The text of a manual · part 2 of 2
Sub I/O Scanner Module (Cat. No. 1771-SN, Series A, Revision D) Installation Instructions, pages 9 to 16
Pages 9 to 16 of 16
The original document is the PDF (608 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1771-SN
Page 9
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
Block-Transfer Programming Example for a PLC-5 Processor
Figure 5 1771-ASB Output PLO-5, -1771-SN (ser. A or B) if 1771-A4, -A4B 1771-A4, -A4B \ Chassis Chassis
1771-ASB 1771-ASB (ser. A or B) (ser. B) Input, -1771-A4, -A4B 1771-4, -A4B y Chassis \ Chassis g | 0 1 |
3
Remote Racks 1,2 1-slot addressing
Local Rack 0 2-slot addressing
SN address = 030
Remote Rack 4 Remote Rack 7 2-slot addressing 1/2-slot addressing
Chassi Chassi Chassi Swiches WWM MER) Switches NCNM ON MN,, - Suitches WAN SN Switches Cor eit ECE CEL eben) TEE beet | cea) meee | eee ELLE Bank 0 Bank 1 ASB Switches ASB Switches ASB Switches 18177 Ladder Logic: Comments: + ON7:0 NZS *BTR------~--- - --.. SN mace SRes Tmorw ni '~00- SN Group add: 3 ier ou sa? SN module addr: 0 Contre! Block N7:0e-<ER) Control block: user designated (5 words) iLangth 6a: Data file: user designated at addr: 100 jfontinuous M Length = 8+(8x7) = 64 LNs NOHO pe uceeeeeeeeen ee Remote 1/0 rung: sate +BLOGK TANGER uniTEs-ce- Input: Rack #4, 1/0 group #2, bit #7 tmodute piece wo. zo Output: Rack #1, 1/0 group #6, bit #4 Length 7g: poontinuous UN: 1 N7:134 N7:214 o--2 ¢
TEND OF FILE}
Page 10
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
Figure 6 Input and output data files for transfer to the processor Read File Write File (input) (output) 1771-SN 15 08 07 00 - * - Decimal Bit 1771-SN 15 08 07 00 - * - Decimal Block Transfer Read 17 10 07 00 ~~ Octal Bit Block Transfer Write 1? 10 07 00 - « - Octal Bit Input Data Table 0 0 Output Data Table 0 0 Words 0 0 Words 0 0 Decimal Octal 0 0 Not Used Decimal Octal 0 0 0 0 0 0 1-8 0-7 0 0 1-8 0-7 0 0 Not Us Fault Coun. 0 ~~ FautBit 0 0 Fault Table | Fault Table 0 0 Fault Table | Fault Table 0 0 9-16 10-17 Rack 1 9-16 10-17 Rack 1 17 - 24 20 - 27 Rack 2 17 - 24 20 - 27 Rack 2 25 - 32 30 - 37 Rack 3 25 - 32 30 - 37 Rack 3 33 - 40 40 - 47 Rack 4 33 - 40 40 - 47 Rack 4 41 - 48 50 - 57 Rack 5 41 - 48 50 - 57 Rack 5 49 - 56 60 - 67 Rack 6 49 - 56 60 - 67 Rack 6 57 - 64 70-77 Rack 7 57 - 64 70-77 Rack 7 Figure 7 Fault Table: Each bit identifies a quarter rack Decimal 15 14 13 12/11 10 09 08 07 06 05 04/03 02 O1 00 Octal P17 | 16 | 15) 14 | 13) 12 | 11 | 10, Upper Byte wm 07 | 06 | 05 | 04 | 03 | 02 | O1 | 00 «Bit
15 14
0-112-3'4-516-7
17 | 16 | 15 | 14
13 12
0-119-314-56-7
11 10
13 | 12 | 11 | 10
Lower Byte of Seventh Word
09 08 «a - Upper Byte
0-112-3.4-56-7
0-112 -314-516-7 |, - Not Used - -
Lower Byte of Eighth Word
0-112 -3'4 -5'6 -7
07 06 05 04 p07 | 06 | 05 | 04
0-112 -3/4 5/6 -7} - e - Module groups
03 02 O01 00 03 | 02 | 01 | 00
0-12-34 -516-7
0-112 -314 -516-7
_.__4 ta - Rack number
12826
Page 11
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
Status Word
The upper byte of the sixth decimal word of the block-transfer read contains a retentive count of the number of serial communication faults detected by the 1771-SN Scanner. This counter resets by cycling power to the SN Scanner. The 1771-SN Scanner sets bit 0 of this word every time it detects a fault, and resets it when you correct the fault.
Fault Table
If a rack fault occurs, the Scanner sets a bit in the seventh and/or eighth decimal words identifying the quarter chassis in which a fault occurred (Figure 7).
Important: All addresses in the following sections refer to the PLC-2 Programming Example (Figure 3).
Storage of Read File (PLC-2 applications)
For PLC-2 applications you should move the block-transfer read data file to a storage location using a file to file move instruction. Set the file length of the file move instruction to 8 + (8 x the highest rack number) words.
Input Data (Block-Transfer Read)
Input data from the remote I/O racks connected to the 1771-SN Scanner, transfers to the PLC through the block-transfer read in the ladder logic. Eight words are required for I/O data from each full remote I/O chassis. Use the following equation to determine the total number of words required (file length):
8 + (8 x highest rack number)=file length
Important: The first 8 words (0 through 7 octal) are reserved for fault indication and do not contain input data.
The ninth word (10 octal) corresponds to module group 0 of rack number 1. The most significant byte is slot 1. The least significant byte is slot 0.
The 17th word (20 octal) corresponds to module group 0 of rack number 2, etc.
Output Data (Block-Transfer Write) Output data to the remote I/O racks connected to the 1771-SN Scanner, transfers from the PLC through the block-transfer write in the ladder logic.
Important: The first 8 words (0 through 7 octal) are reserved.
The ninth word (10 octal) corresponds to module group 0 of rack number 1. The most significant byte is slot 1. The least significant byte is slot 0.
The 17th word (20 octal) corresponds to module group 0 of rack number 2, etc.
Page 12
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
Block-Transfer Write File
Assign a block-transfer write (BTW) file for sending output data through the Scanner to remote I/O chassis. Output data for rack 1 uses words 10 through 17 octal. Rack 2 uses words 20 through 27 octal. Choose your own method for moving output data into the BTW file.
Module Address Location in the chassis and addressing scheme (1, 2, or 1/2 slot addressing) determine the 1771-SN Scanner’s address.
Ladder Program for Remote I/O
Remote I/O addresses correspond with the addresses in the block-transfer read (input) and block-transfer write (output) files. For example, you would monitor an input in rack 6, module group 5, terminal 2, and energize an output in rack 2, module group 1, terminal 6 as follows based on example block-transfer files (Figure 3) at 300 (read) and 400 (write).
365 421
| 1 ¢ { \ | | IC \ / |
02 06
Local Processor Scan
When you use a Sub I/O Scanner, the time period for the processor to scan the program and local I/O includes a block-transfer write to the Scanner or a block-transfer read from the Scanner. The total time for the block-transfer is:
Block-transfer time = 0.1ms + 0.16ms x number of words For example, each block-transfer of 64 words takes 10ms.
Remote I/O Update
The time required for a remote output to change after receiving a changed input is the sum of:
# the input circuit delay time
= aremote I/O scan (7ms per chassis) to read from the input module
= the through-put time of the scanner (15ms)
# 3 local processor scans: block-transfer read, perform ladder logic and block-transfer write = the through-put time of the scanner (15ms)
= aremote I/O scan (7ms per chassis) to write to the output module
Page 13
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
For example, with 2 remote I/O chassis, a local processor scan time (including block-transfer for the Scanner) of 40ms and an input circuit delay time of 24ms, the remote I/O update time is:
Input Circuit delay time 24ms 1771-SN scan (7msjchassis x 2 chassis) 14ms 1771-SN throughput 15ms Block-transfer read time 40ms Program (read) 20ms Program (write) 20ms Block-transfer write time 40ms 1771-SN through put 15ms 1771-SN scan (7msjchassis x 2 chassis) 14ms Total 202ms Troubleshoot Your Module When troubleshooting your module, check the following in the order given to determine the cause of the fault.
= LEDs on the SN Scanner # block-transfer rungs in the ladder program of your processor ® status bits in the status word read by the processor
Page 14
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
LED Display for Normal and Fault Conditions
Under normal and fault conditions, the LEDs light as follows:
ON BLINKING OFF Power Normal Operation Not Used No Power-Check (PWR) backplane power supply Serial Communication Normal Operation-Communicating | Communicating with some remote | No Communications (SER COM)! with all remote racks racks or partial communications with all racks
Check the following:
cable connections in the remote I/O link power to the I/O chassis transmission rate setting of the 1771-SN Scanner is the same as the 1771-AS or ASB switch settings of remote I/O chassis correspond to the remote rack numbers that you set for the 1771-SN Scanner
Backplane Communication
Processor and SN doing block
Processor and SN doing block
No block transfers being done
(BPLN COM)! transfers at arate greater than 1 transfers at arate less than 1 every Refer to “Possible Causes of Block-every 1/2 second 1/2 second Transfer Errors” below
Module Fault SN hardware fault- Not Used Normal Operation
(SN FLT) Cycle power to the I/O chassis containing the 1771-SN
Replace the module if the LED remains lit after restoring power
1 The Serial Communication and Backplane Communication LEDs blink at power-up if you do not select a rack number for the 1771-SN using switch bank 1. To operate the module, you must assign a rack number.
All LEDs light briefly at power-up for a lamp test.
Possible Causes of Block-Transfer Errors Observe block-transfer rungs in the ladder diagram of the local processor. You have a block-transfer error when you observe that enable and done bits of block-transfer instructions either do not intensify or remain intensified. They should alternately turn on (intensify) and turn off.
Page 15
System Configuration
Installation Instructions
Sub 1/O Scanner Module
Cat. No. 1771-SN
Following are possible causes of block-transfer errors:
# The 1771-SN’s location; rack, group and slot in the local I/O chassis does not match the rack, group and slot of block-transfer instructions in the ladder diagram.
# When using PLC-2 unconditional block-transfers the block lengths of block-transfer read and write instructions are not equal. If different, do not enable block-transfer read and block-transfer write instructions in the same scan.
® Conditioning instructions in block-transfer rungs allow the rungs to turn on and off at the wrong time.
You can connect up to 16 remote I/O chassis to the Scanner using a daisy-chain cable configuration (Figure 2). You can use smaller I/O chassis but no more than seven full I/O racks (896 I/O per system. The Scanner cannot perform block-transfers with remote I/O adapters. Table 3 represents the configurations for maximum discrete I/O that you can use with the Scanner.
Table 3 System configurations for maximum discrete I/O Type of Addressing | I/O Adapter 1/0 Chassis Number of Qty-Type Qty-Type Discrete 0 2 slot 7 1771-AS,-ASB 7 1771-A4,-A4B | up to 896 1 slot 4 1771-ASB 4 1771-A4B up to 896 7 1771-ASB 7 1771-A2B up to 896 1/2 slot 4 1771-ASB 4 1771-A2B up to 896
Refer to Chapter 4, “Assigning Addressing Modes, Racks and Groups” in the 1785 PLC-5 Family Programmable Controllers Design Manual, publication 1785-6.2.1, for information on 1/2, 1 and 2 slot addressing.
Page 16
Installation Instructions
Sub 1/O Scanner Module Cat. No. 1771-SN
Specifications
68 Rockwell Automation
1771-SN Sub 1/0 Scanner Module
Module Location
1771-A1B thru -A4B or later I/O chassis and 1771-AM1 and -AM2 I/O chassis
Data Transmission Rate
10,000 cable-feet at 57.6k bits/s 5,000 cable-feet at 115.2k bits/s
Interconnect Cable
1770-CD or equivalent (refer to the Approved Cable Vendor List, pub. no. ICCG-2.2)
Backplane Current
1.2A
Power Dissipation
7W maximum @ 1.2A
Thermal Dissipation
24 BTU maximum @ 1.2A
Keying
Between 2 and 4 Between 24 and 26
Environmental Conditions: Operating Temperature Storage Temperature Relative Humidity
0° to 60°C (32° to 140°F) -40° to 85°C (-40° to 185°F) 5% to 95% (without condensation)
System
Supports PLC-2 rack addresses 1 thru 7 Supports up to 16 total adapters Does not support complementary 1/0
Part Numbers and Catalog Numbers
Daisy-Chain configurations Phoenix Connector (6-pin) (Allen-Bradley part number 940611-01)
1771-ASB Remote I/O Adapter termination resistor (Cat. No. 1770-XT)
Dropline Configurations T-Connector (Cat. No. 1770-XG), Allen-Bradley part number 966308-01)
Station Connector (Cat. No. 1770-SC), (Allen-Bradley part number 966080-01)
Terminator Set (Cat. No. 1770-XF), (Allen-Bradley part number 966307-01)
PLC, RediPANEL, PanelView, PLC-2/10, PLC-2/12, PLC-2/15 and Dataliner are trademarks of Allen-Bradley Company, Inc.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve
Allen-Bradley
Worldwide representation.
productivity and quality for more than 90 years. We design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies., - ZZ
Argentina * Australia * Austria * Bahrain « Belgium * Brazil * Bulgaria * Canada * Chile * China, PRC * Colombia * Costa Rica * Croatia * Cyprus * Czech Republic « Denmark * Ecuador * Egypt * El Salvador * Finland * France * Germany * Greece * Guatemala * Honduras * Hong Kong * Hungary * Iceland * India * Indonesia * lreland « Israel « Italy * Jamaica * Japan * Jordan * Korea * Kuwait * Lebanon * Malaysia * Mexico * Netherlands * New Zealand * Norway * Pakistan * Peru « Philippines * Poland * Portugal * Puerto Rico * Qatar * Romania * Russia-ClS * Saudi Arabia * Singapore * Slovakia * Slovenia * South Africa, Republic * Spain « Sweden * Switzerland * Taiwan * Thailand * Turkey * United Arab Emirates * United Kingdom * United States * Uruguay * Venezuela * Yugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication 1771-5 15, Mav 1995
PN 955121-40