Page 12
12
1771 Digital I/O Relay Contact Output Modules
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111
Individual discrete I/O modules can also comply with various other agency requirements when product or packaging is so marked. Agency Certification • CSA certified (when product or packaging is • CSA Class I, Division 2, Groups A, B, C, D certified marked) • UL listed • CE marked for all applicable directives
Publication 1771-2.181 - September 1997
Page 13
1771 Digital I/O Relay Contact Output Modules
13
Refer to the following pages for detailed information about each Allen-Bradley relay contact output module. This information includes:
• • • • • • simplified schematic application notes connection diagram driving an input module with an output module switch and jumper settings specifications
-
1771-OW (8 outputs/selectable)
15
1771-OW16 (8 fixed, 8 selectable)
15
1771-OWN (32 outputs/selectable)
17
1771-OWNA (32 outputs)
19
1771-OX (4 outputs/power)
21
1771-OYL (24V/8outputs)
23
1771-OZL (24V/8outputs)
25
Publication 1771-2.181 - September 1997
Page 14
14
1771 Digital I/O Relay Contact Output Modules
Publication 1771-2.181 - September 1997
Page 15
Selectable Relay Contact Output Module (Cat. No. 1771-OW)
-
15
+5V
Output Indicator
+ Normally closed
Output
Normally open Backplane Logic Circuitry
Relay Driver
Common To next output
1771-OW modules do not contain surge limiting circuitry. Use these modules for switching resistive loads only (e.g., lamps, indicators, heating elements). They are not recommended for inductive or capacitive loads (e.g., motor starters, solenoids, relays). Outputs on the 1771-OW module are arranged in 4 groups of 2, each group with its own common. Each output is electrically isolated from module logic circuitry. The module can simultaneously switch all 8 outputs to separate loads, each conducting a maximum load of 1.0A continuously, at rated power. AC loads switched by the modules should have a power factor of 1.0. You can use the 1771-OW module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OW module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current.
10509-I
(internal circuits on left; external circuits on right.) 120V ac L2
L1 Output 0 Common 1 2 Common 3 4 Common 5 6 Common 7
1 2
Output Device
3 4 5 6 7 8 9 10 11 12
Output Device 24V dc
(Actual wiring runs in this direction.) When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting. All outputs are individually selectable for either normallyĆopen or normallyĆclosed operation. They are preset for normallyĆopen operation at the factory. See next page for relay output jumper setting.
Note: Contacts are shown in N.O. configuration for simplicity. Placement of each relay's jumper sets N.O. or N.C. operation. 10510-I
Publication 1771-2.181 - September 1997
Page 16
16
Selectable Relay Contact Output Module (Cat. No. 1771-OW)
# Outputs per Module
- $#
8 (4 groups of 2)
Module Location
1771 I/O chassis
Voltage Rating
24 - 138V ac rms 24 - 125V dc
Selectable Contact Output Module (Cat. No. 1771-OW)
Current Rating1
1A per output (maximum)
Surge Current
1A maximum per output (at rated power)2
Power Rating dc: 30W per output (resistive) ac (suppressed)2: 30W per output (resistive)
Minimum Contact Load Operate/Release Time
1
Output 0
4
2
Bounce Time
1ms maximum
Common
Switching Frequency
10Hz maximum
3
Power Dissipation
3.7 Watts (max.); 3.3 Watts (min.)
Thermal Dissipation
12.6 BTU/hr (max.); 11.3 BTU/hr (min.)
4 Common
Backplane Current
700mA maximum
Isolation Voltage
1000V between open contacts 1500V between coil and contact Wire Size Category
14 gauge (2mm2) stranded maximum 3/64 inch (1.2mm) insulation maximum 13
Environmental Conditions Operating Temperature Storage Temperature Relative Humidity
5
01 02 03 04 05 06 07 10 11 12 13 14 15 16 17
15K 2W
5 6 Common 7
0 to 60oC (32 to 140oF) -40 to 85oC (-40 to 185oF) 5 to 95% (without condensation)
Keying
L1 ac High
3
1
5ms(+1ms) typical
Conductors
2
Input 00
Common dc: 10mA @ 24V ac: 10mA @ 24V
120V ac Input Module (Cat. No. 1771-IAD)
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
L2 ac Low
Between 6 and 8 Between 16 and 18
Field Wiring Arm
1771-WD
Wiring Arm Screw Torque
10511-I
7-9 inchĆpounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-2.110
& $#
N.O.2 N.C.2
K2
N.O.3 N.C.3
K4
N.O.1 N.C.1
1 Spikes peaks and surges must be within the power rating. Resistive loads only. ac or dc power = 30W max.
2 Surge limiting circuitry is not provided in the module. For reliable operation, the user must ensure
Normally Open that surges do not exceed either the voltage or current rating of the module.
3 You use this conductor category information for planning conductor routing as described in the system level installation manual.
$#
$#
0
K1
4
K5
1
K2
5
K6
2
K3
6
K7
3
K4
7
K8
N.O.1 N.C.1 N.O.1 N.C.1
K1
N.O.4 N.C.4
K3
Normally Closed
Printed Circuit Board 10553-I
Publication 1771-2.181 - September 1997
Page 17
Selectable Relay Contact Output Module (Cat. No. 1771-OW16 Series B)
17
Output Indicator
Backplane Logic Circuitry
Relay Driver
+5V Outputs 00-07
Normally open
Output Common
+5V
Outputs 10-17
Normally closed Output Common
Relay Driver
Normally open Output 10512-I
1771-OW16 modules do not contain surge limiting circuitry. With properly chosen surge limiting devices, this module can be used to switch resistive (e.g., lamps, indicators, heating elements), capacitive and inductive loads (e.g., motor starters, solenoids, relays). When driving inductive or high current loads, a resistorĆcapacitor network should be placed across the module's relay contacts at the field wiring arm. This will help reduce the generation of electromagnetic noise created by the contacts when changing state. Outputs on the 1771-OW16 module are arranged in 2 groups of 8. Each output has a separate common and is electrically isolated from module logic circuitry. The first group of outputs are arranged as normallyĆopen contacts. The second group of outputs are selectable normallyĆopen or normallyĆclosed. The module can simultaneously switch all 16 outputs to separate loads. Each output can conduct a maximum load of 2.0A continuously at 500VA for ac loads, and 80W maximum for dc loads, but the total output power of the module cannot exceed 1440VA or 1280W. You can use the 1771-OW16 module to drive an input of the following ac modules: 1771-IA, ĆIA2, ĆIAD, ĆIAN, ĆID, ĆID16, ĆIN, ĆIND. The 1771-OW16 module can drive an input of the following dc modules at nominal voltage: 1771-IB, ĆIBD, ĆIBN, ĆIH, ĆIQ, ĆIQ16, ĆIT, ĆIV, and ĆIVN. For reliable operation, a load current of at least 10mA should be maintained. Do not attempt to increase load current or wattage capability beyond the rating by connecting two or more outputs in parallel. The slightest variation in output relay switching time may cause one set of the contacts to switch the total load current. When the output image table bit at the address corresponding to any output is energized (set to 1), the corresponding relay contact is closed or opened, respective to the jumper setting.
Output 01 Common 01
2 4
Output 03
6
Common 03
8
Output 05
10
Common 05
12
Output 07
14
Common 07
16 18
Output 11 Ć NC Output 11 Ć NO
20
Common 11
22
Output 13 Ć NC Output 13 Ć NO Common 13 Output 15 Ć NC Output 15 Ć NO
24
Output 00 Common 00 Output 02 Common 02 Output 04 Common 04 Output 06 Common 06 Output 10 Ć NC Output 10 Ć NO Common 10 Output 12 Ć NC Output 12 Ć NO
26
Common 12
28
Output 14 Ć NC
30
Output 14 Ć NO
32
Common 14
34
Output 16 Ć NC
36
Output 16 Ć NO
Output 17 Ć NC Output 17 Ć NO
38
Common 16
Common 17
40
Common 15
If the output relay is not energized: = normally open contacts - = normally closed contacts 10513-I
Publication 1771-2.181 - September 1997
Page 18
18
Selectable Relay Contact Output Module (Cat. No. 1771-OW16 Series B)
%$( % - Outputs per module
16
Module Location
1771-A1B thru ĆA4B I/O Chassis; 1771-AM1 or ĆAM2
Voltage Rating
24-250V ac (rms), 47-63Hz; 24-150V dc
Power Rating1 dc: 80 Watts per output (max); 1280 Watts per module (max.) ac: 500 VA per output (max); 1440 VA per module (max.) Φ
Current Rating (maximum per channel)2 ac: 2A per output at rated power dc: 2A per output up to 40V; 1A per output at 50V 0.5A per output at 100V; 0.25A per output at 150V
Maximum Surge Current dc: 2A maximum per output (at rated power); ac: Refer to Table A below
Minimum Contact Load
10mA
Operate/Release Time
10ms maximum; 5ms (+1ms) typical
Bounce Time Maximum
4ms
Switching Frequency Maximum
1/3Hz @ maximum load
Expected Life of Electrical Contacts
300K operations @ 25oC Φ =
Power Dissipation
All relays off: 0.015 Watts; All relays on: 6.55 Watts
Thermal Dissipation
All relays off: 0.05 BTU/hr; All relays on: 22.24 BTU/hr
Backplane Current
1.3A maximum
Maximum Cable Length
1000ft (304.8m) 1500V ac for 1 second customer side to system side; 1500V ac for 1 second channel to channel; relay rated 4000V coil to contact
Isolation Voltage Conductors
14 gauge (2mm2) stranded maximum3
Wire Size
3/64 inch (1.2mm) insulation maximum 14
Category Environmental Conditions Operational Temp. Storage Temperature Relative Humidity
0o to 60oC (32o to 140oF) Ć40o to 85oC (Ć40o to 185oF)
5 to 95% (without condensation) Between 2 and 4 Between 32 and 34
Keying Field Wiring Arm
Catalog Number 1771-WN
Wiring Arm Screw Torque
7-9 inchĆpounds
Agency Certification (when product or packaging is marked)
• CSA certified • CSA Class I, Division 2, Groups A, B, C, D certified • UL listed • CE marked for all applicable directives
Installation Data
1771-2.206
1 An individual output should not be subjected to high power loads and then be required to run low power loads. 2 Output current maximum per module is limited by the maximum output power rating. 3 14 gauge wire connected to all terminals may not allow the field wiring arm cover to close. A smaller wire size may be required.
4 You use this conductor category information for planning conductor routing as described in the systemĆlevel installation manual.
#*# #*#
%$) $*%*(
#*#
120
30
3
2
3600
360
240
15
1.5
2
3600
360
Publication 1771-2.181 - September 1997
%$ - +
Selectable Contact Output Module (Cat. No. 1771-OW16 120V ac Input Module Series B) (Cat. No. 1771-IAD Series B) L1 ac High
2 4 6
1
8
4
10 12
5 6
14 16
7 8
18 20
10
2 3
9
22 24
11
26
13
28
14
30
15
32 34
16
36 38
18
40
20
12
17 19 21
Input 00 Input 01 Input 02 Input 03 Input 04 Input 05 Input 06 Input 07 Input 10 Input 11 Input 12 Input 13 Input 14 Input 15 Input 16 Input 17
L2 ac Low 10514-I