Page 59
Chapter 4 Installing Your Programmable Controller
Figure 4.10 Ground Bus Connections ground bus mounting ground bus ground lug grounding electrode conductor to grounding electrode system equipment grounding conductors
10309-I
Figure 4.11 Details of Ground Connection at Enclosure Wall enclosure wall (inside) scrape paint on both sides bolt star washer ground lug enclosure wall (outside)
star washer equipment grounding conductor nut 10310-I
Connect an equipment grounding conductor directly from each chassis to an individual bolt on the ground bus (Figure 4.12). For those chassis with a ground stud, use the ground stud for this connection. For those chassis with no ground stud, use a mounting bolt.
4-19
Page 60
Chapter 4 Installing Your Programmable Controller
If the power supply has its own groundable chassis, do not connect the GND terminal of the power supply. However, when you connect power to a power supply without a groundable chassis of its own (such as an ac-input power-supply module), you must also use 12 AWG copper wire to connect its GND terminal to the ground stud or mounting bolt connected to the ground bus (Figure 4.12). Do not lay one ground lug directly on top of the other; this type of connection can become loose due to compression op f the metal lugs. Sandwich the first lug between a star washer and a nut with a captured star washer. After tightening the nut, sandwich the second lug between the first nut and a second nut with a captive star washer (Figure 4.12). Grounding-Electrode Conductor Connect the ground bus to the grounding-electrode system through a grounding-electrode conductor. The grounding-electrode system is at earth-ground potential and is the central ground for all electrical equipment and ac power within any facility. Use 8 AWG copper wire minimum for the grounding-electrode conductor to guard against EMI. The National Electrical Code specifies safety requirements for the grounding-electrode conductor. Shielded Cables Certain connections require shielded cables to help reduce the effects of electrical noise coupling. Ground each shield at one end only. A shield grounded at both ends forms a ground loop which could cause faulty processor operation. Ground each shield at the end specified in the appropriate publication for the product. Avoid breaking shields at junction boxes. Many type of connectors for shielded conductors are available from various manufacturers. If you do break a shield at a junction box: Connect only category-2 conductors in the junction box. Do not strip the shield back any further than necessary to make a connection Connect the shields of the two cable segments to ensure continuity along the entire length of the cable.
4-20
Page 61
Chapter 4 Installing Your Programmable Controller
Figure 4.12 Grounding Configuration (Typical) enclosure wall ground bus grounding electrode conductor to grounding electrode system
PLC-2/30 processor equipment grounding conductor 8 AWG
1771-P7 power supply
I/O chassis wall
14 AWG mini-processor with built-in power supply ground lug nut power supply module star washer ground lug
14 AWG 15317
4-21
Page 62
Chapter 4 Installing Your Programmable Controller
Step 3 - Setting the Switches within the Switch Group Assembly
Figure 4.13 Locating Switch Group Assembly on the Backplane of an I/O Chassis
Switch Group Assembly
Table 4.C and Table 4.D explain how each switch is used by the processor. Switches 2 and 3 are not used. Use a ball-point pen to set each switch. Do not use a pencil because the tip can break off and jam the switch.
4-22
Page 63
Chapter 4 Installing Your Programmable Controller
Table 4.C Set Switches 1, 4, 5 and 8 If you want:
Then set:
And
Outputs to remain in their last state when a fault (red LED in ON) is detected 1
Switch 1 ON
--
Outputs to de-energize when a fault (red LED is ON) is detected 1
Switch 1 OFF
--
2-slot addressing
2
1-slot addressing
3
Switch 4 OFF Switch 4 OFF Switch 4 ON
Switch 5 OFF Switch 5 ON Switch 5 ON
Switch 8 OFF
--
1/2-slot addressing 4 RAM memory protect disabled RAM memory protect enabled 1 2
3
4
5
5
Switch 8 ON
Last state switch only on PLC-2/16 and -2/17 series C or later, and PLC-2/02 series A or later. When using 2-slot addressing and 8-pt. I/O modules: a 16-slot chassis equals one rack which can address 128 I/O. See chapters 5 and 7. When using 1-slot addressing and 16-pt. I/O modules: a 16-slot chassis equals two racks which can address 256 I/O. See chapters 5 and 7. When using 1/2-slot addressing and 16-pt. I/O modules: a 16-slot chassis can address four racks which equals 512 I/O. See chapters 5 and 7. When memory protect is enabled, you can only change the status and value of the bits in the first 128 words (word addresses up to 1778) of the data table.
4-23
Page 64
Chapter 4 Installing Your Programmable Controller
Table 4.D Set Switches 6 and 7 If
And
Then
Without and EEPROM installed in your processor Switch 6 is OFF
Switch 7 may be either ON or OFF
With a battery installed and a program stored in RAM memory, your processor powers-up in the mode identified by the position of the mode select switch. If the mode select switch is in the RP position, the processor will power-up in the remote program mode. Without a battery installed and without a program stored in RAM memory, your processor powers-up in the program mode or remote program mode (depending on the keyswitch position) and a PROCESSOR MEMORY INVALID message appears on the 1770-T3 terminal.
Switch 6 is ON
If
Switch 7 may be either ON or OFF
If the mode select switch is in RP position with valid memory, the processor powers up in the same mode (run/program, remote test or remote test or remote program) that it powered down in. If the switch is not in the R/P position, then the power up mode is determined by the position of the switch (run or program).
And
Then
With an EEPROM installed in your processor Switch 6 is OFF
Switch 7 may be either ON or OFF
Contents of the EEPROM memory module area transferred to RAM memory whether or not RAM memory is valid. If switch 6 is OFF, your processor powers-up in the mode selected by the keyswitch. 2
Switch 6 is ON
Switch 7 is ON
Contents of the EEPROM memory module are not transferred to RAM memory is RAM memory is valid. 1 Contents of the EEPROM memory module are transferred to RAM memory if RAM memory is not valid. 2
Switch 6 is ON
Switch 7 is OFF
With a battery installed and a program stored in RAM memory, your processor powers-up in the mode identified by the position of the mode select switch. 1 Contents of the EEPROM memory module are not transferred to RAM memory. Without a battery installed and without a program stored in RAM memory, your processor powers-up in the program mode and a PROCESSOR MEMORY INVALID message appears on the 1770-T3 terminal.
1
2
If the mode select switch is in the RP position, then the processor powers-up in the last programmed mode or operation, i.e. Run/Program, Remote Test, Remote Program. If the mode select switch is in the RP position, then the processor powers-up running (RUN/PROG mode). We recommend that you put the mode select switch in the PROG position so that the processor will power-up in the program mode.
Step 4 - Installing Keying Bands and Field Wiring Arms
We ship plastic keying bands with each I/O chassis. With your fingers, insert two keying bands in the top backplane connectors of the I/O chassis. For the processor, place one keying band in the leftmost slot (Figure 4.14) between pins: 46 and 48 54 and 56
4-24
Page 65
Chapter 4 Installing Your Programmable Controller
Figure 4.14 Place the Keying Bands on the Backplane of the I/O Chassis
2 4 6 8 10 12 14
I/O chassis backplane connector
16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 use these numbers as a guide
ÉÉÉÉ keying bands (cat. no. 1777-RK)
ÉÉÉÉ
10313-I
Use the numbers to the right of the backplane socket as a guide when positioning the keying bands. See the installation instructions for the keying position of each I/O module. Do not place any I/O modules in the left-most slot. Your processor goes there.
ATTENTION: If keying bands (in general) are not installed, a module inserted into a wrong slot could be damaged by improper voltages connected through the wiring arm. Short circuits on the I/O module can result from misalignment if keying bands are not installed.
Snap each field wiring arm onto the lower horizontal bar of the I/O chassis (Figure 4.15). When I/O modules are in place, the field wiring arm pivots and connects to the module.
4-25
Page 66
Chapter 4 Installing Your Programmable Controller
Figure 4.15 Snap the Field Wiring Arm onto the I/O Chassis wiring arm horizontal bar
C-shaped bracket remove install
Step 5 - Installing I/O Modules
4-26
Insert each I/O module into its properly keyed slot by sliding it onto the plastic tracks of the I/O chassis (Figure 4.16). Snap the module locking latch over the I/O module.
Page 67
Chapter 4 Installing Your Programmable Controller
Figure 4.16 Place Each I/O Module into its Corresponding Keyed Slot in the I/O Chassis locking bar
I/O module card guides corresponding keyed slot
20213
ATTENTION: Do not force and I/O module into a backplane connector. Forcing an I/O module can damage the backplane connector or the I/O module.
Calculate the total current requirement for all installed modules to ensure that the sum does not exceed the limit of the I/O chassis’ power supply. The 1772-LWP, -LXP, and -LZP processor provides 4A to power the I/O modules. If you need additional power, you can choose either a 1771-P3 or 177-P4 power supply module to parallel to the 1772-LWP, -LXP, -LZP: Catalog Number
Input Voltage
Current to the Backplane
1771-P3
120V ac
3A
1771-P4
120V ac
8A
1771-P5
24V ac
8A
1771-P7
120/220V ac
16A