Page 260

Chapter

17

Jump Instructions and Subroutine Programming

Chapter Objectives

This chapter describes the instructions you can use to selectively jump over portions of a program. The instructions are: Jump Jump to Subroutine Label Return This chapter describes how jump instructions and subroutine programming direct the path of the program scan through the main program and the subroutine area.

Jump

A Jump instruction is an output instruction. It has an identification number from 00-07. When its rung is true, it instructs the processor to jump forward in the main program to the Label instruction having the same identification number. The main program executes from that point. 010

01 JMP

00

You can reduce scan time by selectively jumping over a portion of the program. Do not program in an area where the Jump instruction crosses the boundary between the main program and subroutine area, or vice-versa.

ATTENTION: Allowances should be made for conditions which could be created by the Jump instruction. Jumped program rungs are not scanned by the processor. Input conditions are not examined and outputs that are controlled by these rungs remain in their last state. Timers and counters cease to function. Critical rungs should be re-programmed outside of the jumped section in the program.

17-1

Page 261

Chapter 17 Jump Instructions and Subroutine Prorgramming

Jump to Subroutine

The Jump to Subroutine instruction is an output instruction. It has an octal identification number from 00-07. When its rung is true, it instructs the processor to jump from the main program to the label instruction having the same number in the subroutine area. Subroutine execution begins at that point. This instruction always causes the processor to cross the boundary from the main program to the subroutine area. 02

010

JSR 00

Label

The Label instruction is the target for both the Jump and Jump to Subroutine instructions. Label instructions are assigned octal identification numbers from 00-07. The label identification number must be the same as that of the Jump and/or Jump to Subroutine instruction with which it is used. A Label instruction can be defined only once, meaning that a label with a given identification number can only appear in one location. However, a Label instruction can be the target of jumps from more than one location. The Label instruction is always logically true. Programmed as the first condition instruction in the rung. If conditions precede a Label instruction, they will be ignored by the processor during a jump operation. Do not program with a program control instruction. Important: If conditions precede a Label instruction, they are ignored by the processor during a jump operation. 01

010

010

00

00

LBL

ATTENTION: Do not place a Label instruction in a ZCL or MCR zone. When jumping over a start fence, the processor executes the program from the label to the end fence as if the start fence had been true. The start fence may have been false intending that all outputs within the zone are controlled by the output override instruction (i.e. OFF for MCR or last state for ZCL instructions). Failure to observe this warning could cause unexpected operation with possible damage to equipment and/or injury to personnel.

17-2

Page 262

Chapter 17 Jump Instructions and Subroutine Programming

Return

The Return instruction is an output instruction. It is used only in the subroutine area to terminate a subroutine or selectable timed interrupt and return the processor to the main program or, in the case of nested subroutines, return program execution to the preceding subroutine. It returns program execution to the instruction immediately following the Jump to Subroutine instruction that initiated the subroutine. Program execution continues from that point. It is programmed as an output instruction without an identification number in the subroutine area. It is usually programmed unconditionally. Every subroutine must have a Return instruction. RET

Entering Jump Instructions

Enter one of the above instructions by performing the following steps. 1.

Press -(JMP)-, -(SR)-, or [SHIFT] -(RET)-.

Important: Do not perform step 2 for a Return instruction. 2.

Enter <octal identification number>.

Removing a Label Instruction Remove the Label instruction by performing the following steps. 1.

Position the cursor over the Label instruction you want to remove.

2.

Press [Remove][Shift][LBL].

Editing Jump Instructions Edit one of the above instructions by performing the following steps. 1.

Position the cursor over the instruction you are going to edit.

2.

Press [Remove]

3.

Press -(JMP)-, -(JSR)-, or [SHIFT]-(RET)- or any other appropriate instruction type key.

Important: Do not perform step 3 for a Return instruction. 4.

Subroutine Area Instruction

Enter <octal identification number>.

The subroutine area is located in the memory between the end of the main program and the beginning of the message store areas (Figure 17.1). The subroutine area allows you to store small programs you plan to access periodically. Subroutines are not scanned unless you program the processor to jump into this area.

17-3

Page 263

Chapter 17 Jump Instructions and Subroutine Prorgramming

Figure 17.1 Subroutine Area Total Decimal Words

Timer Counter Preset Values (PR) (or Bit Word Storage)

Varies

Octal Word Address

Data Table 177 200

Main Program

Varies

Subroutine Area

Varies

User Program

Subroutines

Varies

End

Varies

Message Storage Area (if used)

17-4

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

1920 3968 7808

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

2048 4096 7936

User Program

Message Storage 3577 7577 17177

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

3777 7777 17377

Mini-PLC-2/02 Mini-PLC-2/16 Mini-PLC-2/17

Page 264

Chapter 17 Jump Instructions and Subroutine Programming

You can program a maximum of 8 subroutines in the subroutine area. Each subroutine begins with a Label instruction and ends with a return instruction. The Return should be an unconditional rung. The subroutine area serves as the end of the main program and defines the beginning of the subroutine area (Figure 17.2). Figure 17.2 Subroutine Programming Example 01 JSR

112 00 112

013 10 012 U OFF 11 200 U OFF 17

02 114 06 116 02 116 02 116 13 SUBROUTINE AREA 01 LBL

114

012

06

11

116

116

116

FILE TO FILE MOVE

11

12

13

COUNTER ADDR: 200 POSITION: 001 FILE LENGTH: 007 FILE A: 400- 406 FILE R: 500- 506 RATE PER SCAN: 007

200 EN

17

200 DN 15 RET

You can establish a subroutine area by performing the following steps. 1. Move the cursor down to the end of the main program. 2. Press [Shift] [SBR]

17-5

Page 265

Chapter 17 Jump Instructions and Subroutine Prorgramming

The boundary marker subroutine area appears. A Subroutine Area instruction can only be programmed after the last instruction in the main program. The Subroutine Area instruction cannot be inserted between rungs in the main program. It requires 1 word of memory, it can be programmed only once, and it cannot be removed except by clearing the memory. You cannot nest subroutine programs by inserting a Jump To Subroutine instruction within the subroutine area, but it is possible to jump from one subroutine to another using a Jump instruction.

17-6