Sub I/O Scanner Module (Cat. No. 1771-SN, Series A, Revision D) Installation Instructions, pages 1 to 8

Pages 1 to 8 of 16

The original document is the PDF (608 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1771-SN

Page 1 read from a scan by OCR; it may hold reading errors

®

To The Installer

Compatible Processors

Compatible Adapters

ALLEN-BRADLEY

Sub I/O Scanner Module

(Cat. No. 1771-SN, Series A, Revision D)

Installation Instructions

This document gives you information on:

® compatible processors

= compatible adapters

= how to install the 1771-SN Scanner Module = how to connect the remote I/O link

= how to set the sub I/O scanner switches

= how to set switches on remote devices

# how to program the 1771-SN Scanner Module # the ladder program for remote I/O

® update time

# how to troubleshoot your module

# guard against electrostatic discharge

® system configuration

® specifications

Use the 1771-SN Scanner Module with any processor with block-transfer capability.

The 1771-SN Scanner Module communicates only with adapters with discrete transfer capability.

The module does not support complementary I/O.

Page 2 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Guard Against Electrostatic Discharge

Install the 1771-SN Scanner Module

Under some conditions, electrostatic discharge can degrade performance or damage the module. Observe the following precautions to guard against electrostatic damage.

# Touch a grounded object to discharge yourself of static electricity before handling the module. # Do not touch the backplane connector or connector pins.

# When not in use, keep the module in its static-shield bag.

Before you install the module into the I/O chassis:

1. Turn off power to the chassis.

ATTENTION: Remove power from the 1771-I/O chassis backplane before removing or installing an I/O Module.

# Failure to remove power from the backplane could cause module damage, degradation of performance, or injury.

# Failure to remove power from the backplane could cause injury or equipment damage due to possible unexpected operation.

2. Reserve an J/O slot for the module by placing keying bands on the backplane connector. Position keying bands between the following numbers labeled on the backplane adjacent to the upper backplane connector:

= between 2 and 4 = between 24 and 26 The keying bands mate with corresponding slots in the module connector.

Page 3 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Connect the Remote I/O Link Connect your module in a daisy-chain configuration.

Connect to the Module Connector

Connect your cable (1770-CD or equivalent, refer to the Approved Cable Vendor List, pub. no. ICCG-2.2) to the module connector at the bottom front of the module (Figure 1). Use either of the two sets of terminals. They connect in parallel inside of the module.

Figure 1 Connecting your module to a daisy-chain cable

Install a 150 ohm 1/2 watt resistor (cat. no. 1770-XF). Do not use

82 ohm resistors with this module. This module does not support extended node capability.

7 0 Cable Line 2 | (Clear S Ko no. 1771 - CD) Line 1 | (Blue) 8 ae Line 2 | (Clear) Se Shield S ({p) Line 1 | (Blue) S Mating Connector

Connector on 1771 -SN 12827

Page 4 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Connect to a Daisy-Chain Hook-up When using a daisy-chain hook-up (Figure 2), connect each I/O chassis to the remote I/O channel. This cable length should not exceed:

# 10,000 cable feet for 57.6k bits per second.

# 5,000 cable feet for 115.2k bits per second.

Install a 150-ohm 1/2-Watt terminator resistor (1770-XT or equivalent) (Figure 1) between the blue and clear wires at both ends of the communication link.

Figure 2

Example Daisy-Chain Hook-Up

1771 - SN Scanner ha pa ge i

© ==} oe iJ Terminator resistor: \ Clear Clear /

150 ohm 1/2-Watt

1 { Shield, ~ Shield | 3

Mini - PLC Processor

Shield

10 Chassis 1771 -ASB, - Remote I/O Chassis 1771 - ASB 3 lone) lomo) | |, |] ooo0go | oooodo eooe oo56 b556 Up to sixteen

Node adapter devices devices total

13132

Page 5 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Setting Sub I/O Scanner Select module options by setting switches in switch bank 0 (Table 1) and

Switches switch bank 1 (Table 2) in the cutout located on the left side of the module. Each switch bank has eight switches. Set each switch to the ON (closed) position by pressing the switch toward the numbers on the switch or to the OFF (open) position by pressing the switch toward “open”.

Table 1 Switch Bank 0 mm - To Set To Set Switch To _° _~ Communication Rate! 57.6k bits/s 1 ON (closed) (up to 10,000 me feet) ci | Switch Bank 0 115.2k bits/s { OFF (open) (up to 5,000 =_° - feet) Switches 1 and 3 are OFF (open) _¢ Mio Remote Outputs? off 2 ON (closed) Shading represents _° =~ (for local chassis fault) last state 2 OFF (open) the switch position <_ Ec Fault Control independent 3 ON (closed) | ae dependent 3 OFF (open) Lo /~ Fault Table’ enable 4 OFF (open) m- disable 4 ON (closed) 5 os Switch Bank 1 Unused Switches, 5,6, 7,8 OFF (open) Ce mo 1 Set the same communication rate for the 1771-SN Scanner and all adapter devices linked to the 1771-SN Scanner on the remote 1/O link. a 2 Controls output states of non-faulted remote I/O chassis when the local processor in the - chassis containing the Scanner detects a fault. A switch selection of each remote chassis 49407 controls the output states of that chassis when the adapter in that chassis detects a fault.

Independent fault control Lost communications with one I/O chassis does not affect operation of the other I/O chassis if each chassis has a different assigned rack number.

If both I/O chassis have the same rack number, you must set the faulted I/O search switch on the ON (closed) position to prevent a fault in one I/O chassis from affecting the other.

The 1771-SN Scanner clears the fault bit automatically after you correct the fault. You must recycle power to the Scanner to clear the fault counter.

Dependent fault control Lost communication with one I/O chassis causes the outputs of the other chassis to reset or remain in their last state according to how you set the last state switch on each chassis.

To clear a dependent fault, you must correct the fault and re-enable the backplane by switching the processor to program mode and back to the run mode.

3 When you enable this function, the module generates a fault table in the seventh and eighth words of the block-transfer read file (Figure 7). The module sets a fault bit to report a fault in each possible quarter rack (two I/O groups) on the serial link. The read file also contains discrete input data from the remote I/O chassis.

Page 6 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Table 2 Switch Bank 1

To Set To Set Switch To ~ Remote I/O enable scanning of | 1 through 7 ON (closed) _° Z/~ Rack Number! corresponding I/O Me |~ rack 3 Switch Bank 0 inhibit scanning of | 1 through 7 OFF (open) Switches 1 and 3 =e H- corresponding I/O are OFF (open) Le ie rack Shading represents Le Z~ Faulted /O Search? ari ° OFF oneal the switch position <_ Cc 1 Set switch 1, ON to enable scanning of rack 1; switch 2 for rack 2; switch 3 for rack 3; etc. ma j- Selecting I/O rack numbers greater than two increases block-transfer file lengths and I/O a update times. | Ke 2 We recommend that you assign a separate remote I/O rack number to each I/O chassis, however; gM switch Bank 4 I And And Then [+ Me Le io Both I/O chassis have the | you enable you select a communication loss with a ~ same assigned rack Faulted I/O Search | independent one I/O chassis does not number fault control affect the other chassis Both I/O chassis have the you disable you select a communication loss with 18407 same assigned rack Faulted I/O Search | independent one I/O chassis causes the

Setting Switches on Remote

Devices

Programming the 1771-SN

Scanner number fault control outputs of both chassis to be reset or left at last state

Use PLC-2 compatible switch settings for all remote devices controlled by the 1771-SN Scanner.

Your ladder program instructions must include block-transfer read and write instructions (and a file to file move instruction for PLC-2 Processors only) (Figure 3). You can calculate block length using the equation:

8 + (8 x highest rack number)

If you select the default block length 00 for the BTR/BTW to the SN module, it will read and write sixteen words or enough data for rack 1. If you have a higher rack number, use the formula above to determine the

BTR/BTW length.

Following are example block-transfer programs for PLC-2, PLC-3, and

PLC-5 Processors.

Page 7 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Figure 3 Block-Transfer Programming Example for a PLC-2 Processor

1771-ASB 1771-ASB ser. B ser. Aor B PLO-2 771sn __ - *(Ser. B) Output ( ) Input 1771-A4, -A4B 1771-A4, -A4B \ Chassis \ 1 Chassis A | | 8 ! 1 2:3 14 6 {| | | a, _ | 1771-A2, -A2B Local Rack 1 Remote Racks 1,2,3,4 Chassis 2-slot addressing 1/2-slot addressing Remote Rack 6

SN address = 170 1-slot addressing

SN Switches Chassis. on us ie Chassis ‘LTT ls re AAA GAARA) ARMADA UG

Bank 0 Bank 1 | afetefetefttele | | nuk | | alele he lk: 4) | ton |

ASB Switches ASB Switches

18175

Page 8 read from a scan by OCR; it may hold reading errors

Installation Instructions

Sub 1/O Scanner Module Cat. No. 1771-SN

Figure 4 Block-Transfer Programming Example for a PLC-3 Processor 1771-ASB (ser. B) (ser. A or B) ai SN 4771-A4B Input Output 774.498 PLO-3 Chassis 1 Chassis ihe sles 8 g | 0 4 (Uh |, - | | Processor Rack 0,1 Remote Racks 1,2,3 i-slot addressing 1/2-slot addressing

SN address = 040

Switches (Am mn veal Tritt

Aes (PMNNAMAN| Ann) Sones MEERENEA Git Sones MMARA RAR) AMM Gaaa

Bank 0 Bank 1

18176