The text of a manual · part 3 of 6
1771 Digital I/O Relay Contact Output Modules: Output Module Loading
Pages 7 to 11 of 32, from 1771 Digital I/O Relay Contact Output Modules
The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-OZL
Page 7
1771 Digital I/O Relay Contact Output Modules
7
Incandescent lamps also create a spike due to their low turn-on resistance before they become hot. Therefore, you must use derating or surge suppression (for example Allen-Bradley surge suppressors 1492-H2K120, 1492-H2K024, and 1492-H2K240). Specified relay current is typically derated at ten times the steady-state current of the incandescent lamp load. For derating, you can calculate cold-start load by measuring the cold load resistance. You can also experience large current surges when bulbs burn out (e.g. 20-50 amps).
The operating temperature of the relay greatly influences the life of the relay contacts. The 1771 relay contact output modules have a maximum operating temperature of 60o. Operation at lower temperatures will extend relay contact life. Since electromechanical relays are not hermetically sealed, they are not recommended in environments with contaminants such as acid, ammonia, nitrogen, and chlorine - especially with voltages under 24V ac/dc or for prolonged periods without operation. Such environments contaminate the relay contacts, causing reliability problems. Higher voltage usage, between 24 and 120V ac/dc, and continued operation help keep contacts clean as a result of the burning off of contact contaminants. Relays are also subject to reliability problems under high vibration environments as mechanical motion can intermittently break contacts. Mercury-wetted relays and dry-reed relays are hermetically sealed from the environments, thus preventing environmental reliability problems. Mercury-wetted relays are generally sensitive to mounting position.
The life of the relays in the output modules is directly affected by the load through the contacts and the operating temperature. Minimum currents and voltages specified for 1771 relay contact output modules are selected to provide clean contacts throughout the life of the contacts. The relays can operate below the minimum specifications, but operation will not be reliable. Exceeding the maximum power ratings for the module will shorten the life of the relay contacts. Do not operate relay contact output modules at power levels greater than maximum specifications. By using the operating range graphs, you can determine if you are within the operating capability of the relay. You only need to know any two of the following:
• voltage • load current (mA) • load power consumption (W) Publication 1771-2.181 - September 1997
Page 8
8
" -,+(,+
Using Figure 1, follow this example: Given a 30V dc, 4W indicator, is this in operating range? 1. Locate the vertical line for 30V. 2. Locate the angled line for 4W; it is at this angle (\). 3. Find where the two lines cross. If this is within the shaded area of the graph, you are in the permissible operating area for the relay contact output module. (In this example, you are in the permissible operating range.) Refer to the following operating range graphs to determine the operating capability of the relay.
' '
1 see note 2
*,) %,*+ ."+!"&
'&$0 ') 2 CAUTION! Do not operate in this area.
see note 1
- - - -
-
-
Page 9
1771 Digital I/O Relay Contact Output Modules
Figure 2 1771-OW16 ac and de Operating Load Range! (Relay Contacts) 24V minimum, - 150V dc max. - - - 250V ac max. 3.00 NI y ~ NI il ~~ y | NX N Nia note 2 N l 1.00: NO N | 0.90 0.80| X N NI xe 0.701 XN N N N 0.60 aN N NX N IN ™~ | ~ 0.50 | 0.40 ~ ~ NJ ~~ - Ww ‘NX NU WS x N 500VA 0.25 aN N 020 N X\ \ ‘ Current NX IN 5 »~ q [Amperes IS 200VA (Amperes) N N NX N\ 0.10 NI 0.09 NK 0.08 NS N N\ NN 0.07 0.06 \ J 100VA 0.05 ~ a N NX IN 0.04 N. N wes ‘NX xe q q 50VA N N\ NJ 25VA aN NY 0.01 ~ N \ NX 10 20 30 40 50 70 80 90100 200 00 400 500‘ag0 800 1000 0.1VA 0.5VA 1VA 2.5VA 5VA 10VA Volts Legend ac and dc 1 Spikes, peaks and surges must be within the power rating. Resistive, capacitive or inductive loads only. ac power = 500VA max; dc power = 80W max. ac only 2 CAUTION! Do not operate in this area. 10507-1
Publication 1771-2.181 - September 1997
Page 10
10 1771 Digital l/(O Relay Contact Output Modules
Figure 3 1771-OX ac and dc Operating Load Range! (Relay Contacts)
175V de max. ~ | i 250V ac max. t | |
2.0A f& aN S S NX N N \Y NN 1.0A N N N NO see note 2 X X 8 \ N\ X\ X\ NX aN X\ N\ 6 IN NX ) XN 5 OW N\ NN NX aN IN NX xa IN L NI ; SJ NE EN ET NG a Nu Current IN mS ine aN IN NN _~ (Amperes) NY IN N IN N 200VA NA N NX aN aN N aN WN 08 [ON IN aN NX N IN X\ NX NN NX aN 100VA 06 X\ EN EN N aN 05 N N N NO NX NX 0 NJ “NI DA NJ N 50VA 02 IN NO aN xe xe \ NIN N\ \t oS \ N N NN 20VA 01 IN NX N 10 2 «30~ - 40 50 80 10 \, 175 200 250 YQ 400 so 800 100\, 0.1VA 0.5VA 1VA 2.5VA 5VA 10VA
Volts
1 Spikes, peaks and surges must be within the power rating. Resistive or inductive loads only. ac or dc power = 200VA max.
2 CAUTION! Do not operate in this area. 10507-1
Publication 1771-2.181 - September 1997
Page 11
- -
11
-
- - -
--
--
1 Resistive loads only. ac or dc power = 2.4W max.
-
2 CAUTION! Do not operate in this area.
- -