Page 464
Appendix E Quick Reference
Help
Help Directories Function
Key Sequence
Mode
Description
Help directory
[HELP]
Any
Displays a list of the keys that are used with the [HELP] key to obtain further directories.
Control function directory
[SEARCH] [HELP]
Any
Provides a list of all control functions that use the [SEARCH] key.
Record function directory
[RECORD] [HELP]
Any
Provides a list of functions that use the [RECORD] KEY.
Clear memory directory
[CLEAR MEMORY] [HELP]
Remote Prog
Provides a list of all functions that use the [CLEAR MEMORY] key.
Data monitor directory
[DISPLAY] [HELP]
Any
Provides the choice of data monitor display accessed by the [DISPLAY] key.
File instruction directory
[FILE] [HELP]
Any
Provides a list of all instructions that use the [FILE] key.
Sequencer instruction directory
[SEQ][HELP]
Any
Provides a list of all instructions that use the [SEQ] key.
Block transfer directory
[BLOCK XFER] [HELP]
Any
Provides a list of all instructions that use the [BLOCK XFER] key.
[CANCEL COMMAND]
Any
To terminate.
All directories
E-19
Page 465
Appendix E Quick Reference
Memory Layout
To examine memory layout: SEARCH
The word SEARCH appears in the lower left hand corner of the screen. Memory Layout Display
54
Mini-PLC-2/16
Mini-PLC-2/17
Data Table Size 128 words
Data Table Size 128 words
User Program Area 0001 words
User Program Area 0001 words
User Message Area 0000 words
User Message Area 0000 words
Unused Memory Available 3967 words
Unused Memory Available 7807 words
Mini-PLC-2/02 Data Table Size 128 words User Program Area 0001 words User Message Area 0000 words Unused Memory Available 1919 words
This illustrates the memory layout display for a 178 word data table. Even if there are no messages or programs in the memory, the END statement is there and it requires one word. Adding the number of words in the four areas equals the memory size (decimal).
E-20
Page 466
Appendix E Quick Reference
Memory Structure Total Decimal Words
8
Data Table Factory Configured for 2-Slot Addressing Decimal Words Per Area
8
Word Address
Processor Work Area No. 1
Bit Address 000
00
007 010
17 00
017 020
17 00
026 027 030
17
077 100
17 00
107 110
17 00
117 120
17 00
Output 7 Image Table 16
8 Bit/Word Storage
24
64
72
8
40
8
Reserved
1
2
Timer/Counter Accumulated Values (AC) (or Bit/Word Storage)
Processor Work Area No. 2 Input Image Table
80
8 Bit/Word Storage
88
8 Timer/Counter Preset Values (PR) (or Bit/Word Storage)
3
4
00
FactoryConfigured Data Table 6
5
127 130
17 00
177 200
17 00
128
40
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
1920 3968 7808
1792 3840 7680
Expanded Data Table and/or User Program
3577 17 7577 17 17177 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
2048 4096 7936
128 128 128
User Program
3777 17 7777 17 17377 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
1 2 3 4 5 6 7
May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. May not be used for preset values. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Do not use for bit/word storage.
10148-I
E-21
Page 467
Appendix E Quick Reference
Data Table Configured for 1-Slot Addressing
Total Decimal Words
Decimal Words Per Area
8
8
Word Address
Bit Address 000 00
Processor Work Area No. 1
007 17 010 00
Output Image Table Rack 1 6 16
8
017 17 020 00
Output Image Table Rack 2 1 1 24
8
Reserved
2
7
64
40
Timer Counter Accumulated Values (AC) (or Bit Word Storage) 3
72
8
Processor Work Area No. 2
026 17 027 030 00 077 17 100 00
Configured for 1-Slot Addressing Data Table 5
107 17 110 00
Input Image Table Rack 1 6 80
8
88
8
Input Image Table Rack 2 6
128
40
Timer Counter Preset Values (PR) (or Bit Word Storage)
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
1920 3968 7808
1792 3840 7680
Expanded Data Table and/or User Program
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
2048 4096 7936
128 128 128
User Program
1 2 3 4 5 6 7
E-22
117 17 120 00 4
127 17 130 00 177 17 200 00 3577 17 7577 17 17177 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
3777 17 7777 17 17377 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. Unused timer/counter memory words can reduce data table size and increase user program area. Do not use word 127 for block transfer data storage. Can be decreased to 48 words. Used with 1-slot addressing. You cannot put an output or block transfer module in rack 2, I/O group 7 when using 1-slot addressing. You can put an input module in rack 2, I/O group 7.
10349–I
Page 468
Appendix E Quick Reference
Data Table Configured for 1/2-Slot Addressing Word Address
Total Decimal Words
Decimal Words Per Area
8
8
Processor Work Area No. 1
16
8
Output Image Table Rack 1
24
8
Output Image Table Rack 2 1 Reserved 2 6
32
8
Output Image Table Rack 3
40
8
64
24
Output Image Table Rack 4 Timer/Counter Accumulated Values (AC) 3 (or Bit/Word Storage)
72
8
Processor Work Area No. 2
Bit Address 000 00 007 17 010 00 017 17 020 00 026 17 027 030 00 037 17 040 00 047 00 050 00 077 17 100 00
Configured for 1/2-Slot Addressing Data Table 5
107 17 110 00
Input Image Table Rack 1 80
8
88
8
Input Image Table Rack 2
96
8
Input Image Table Rack 3
8
Input Image Table Rack 4
24
Timer/Counter Preset Values (PR) (or Bit/Word Storage)
104
128 Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
1920 1792 3968 3840 7808 7680
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
2048 4096 7936
128 128 128
117 17 120 00 4
127 17 130 00 137 17 140 00 147 00 150 00
Expanded Data Table and/or User Program
177 17 200 00 3577 17 7577 17 17177 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
User Program
3777 17 7777 17 17377 17
Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17
May not be used for accumulated values. Not available for bit/word storage. Bits in this word are used by the processor. 3 Unused timer/counter memory words can reduce data table size and increase user program area. 4 Do not use word 127 for block transfer data storage. 5 Can be decreased to 48 words. 6 You cannot put an output or block transfer module in rack 2, I/O Group 7 when using 1/2-slot addressing. You can put an input module in rack 2, I/O group 7. 1 2
10350–I
E-23
Page 469
Appendix E Quick Reference
PID Control Block
Control Word 01 Bit Descriptions: Status Bits 00
- Equation (Set by User) Independent Gain =0
Dependent Gain = 1
01
- Mode (Set by User) Auto = )
Manual = 1
02
- Control Action (Set by User) Direct (SP-PV) = 0
Reverse (PV-SP) = 1
03
- Output Limiting (Set by User) No - 0
Yes = 1
04
- Set Output (Set by User) Inhibited = 0
Enabled = 1
05
- Cascade Bit (Set by User) 3 No = 0 Secondary Cascade Loop = 1
06
- Derivative Uses Error (set by User) 3 PV = 0 E=1
07
- Input Format (for Series C or later) Binary = 0 BCD = 1
10
- Dead Band (set by Instruction) 1 Out of DB = 0 Within DB = 1
11
- Maximum Output Alarm (set by Instruction) 1 Within limit = 0 Above limit = 1
12
- Minimum Output Alarm (Set by Instruction) 1 Within limit = 0 Below limit = 1
13
- Set point Error (Set by Instruction) 1 In range = 0 Out of range = 1
14
- Reserved
15
- Done bit (set by Instruction) 1 Not executed = 0 Executed = 1
16
- Reserved
17
- Enabled bit (set by Instruction) 1 Not enabled = 0 Enabled = 1
1 2 3
E-24
2
2
Do not change. Values are set by PID function. Do not change Reserved bits. Do not change while the processor is operating.
Page 470
Appendix E Quick Reference
Control Word 02 Bit Descriptions: Status and SIgn Bits 00
-
01
- KP/10 (Set by User) Do not move decimal = 0 Move decimal = 1
02
- Feedforward/Bias Sign (Set by User) Pos = 0 Neg = 1
03
- Maximum Scaling Sign (Set by User) Pos = 0 Neg = 1
04
- Minimum Scaling Sign (Set by User) Pos = 0 Neg = 1
05
- Set Point Sign (Set by User) Pos = 0 Neg = 1
06
- Process Variable Sign (Set by Instruction) 1 Pos = 0 Neg = 1
07
- Error Sign (Set by Instruction) 1 Pos = 0 Neg = 1
10
- Resume Control From Last State 2 Disabled - on first scan, a new CO is calculated Enabled = on first scan, the accumulated integral value is back-calculated from the last CO value
11
- Bumpless Transfer With Proportional Controllers 3 0 = no adjustment to Bias 1 = bumpless manual to auto mode by adjusting Bias
1 2 3
KIx10 (Set by User) Do not move decimal = 0 Move decimal to right = 1
Do not change these vales. They are set by the PID function. This bit should only be set after the PID program has been run to obtain a valid last CO value Do not change while the processor is operating.
E-25
Page 471
Appendix E Quick Reference
Words 03 through 09 All range values are unitless unless noted otherwise. Independent Gain Equation Range
Range
Dependent Gain Equation Word 03
0000-9999
Set Point - SP Word 04
00.00-99.99
Word 05
Range
Range 1 2 3
E-26
Term 1/TI Range 00.00-99.99
Integral Gain
Units Word 06
Term KD Range Bit set 00.01-99.99 Bit reset 000.1-999.9 Units - sec
Unites - min
3
Range
Feedforward - FFWD 1 Word 08
0000-9999
Maximum Scaling Value 1 Word 09
0000-9999 rep/min
Term TD Range 00.00-99.99
Derivative Gain
Word 07 0000-4095 or 0000-FFFF
0000-9999
Range 00.00-99.99
Proportional Gain
Term KI Range Bit set 0.000-9.999 Bit reset 0.000-9.999 Units rep/sec
Range
Range 1
Minimum Scaling Value
Can be negative number by setting appropriate sign bits. Do not change while processor is operating. With word 02 Bit 11 set.
Range 2
Range
0000-4095 or 0000-FFFF
0000-9999
0000-9999
3
Page 472
Appendix E Quick Reference
Table 1.B Words 10 through 24 Independent Gain Equation Range
Range Units Range Unites
Range Units
Range Units
Range
Range
Range Units
Dependent Gain Equation Word 10
0000-9999
Zero Crossing Dead Band
Word 11 0000-100% Percent 0000-100%
Set Output Value Word 12 Maximum Control Output
Percent Word 13 0000-100%
Minimum Control Output
Percent Word 14 0000-99.99
Loop Update Time sec Word 15 0000-9999
Process Variable - PV Word 16
0000-9999
Error 2 Word 17
0000-100%
Control Output 2
Percent
Range Units
Range Units Range Units
Range Units
Range Units
Range
Range
Range Units
0000-9999 0000-9999
0000-100% Percent 0000-100% Percent
0000-100% Percent
00.00-99.99 sec
0000-9999
0000-9999
0000-100% Percent
Words 18 through 24 Reserved 3 1 2 3
Do not change while processor is operating. Do not change. These values are set by the PID function. Do not change Reserved bits.
E-27