1

8

4

10 12

5 6

14 16

7 8

18 20

10

2 3

9

22 24

11

26

13

28

14

30

15

32 34

16

36 38

18

40

20

12

17 19 21

Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17

L2 ac Low 10514-I