The text of a manual · part 9 of 59
Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual: 4 - Installing Your Programmable Controller, pages 68 to 76
Pages 68 to 76 of 492, from Mini-PLC-2/02, 2/16, 2/17 Processor (cat. no. 1772-LZ, LZP, LX, LXP, LW, LWP) User Manual
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1772-LX / LXP
Page 68
Chapter 4 Installing Your Programmable Controller
ATTENTION: We recommend that you use the following series of modules when using slot-mounted power supplies: Isolated ac (120V) Output Module (1711-OD) series C Isolated ac (220V) Output Module (1771-OR) series B Contact Output Module (1771-OYL, -OZL, or -OW)
These modules are compatible with the “soft-start” feature of slot-mounted power supplies. Outputs of certain discrete modules may momentarily change operating state during power-up or power-down period, which may cause damage to equipment and injure personnel. Updates to the latest series modules are available for the 1771-OD series A or B, 1771-OR series A, and 1771-OY series A. The 1771-OZ series A or B must be replaced by the 1771-OYL, 177-OZL, or 1771-OW.
Step 6 - Backup Battery
We recommend that you replace the internal lithium battery every year. Leave the processor turned on when you replace the battery. If you turn off the processor and replace the battery, you may lose the CMOS RAM memory. 1.
Remove the screw that secures the slotted battery cover.
2.
Remove the battery cover from the processor.
3.
Replace the battery in the battery holder. The positive (+) end of the battery should contact the positive (+) end of the battery holder. The negative (–) end of the battery should contact the negative (–) end of the battery holder.
+ battery cover cover screw lithium battery 20214
4-28
Page 69
Chapter 4 Installing Your Programmable Controller
4.
Replace the battery cover.
5.
Tighten the screw.
How to Dispose of the Battery Batteries should be collected for disposal in a manner to prevent short circuiting, compacting, or destruction of case integrity and hermetic seal.
ATTENTION: Do not incinerate or dispose of lithium batteries in general trash collection. Explosion or violent rupture is possible.
For disposal, batteries must be packaged and shipped, in accordance with transportation regulations, to a proper disposal site. The U.S. Department of Transportation authorizes shipment of “lithium batteries for disposal” by motor vehicle only in regulation 173.1015 of CFR49 (effective Jan. 5, 1983). For additional detailed information, contact: U. S. Department of Transportation Research and Special Programs Administration 400 Seventh Street, S.W. Washington, D.C. 20590 Although the United States Environmental Protection Agency at this time has no regulations specific to lithium batteries, the material contained in the battery may be considered toxic, reactive, or corrosive. The person disposing of the material is responsible for any hazard created in doing so. State and local regulations may exist regarding the disposal of these materials.
Step 7 - Installing the EEPROM Memory Module
If you have a processor with a power supply, start at step 1. If you have a processor without a power supply, turn off power to the chassis and start at step 5. 1.
Move the POWER switch to the off position.
2.
Turn off the incoming power source to the processor and chassis
3.
Unplug the power cable
4.
Lift the latch of the I/O chassis that holds your processor.
5.
Slide the processor out of the I/O chassis.
4-29
Page 70
Chapter 4 Installing Your Programmable Controller
6.
Place the processor on a clean flat surface with the bottom of the module facing you.
7.
Position the EEPROM memory module in the memory module slot with its label facing upward. Insert and press firmly for proper connection (Figure 4.17).
Figure 4.17 Inserting the EEPROM Memory Module into the Processor
10316-I
8.
Slide the processor into the I/O chassis.
9.
Secure the I/O chassis latches.
10. Connect the power cable. 11. Apply power to the processor How to Remove the EEPROM Repeat steps 1 through 4 from the previous procedure, then insert a coin into the slot so that it engages the lip on the EEPROM memory module. Carefully rotate the coin upward to start removing the EEPROM memory module from its slot. Grasp and remove the EEPROM memory module.
4-30
Page 71
Chapter 4 Installing Your Programmable Controller
Step 8 - Installing the Processor
Slide your processor into the leftmost slot of the I/O chassis (Figure 4.18) Figure 4.18 Place the Processor in the Left-Most Slot of the I/O Chassis locking bar
Mini-PLC-2/17 processor left-most slot
20215
ATTENTION: Do not place your processor in the I/O chassis without keying bands. Short circuits can result from misalignment.
Step 9 - Installing the Power Supply
Skip this step if you have a processor with a power supply and do not need additional current for your I/O modules. If you need additional current, use an ac powered supply because we recommend that you use the same input voltage source for two paralleled power supplies
ATTENTION: Do not parallel a 1771-P5 power supply and a processor with a power supply because of power-up and power-down timing difference.
4-31
Page 72
Chapter 4 Installing Your Programmable Controller
Step 10 - Connecting to the Field Wiring Arms
Your I/O devices connect to the I/O module’s field wiring arm. Every I/O module must be properly wired and every I/O connection must be made at the proper field wiring arm terminal. Refer to the specific I/O module publication for connection diagrams. We recommend using copper wire for these connections. 1.
Grasp the lug and open the terminal cover to the right.
lug
2.
Measure the wire distance from your I/O devices to the field wiring arm terminals. This distance determines the length of wire you need for your application.
3.
Strip some of the outer jacket from the end of the cable that connects to the field wiring arm.
Strip some casing to expose the wires
4-32
Page 73
Chapter 4 Installing Your Programmable Controller
For a single-conductor wire or multi-conductor cable, perform the following steps. For a multi-conductor shielded cable, proceed to the next section (page 4-34). Single-Conductor Wire or Multi-Conductor Cable 1.
Strip about 3/8 inch insulation to expose the end of the wire Strip about 3/8 inch insulation to expose the wire
2.
Loosen a terminal screw and place the wire under the pressure plate of the terminal.
10604-I
3.
Secure the terminal screw.
4-33
Page 74
Chapter 4 Installing Your Programmable Controller
4.
Repeat steps 2 and 3 until you wire the appropriate I/O devices to the field wiring arm.
10618-I
5.
Connect the drain wire to ground.
6.
Gather all wires and neatly bundle them using tie wraps.
7.
Label all wires with a 5-digit I/O address code at each wire connection. Chapter 7 describes I/O addressing.
Multi-Conductor Shielded Cable Intelligent and low-voltage dc discrete I/O modules require shielded cables that help to reduce the effects of electrical noise coupling. Ground a shield at one end only as specified in the appropriate publication for the product. A shield grounded at both ends may form a ground loop that can introduce objectionable ground currents resulting in faulty operation of the programmable controller. Avoid breaking shields at junction boxes. If you do break a shield at a junction box, make sure that the junction box contains only low-level conductors. Also, do not strip the shield back any farther than necessary to make a connection.
4-34
Page 75
Chapter 4 Installing Your Programmable Controller
Multi-conductor shielded cable is Belden type 8761. It consists of twisted pairs of conductor wires wrapped in two layers of shielding. Our wiring procedure shows one pair of conductor wires. The required number of I/O terminals determines the number of conductor wires needed within the cable for your application. Figure 4.19 shows each component making up this cable. Figure 4.19 A Multi-Conductor Cable Contains these Component foil shield insulation conductor outer jacket drain wire 10319-I
1.
Cut the braided shield. braided shield
2.
Remove the foil shield foil shield
4-35
Page 76
Chapter 4 Installing Your Programmable Controller
3.
Cut the insulation and filler cords. insulation filler rods conductor wires drain wire
4.
Fold the drain wire back to separate it from the conductor wire. conductor wires drain wire
5.
Strip about 3/8 inch insulation to expose the end of the wire. drain wire exposed wire
6.
insulation
Loosen a terminal screw and place the wire under the pressure plate of the terminal screw.
10604-I
7. 4-36
Secure the terminal screw.