The text of a manual · part 56 of 59
Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual: E - Quick Reference, pages 455 to 463
Pages 455 to 463 of 492, from Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LX / LXP
Page 455
Appendix E Quick Reference
EAF Function Numbers If you want to perform an operation of this type
Use this function number
The Mini-PLC-2/02, Mini-PLC-2/16 and Mini-PLC-2/17 can perform these functions. Addition Subtraction Multiplication Division Square Root BCD to Binary Binary to BCD FIFO Load FIFO Unload Log10 Sin x Cos x 10x
(01) (02) (03) (04) (05) (13) (14) (28) (29) (30) (35) (36) (37)
The Mini-PLC-2/17 can perform these additional functions. Loge Y to the X y+/-x Powers of e e+/-x Reciprocal 1/x Averaging Standard Deviation PID Set Clock Set Date Set Leap Year and Day of the Week Read Clock Read Date Read Leap Year and Day of the Week
E-10
(31) (33) (32) (34) (06) (07) (27) (10) (11) (12) (15) (16) (17)
Page 456
Appendix E Quick Reference
Editing Functions Function
Key Sequence
Mode
Insert a condition instruction
[INSERT] (instruction) (address)
Program
Description Position the cursor on the instruction that will precede the instruction to be inserted. Then press the key sequence. 1 2 Position the cursor on the instruction that will follow the instruction to be inserted. Then press the key sequence. 1 2 or [INSERT][]
(instruction) (address)
Remove a condition instruction
[REMOVE] (instruction)
Program
Position the cursor on the instruction to be removed and press the key sequence. 1
Insert a rung
[INSERT][RUNG]
Program
Position the cursor on the instruction in the preceding rung and press the key sequence. Enter instructions and complete the rung. 1
Remove a rung
[REMOVE][RUNG]
Program
Position the cursor anywhere on the rung to be removed and press the key sequence. 1
Change data of a word or block instruction
[INSERT][DATA]
Program
Position the cursor on the word or block instruction whose data is to be changed. Press the key sequence.
Change the address of a word or block instruction
[INSERT] (first digit) []
Program
Position the cursor on a word or block instruction with data and press [Insert]. Enter the first digit of the first data value of the instruction. Then use the [ ] and [ ] key as needed to cursor up to the word address. Enter the appropriate digits of the word address.
(Address) Program on line
[SEARCH] 5 2
Initiates online programming.
Replace an instruction or change the address of an instruction without data
[Instruction] (Address)
Program
Position the cursor on the instruction to be replaced or whose address is to be Press the desired instruction key (or key sequence) and the required address(es).
Change data on line
[SEARCH] 5 1 (Data)
Run/Program
Position the cursor on the word or block instruction whose data is to be changed. Press the key sequence. Cursor keys can be used.
[RECORD]
Press [RECORD] to enter the new data into memory.
[CANCEL COMMAND] All editing functions
[CANCEL COMMAND]
To terminate online data change. Program Run/Program
Aborts the operation at the current cursor position.
1
1
These functions can also be used during online programming.
2
When bit address exceeds 5 digits, press the [Expand Addr] key before entering address and enter a leading zero if necessary. IMPORTANT: Only addresses corresponding to output energize, latch and unlatch instructions are cleared to zero.
E-11
Page 457
Appendix E Quick Reference
Execution Times and Words Per Instruction
Approximate Execution Time Per Scan and Words Per Instruction Instruction Instruction Name
Symbol
True average µ sec.
False average µ sec.
Words Per Instruction
These instructions are features of Mini-PLC-2/02, Mini-PLC-2/16, and Mini-PLC-2/17 Examine On Examine Off Output Energize Output Latch Output Unlatch
-[ ]-[ / ]-( )-(L)-(U)-
7 10 5 10 8 10 7 10 7 10
6 10 5 10 8 10 6 10 6 10
1 1 1 1 1 1 1 1 1 1
Get Put Equal Less Than Get Byte Limit Test
-[G]-(PUT)-(=)-(<)-]B[-]L[-
15 10 12 10 12 10 14 10 11 10 13 10
7 13 10 13 10 14 10
1 1 1 1 1 1 1 1 1 1 1 1
Counter Reset Retentive Timer Reset Timer On-Delay Retentive Timer On-Delay Timer Off-Delay Up Counter Down Counter
-(CTR)-(RTR)-(TON)-(RTO)-(CTD)-(CTU)-(CTD)-
19 19 51 52 55 38 36
6 6 36 33 39 30 31
1 1 1 1 1 1 1
1 2 3 4 5 6 7 8 9 10 11
E-12 add 1 word per instruction when its address is 4008 or greater add 2 words per instruction when its address is 4008 or greater 1 word 999 words 1 bit 999 bits with 2 data values with 10 data values with 50 data values add 8 µs per instruction when its address is 4008 or greater add 16 µs per instruction when its address is 4008 or greater
Page 458
Appendix E Quick Reference
Approximate Execution Time Per Scan and Words Per Instruction (continued) Instruction Instruction Name
Symbol
True average µ sec.
False average µ sec.
Words Per Instruction
Add Subtract Multiply Divide Add Subtract Multiply Divide Square Root BCD to Binary Binary to BCD FIFO Load
-(+)-(-)-(x)-(x)-(:)-(:)EAF 01 EAF 02 EAF 03 EAF 04 EAF 05 EAF 13 EAF 14 EAF 28 EAF 29
9 10 8 10 18 11 20 11 30 30 30 30 30 31 31 116 116 117 117 55 55 56 55
1 1 1 1 2 2 2 2 3 3 3 3 3 3 3 3
FIFO Unload
29 10 32 10 201 11 184 9 247 252 915 1442 1007 228 192 409 3 8051 4 377 3 8051 4 222 5 534 6 234 5 482 6
Bit Shift Left Bit Shift Right
3 5 5
Examine Off Bit Shift Examine On Bit Shift Set Bit Shift Reset Bit Shift
EAF 18 EAF 19 EAF 16 EAF 17
58 60 61 61
18 18 20 20
3 3 3 3
Log 10 Sin X Cos X
EAF 30 EAF 35 EAF 36
807 538 538
30 30 30
3 3 3
1 2 3 4 5 6 7 8 9 10 11 add 1 word per instruction when its address is 4008 or greater add 2 words per instruction when its address is 4008 or greater 1 word 999 words 1 bit 999 bits with 2 data values with 10 data values with 50 data values add 8 µs per instruction when its address is 4008 or greater add 16 µs per instruction when its address is 4008 or greater
E-13
Page 459
Appendix E Quick Reference
Approximate Execution Time Per Scan and Words Per Instruction (continued) Instruction Instruction Name
Symbol
True average µ sec.
False average µ sec.
Words Per Instruction
10x Master Control Reset Zone Control Last State Branch Start Branch End End, Temporary End Subroutine Area Immediate Input Update Immediate Output Update
EAF 37 -(MCR)-(ZCL)-
685 7 12 8 8 11 * 62 67
30 7 8 6 10 8 13 9
3 1 1 1 1 1 1 1 1
Label Return Jump to Subroutine Jump Block Transfer Read Block Transfer Write Sequencer Output Sequence input Sequencer Load File-To-File Move Word-To-File Move File-To-Word Move
LBL -(RET)-(JSR)-(JMP)-
17 * * 34 54 54 343 418 283 291 153 153
0 9 10 52 52 72 36 69 60 49 49
1 1 1 1 2 2 5 5 4 5 4 4
T. END SBR -[I]-(IOT)-
SEQ 0 SEQ 1 SEQ 2 FILE 10 FILE 11 FILE 12
* = combined true execution time - 79 µs 1 add 1 word per instruction when its address is 4008 or greater 2 add 2 words per instruction when its address is 4008 or greater 3 1 word 4 999 words 5 1 bit 6 999 bits 7 with 2 data values 8 with 10 data values 9 with 50 data values 10 add 8 µs per instruction when its address is 4008 or greater 11 add 16 µs per instruction when its address is 4008 or greater
E-14
Page 460
Appendix E Quick Reference
Approximate Execution Time Per Scan and Words Per Instruction (continued) Instruction Instruction Name
Symbol
True average µ sec.
False average µ sec.
Words Per Instruction
These EAF instructions are features of the Mini-PLC-2/17 only. Set Clock Set Date Set Leap Year and Day of Week Read Clock Read Date Read Leap Year and Day of Week PID
EAF 10 EAF 11 EAF 12
217 225 167
30 30 31
3 3 3
EAF 15 EAF 16 EAF 17
203 205 138
30 30 31
3 3 3
EAF 27
2450 (typical) 3500 (max.)
118
3
Loge Powers of e (e+/-x) Powers of Y (y+/-x) Reciprocal (1/x) Average (3-digit
EAF 31 EAF 32 EAF 33 EAF 34 EAF 06
30 30 30 30 101 101
3 3 3 3 3
Average (6-digit)
EAF 06
Standard Deviation (3-digit)
EAF 07
Standard Deviation (6-digit)
EAF 07
1727 2071 1500 1620 2463 7 6787 8 2784 9 2103 7 3374 8 10038 9 4260 7 34430 8 162384 9 13532 7 23322 8 70746 9
1 2 3 4 5 6 7 8 9 10 11
98 98 98 119 119 119 101 101 101
3 3 3 add 1 word per instruction when its address is 4008 or greater add 2 words per instruction when its address is 4008 or greater 1 word 999 words 1 bit 999 bits with 2 data values with 10 data values with 50 data values add 8 µs per instruction when its address is 4008 or greater add 16 µs per instruction when its address is 4008 or greater
E-15
Page 461
Appendix E Quick Reference
FIFO Load and FIFO Unload File Full Bit FIFO Load Conditioning Bit
File Address
130 00
15
060 G 000
030 G 040
031 G 005
032 G 060
050 G 000 040 G 000 FIFO Unload Conditioning Bit
050
Input Word Address Current Data Being Loaded
Input Word Address (
File Length Result Word Address (Number of Words Currently in File)
042 G 000
130
050
01
14
061 G 000
043 G 000
044 G 000
The File
Output Word Address Current Data Being Unloaded
FIle Enpty Bit
File Address
034 G 005
035 G 061
File Length
E-16
070 ) 00
070 ) 00 070 ( ) 00
( 041 G 000
033 G 040
EXECUTE AUX FUNCTION FUNCTION NUMBER:28 DATA ADDR: 030 RESULT ADDR: 050
Output Word Address
EXECUTE AUX FUNCTION FUNCTION NUMBER:29 033 DATA ADDR: 050 RESULT ADDR:
(
070 ) 00
Page 462
Appendix E Quick Reference
Graphic Programming
Alphanumeric/Graphic Key Definitions Key
Function
[LINE FEED]
Moves the cursor down one line in the same column.
[RETURN]
Returns the cursor to the beginning of the next line.
[RUB OUT]
Deletes the last character or control code that was entered.
[REPT LOCK]
Allows the next character that is pressed to be repeated continuously until [REPT LOCK] is pressed again.
[SHIFT]
Allows the next key pressed to be a shift character.
[SHIFT LOCK]
Allows all subsequent keys pressed to be shift characters until [SHIFT] or [SHIFT LOCK] is pressed.
[CTRL]
Used as part of a key sequence to generate a control code.
[ESC]
Terminates the present function.
[MODE SELECT]
Terminates all functions and returns the mode select display to the screen.
Blank Yellow Keys
Space keys. Move the cursor one position to the right.
Industrial Terminal Control Codes Control Code Key Sequence
Function
[CTRL][P] [Column #][;] [Line #][A]
Positions the cursor at the specified column and line number [CTRL][P][A] positions the cursor at the top left corner of the screen.
[CTRL][P][F]
Moves the cursor one space to the right.
[CTRL][P][U]
Moves the cursor one line up in the same column.
[CTRL][P][5][C]
Turns cursor on.
[CTRL][P][4][C]
Turns cursor off.
[CTRL][P][5][G]
Turns on graphics capability.
[CTRL][P][4][G]
Turns off graphics capability.
[CTRL][P][5][P]
Turns Channel C outputs on.
[CTRL][P][4][P]
Turns Channel C outputs off.
[CTRL][I]
Horizontal tab that moves the cursor to the next preset 8th position.
[CTRL][K]
Clears the screen from cursor position to end of screen and moves the cursor to the top left corner of the screen.
Key Sequence
Attribute 1
[CTRL][P][0][T]
Attribute 0 = Normal Intensity
[CTRL][P][1][T]
Attribute 1 = Underline
[CTRL][P][2][T]
Attribute 2 = Intensify
[CTRL][P][3][T]
Attribute 3 = Blinking
[CTRL][P][4][T]
Attribute 4 = Reverse Video
1
Any three attributes can be used at one time using the following key sequence: [CTRL][P][Attribute #][;][Attribute #][;][Attribute #][T]
E-17
Page 463
Appendix E Quick Reference
ASCII Control Codes Control Code 1
1 2 3
E-18
Display 2
ASCII Mnemonic
Name
CTRL 0
3
NU
NUL
NULL
CTRL A
3
SH
SOH
START OF HEADER
CTRL B
3
SX
STX
START OF TEXT
CTRL C
3
EX
ETX
END OF TEST
CTRL D
ET
EOT
END OF TRANSMISSION
CTRL E
EQ
ENQ
ENQUIRE
CTRL F
AK
ACK
ACKNOWLEDGE
CTRL G
BL
BEL
BELL
CTRL H
BS
BS
BACKSPACE
CTRL I
HT
HT
HORIZONTAL TAB
CTRL J
LF
LF
LINE FEED
CTRL K
VT
VT
VERTICAL TAB
CTRL L
FF
FF
FORM FEED
CTRL M
CR
CR
CARRIAGE RETURN
CTRL N
SO
SO
SHIFT OUT
CTRL O
SI
SI
SHIFT IN
CTRL P
DL
DLE
DATA LINK ESCAPE
CTRL Q
D1
DC1
DEVICE CONTROL 1
CTRL R
D2
DC2
DEVICE CONTROL 2
CRTL S
D3
DC3
DEVICE CONTROL 3
CTRL T
D4
DC4
DEVICE CONTROL 4
CTRL U
NK
NAK
NEGATIVE ACKNOWLEDGE
CTRL V
SY
SYN
SYNCHRONOUS IDLE
CTRL W
EB
ETB
END OF TRANSMISSION BLOCK
CTRL X
CN
CAN
CANCEL
CTRL Y
EM
EM
END OF MEDIUM
CTRL Z
SB
SUB
SUBSTITUTE
ESCAPE
EC
ESC
ESCAPE
CTRL,
FS
FS
FILE SEPARATOR
CTRL-
GS
GS
GROUP SEPARATOR
CTRL.
RS
RS
RECORD SEPARATOR
CTRL/
US
US
UNIT SEPARATOR
DELETE
DT
DEL
DELETE
Some ASCII control codes are generated using non standard keystrokes. Will be displayed when Control Code Display option is set ON in Alphanumeric mode, only. (Not in Report Generation mode). Invalid key in Report Generation mode.