Page 187
Chapter 14 EAF Math Instructions
Exponential Enter an exponential function EAF rung like that shown in Figure 14.13. Figure 14.13 EAF Exponential Function Input and Display Rung 060 G 000 040 G 000
061 G 332 041 G 009
062 G 900 042 G 420
063 G 000 043 G 000
EXECUTE AUX FUNCTION FUNCTION NUMBER: 32 DATA ADDR: 040 RESULT ADDR: 060
Enter values for the operand. You can enter these values from the keyboard of your 1770-T3 terminal or through ladder diagram functions. Entry of an operand (exponent of e) of 9.42 yields an exponential function value of 012 332 . 900 000. Figure 14.14 shows how it is stored in the data table. Figure 14.14 EAF Exponential Format in the Data Table After Execution 17
16
15
0
Operand A
14 13
10 7
Data 0 Address
43
0
0
0
040
0
0
9
041
4
2
0
042
0
0
0
043 Result Address
Result
X
0
0
0
1
2
060
3
3
2
061
9
0
0
062
0
0
0
063 10355-I
14-15
Page 188
Chapter 14 EAF Math Instructions
Square Root This function finds the value of +x1/2= y. The Operand and Result words have the format: + xxx xxx . xxx xxx1/2= + yyy yyy . yyy yyy If you want to find the square root of a negative number, this function ignores the minus sign and finds the square root of the absolute value of the number. Enter an EAF square root function like that shown in Figure 14.15. Figure 14.15 EAF Square Root Function Input and Display Rung 060 G 000 040 G 000
061 G 012 041 G 144
062 G 000 042 G 420
063 G 000 043 G 000
EXECUTE AUX FUNCTION FUNCTION NUMBER: 05 DATA ADDR: 040 RESULT ADDR: 060
Enter the value for the Operand. You can enter this value from the keyboard of your 1770-T3 terminal or through ladder diagram functions. Entry of operand 144 produces the number 12. Figure 14.16 shows how the operand and the result are stored.
14-16
Page 189
Chapter 14 EAF Math Instructions
Figure 14.16 EAF Square Root Format in the Data Table After Execution 17
16
15
14 13
0
Operand A
10 7
Data 0 Address
43
0
0
0
040
1
4
4
041
0
0
0
042
0
0
0
043 Result Address
Result
X
S
0
0
0
0
060
0
1
2
061
0
0
0
062
0
0
0
063 10356-I
10 to the X
The 10 to the x function finds the value of 10x = y. The Operand and Result words have the format: x = exponent of 10 (maximum value = 5.999 999) y = resultant number (maximum of 6 digits) 10+/–x . xxx xxx = yyy yyy . yyy yyy Enter an EAF rung like that shown in Figure 14.17. Figure 14.17 EAF Power of 10 Function Input and Display Rung 060 G 000 040 G 000
061 G 243 041 G 002
062 G 221 042 G 386
063 G 000 043 G 000
EXECUTE AUX FUNCTION FUNCTION NUMBER: 37 DATA ADDR: 040 RESULT ADDR: 060
Enter values for the operand. You can enter these values from the keyboard of your 1770-T3 terminal or through ladder diagram functions. Entry of an operand (exponent of 10) of 000 002 . 386 000 yields an exponential value of 000 243 . 221 000. Figure 14.18 shows how it is stored in the data table.
14-17
Page 190
Chapter 14 EAF Math Instructions
Figure 14.18 EAF Power of 10 Format in the Data Table After Execution 17
16
15
14 13
0
Operand A
10 7
Data Address 0
43
0
0
0
040
0
0
2
041
3
8
6
042
0
0
0
043 Result Address
Result
0
0
0
060
2
4
3
061
2
2
1
062
0
0
0
063 10357-I
Reciprocal
The Reciprocal EAF instruction is a feature of the Mini-PLC-2/17 processor only. This EAF function finds the reciprocal of a number. The Operand and Result words have the format: 1/ +/–xxx xxx . xxx xxx = +/–yyy yyy . yyy yyy Enter an EAF rung like that shown in Figure 14.19. Figure 14.19 EAF Reciprocal Function Input and Display Rung 060 G 000 040 G 000
061 G 000 041 G 124
062 G 008 042 G 386
063 G 065 043 G 000
EXECUTE AUX FUNCTION FUNCTION NUMBER: 34 DATA ADDR: 040 RESULT ADDR: 060
Enter the value for the operand. Entry of operand 124 yields as its reciprocal value 0.008065. Figure 14.20 shows how it is stored in the data table.
14-18
Page 191
Chapter 14 EAF Math Instructions
Figure 14.20 EAF Reciprocal Format in the Data Table After Execution 17
16
15
0
Operand A
14 13
10 7
Data 0 Address
43
0
0
0
040
1
2
4
041
0
0
0
042
0
0
0
043 Result Address
Result
X
0
X
0
0
0
060
0
0
0
061
0
0
8
062
0
6
5
063 10358-I
BCD to Binary
The BCD to Binary conversion function converts a BCD Conversion number into a binary number. Its function number is 13 and the conversion takes the form: 0xx xxx = y yyy Important: When the result is displayed using a Get instruction, only the first 12 bits can be seen. Use a SEARCH 53 to look at all 16 bits. Enter an EAF rung like that in Figure 14.21 Figure 14.21 EAF BCD to Binary Conversion Function Input and Display Rung 060 G FFF 040 G 004
EXECUTE AUX FUNCTION 041 G 095
FUNCTION NUMBER: 13 DATA ADDR: 040 RESULT ADDR: 060
14-19
Page 192
Chapter 14 EAF Math Instructions
Enter the BCD number. Entry of the BCD number 004 095 produces the hexadecimal number FFF. If the Operand is greater than +32 767, the result 7FFFh is stored in the data table. However, you will see only FFF below the instruction. You must use a SEARCH 53 to see the entire word. If the Operand is more negative than –32 767, 8001 is displayed at the result address. All negative values are stored as two’s complement. Figure 14.22 shows how the result is stored in the data table. Figure 14.22 EAF BCD to Binary Conversion Format in the Data Table After Execution 17 16
15
14 13
10 7
0
Operand A
0
Data 0 Address
43 0
4
040
9
5
041 Result Address
Result
X
0
0
0
F
F
F
060 10359-I
Bit 16 of the first data address word is the sign bit of the BCD number. Bit 17 of the result address is the sign bit of the binary number. Bits 14-16 of the Result Address word are used if the operand is greater than 4095.
Binary to BCD
The BCD to Binary EAF function converts a Binary number into a BCD number. Its function number is 14 and the conversion takes the form: x xxx = 0yy yyy Enter an EAF rung like that in Figure 14.23 Figure 14.23 EAF Binary to BCD Conversion Function Input and Display Rung 060 061 G G 004 095 040 G FFF
14-20
EXECUTE AUX FUNCTION FUNCTION NUMBER: 14 DATA ADDR: 040 RESULT ADDR: 060
Page 193
Chapter 14 EAF Math Instructions
Enter a Binary number. Entry of the binary number FFF produces the BCD number 004 095. If you enter 7FFF (use SEARCH 53 and set the bits), 32 767 is displayed. All negative values are stored as two’s complement. Figure 14.24 shows how the result is stored in the data table. Bit 16 of the first Result Address word is the sign bit of the BCD number. Figure 14.24 EAF Binary to BCD Conversion Format in the Data Table After Execution 17 Operand A
16
15
14 13
0
0
0
10 7 F
Data 0 Address
43 F
F
040 Result Address
Result
X
0
0 0
0
4
060
9
5
061 10360-I
14-21