Page 40

Chapter

4

Installing Your Programmable Controller

Chapter Objectives

This chapter discusses the location and methods of installing your processor. When you have finished, you should be able to: determine where to locate your processor system install your processor system

Related Hardware

Table 4.A lists the hardware needed to install your processor system. Table 4.A Hardware for Your Processor System Allen-Bradley Hardware

Catalog Number

I/O chassis

1771-A1B, -A2B, -A3B, -A3B1, -A4B

I/O modules

1771 product line

Industrial terminal

1770-T3 series C

Power supplies

1771-P3, -P4, -P5, -P7

Emergency stop

800 product line switches

Master control relay

700 product line

Disconnects

1494 product line

Suppression devices

599-K04, 700-N24, 1401-N10

The quantity of the hardware you need depends on your application. Consult your local Allen-Bradley sales engineer or distributor for more information concerning these items. In addition to our hardware, we recommend: a metal enclosure to protect your processor from electromagnetic interference (EMI) noise and airborne contaminants enclosure backpanel power supplies for I/O devices 6.35 mm (0.25 inch) bolts power cable for ac input power electrical tape or shrink tubing tie wraps for wires

4-1

Page 41

Chapter 4 Installing Your Programmable Controller

Planning Your Processor System

A well-planned layout is essential for the installation of your processor. You should consider the following factors: location environment mechanical protection conductor categories raceway layout power distribution surge suppression Location Determining the proper location should be your primary concern. We specify: This Characteristic:

Should Meet this Specification:

Operating temperature

0 to 60oC (32 to 140oF)

Storage temperature

-40 to 85oC (-40 to 185oF)

Relative humidity

5 to 95% (without condensation)

Environment Separate the processor system from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the processor. Cooling air must not exceed 60oC (140oF) at any point immediately below the processor. If the air temperature does exceed 60oC, install: fans inside the enclosure to bring in filtered air or recirculate internal air, or air conditioning/heat exchangers Follow these guidelines when installing your processor system: Allow six vertical inches above and below all processor components, including other processors. Allow four horizontal inches on the sides of each processor component. When you use more than one processor in the same area, allow six horizontal inches between each processor. Allow two inches (vertical and horizontal) between the processor and the wiring duct or terminal strips. Mount the I/O chassis horizontally to allow convection cooling.

4-2

Page 42

Chapter 4 Installing Your Programmable Controller

Mechanical Protection You provide the enclosure for your processor system. This enclosure is the primary means of protecting your processor system from atmospheric contaminants such as oil, moisture, dust, corrosive materials, or other harmful substances. We suggest that you use an enclosure that conforms to the National Electrical Manufacturer’s Association standard (NEMA Standard Publication No. ICS 6). Mount the enclosure in a position that lets you fully open the doors. You need easy access to the processor’s wiring and related components. When choosing the enclosure size, allow extra space for isolation transformers, fusing, disconnect switch, master control relay and terminal strips. Your processor requires a minimum of eight inches of space from the rear of the chassis to the innermost front surface of the enclosure. Conductor Categories When planning your raceway layout, classify into the following categories all wires and cables connecting your processor system. See the documentation for each specific I/O module for its individual classification. Category-1 Conductors Category-1 conductors are, in general, high-power conductors that are, therefore, more tolerant of electrical noise than category 2 conductors and may also generate more noise. They include: ac power lines high-power ac I/O lines, They connect to ac I/O modules that are rated for high power and high noise immunity. high-power dc I/O lines, They connect to dc I/O modules that are rated for high power or have input circuits with long time-constant filters for high noise rejection. They typically connect to devices such as: - hard-contact switches - relays - solenoids

4-3

Page 43

Chapter 4 Installing Your Programmable Controller

Category-2 Conductors Category-2 conductors are, in general, low-power conductors that are, therefore, less tolerant of noise than category-1 conductors and should also generate less noise. They include: serial communication cables, They connect between processors or to remote I/O adapter modules, programming terminals, computers, or data terminals. low-power dc I/O lines, They connect to dc I/O modules that are rated for low power and have input circuits with short time-constant filters to detect short pulses. They typically connect to devices such as: - proximity switches photo-electric sensors TTL devices encoders motion-control devices analog devices low-power ac-dc I/O lines, They connect to I/O modules that are rated for low power such as low-power contact-output modules. Category-3 Conductors Category-3 conductors interconnect the processor components within an enclosure. Processor cables include: processor power cables, provide backplane power to processor components local I/O interconnect cables, connect to local I/O adapter modules processor-peripheral cables, connect processors to their communication interface modules Raceway Layout Guidelines The following are general guidelines for routing wires and cables for your processor system. These guidelines apply to wire and cable routing both inside and outside of the enclosure. Follow these guidelines to guard against coupling noise from one category conductor to another. All category-1 conductors can be routed with machine power conductors of up to 600V ac (feeding up to 100 hp devices) if this does not violate local codes. Article 300-3 of the National Electrical Code requires that all conductors (ac and/or dc) in the same raceway must be insulated for the highest voltage applied to any one of the conductors in the raceway. 4-4

Page 44

Chapter 4 Installing Your Programmable Controller

All category-2 conductors must be properly shielded, where applicable, and routed in a separate raceway. If a category-2 conductor must cross power feed lines, it should do so at right angles. Route category-2 conductors at least 1 foot from 120V ac power lines, 2 feet from 240V ac power lines, and 3 feet from 480V ac power lines. Route category-2 conductors at least 3 feet from any electric motors, transformers, rectifiers, generators, arc welders, induction furnaces, or sources of microwave radiation. If a category-2 conductor is in a metal raceway or conduit, that raceway or conduit must be well grounded along its entire length. All category-3 conductors should be routed external to all raceways or in a raceway separate from any category-1 or category-2 conductors. Power Distribution In many applications, you can connect the processor power supply directly to the secondary of a transformer (Figure 4.1 and Figure 4.2). The transformer can provide dc isolation from other equipment not connected to that transformer secondary. Connect the transformer primary to the ac source; connect the high side of the transformer secondary to the L1 terminal of the power supply; connect the low side of the transformer secondary to the neutral (common) terminal of the power supply. Sizing the Transformer Note that the external-transformer rating (in VA) of each supply is 2.5 times its input power requirements (in Watts). This is necessary because, converting ac to dc draws power only from the peak of the ac voltage wave-form. If the transformer’s rating is too small, it will clip the peak of the sine wave. When the input voltage is still above the lower voltage limit, the power supply will sense this clipped wave form as a low voltage and shut down the processor prematurely. If the transformer is too large, it will not provide as much isolation as a transformer of proper size because a larger noise spike on the primary can pass through to the secondary.

4-5

Page 45

Chapter 4 Installing Your Programmable Controller

To determine the required rating of the transformer, add the external-transformer rating for the power supply and all other power requirements (input circuits, output circuits). The power requirements must take into consideration the surge currents of devices controlled by the processor. Choose a transformer with the closest standard transformer rating above the calculated requirements. For example, the external-transformer rating of a 1771-P4S power supply is 150VA. A 150VA transformer could be used if a 1771-P4S power supply were the only load. A 500VA transformer should be used if there were 350VA of load in addition to that of the 1771-P4S power supply. Undervoltage Shutdown Each power supply is designed to generate a shutdown signal if the ac line voltage drops below its lower voltage limit. A shutdown in that situation is necessary to ensure that only valid data is stored in memory. The controller resumes operation when the line voltage reaches the lower voltage limit again.

4-6

Page 46

Chapter 4 Installing Your Programmable Controller

Figure 4.1 Grounded ac Power-Distribution System with Master Control Relay disc 1FU

L1

L1 incoming ac

2FU

L2

L2 3FU L3 to motor starters

L3 H1

H4 H3 step-down transformer

H2

4

FUSE use any number of E-stop switches in series

X1 enclosure wall backpanel ground bus

X2 start grounding electrode conductors

CRM grounding electrode conductor to ground electrode system

1

CRM I/O chassis power supply L1 N connect when applicable GND

3 user dc supply

CRM 2

CRM output device input module wiring arm output module wiring arm

+ – to dc I/O devices input device

1

2

3

4

To minimize EMI generation, you should connect a suppression network: for 120V ac, use Allen-Bradley cat. no. 700-N24; for 220/240V ac, use cat. no. 599-KA04. To minimize EMI generation, you should connect a suppression network: for 120V ac, use Allen-Bradley cat. no. 700-N24; for 220/240V ac, use cat. no. 599-KA04. For a power supply with a groundable chassis, this represents connection to the chassis only. For a power supply without a groundable chassis, this represents connection to both the chassis and the GND terminal. In many applications, a second transformer provides power to the input circuits and power supplies for isolation from the output circuits. 102300-I

4-7

Page 47

Chapter 4 Installing Your Programmable Controller

Figure 4.2 Ungrounded ac Power-Distribution System with Master Control Relay disc incoming ac

1FU

L1

2FU

L2

3FU

L3

L1 L2 L3

H1 to motor starters

H4 H3 step-down transformer

H2

4

FUSE

FUSE X1 enclosure wall backpanel ground bus

X2

1LT

2LT use any number of E-stop switches in series grounding electrode conductors start grounding electrode conductor to groundi electrode system

CRM 1

CRM I/O chassis power supply L1 N

GND connect when applicable

3 user dc supply

CRM

CRM 2 output device input module wiring arm

CRM output module wiring arm

+ – to dc I/O devices input device

1

2

3

4

To minimize EMI generation, you should connect a suppression network: for 120V ac, use Allen-Bradley cat. no. 700-N24; for 220/240V ac, use cat. no. 599-KA04. To minimize EMI generation, you should connect a suppression network: for 120V ac, use Allen-Bradley cat. no. 700-N24; for 220/240V ac, use cat. no. 599-KA04. For a power supply with a groundable chassis, this represents connection to the chassis only. For a power supply without a groundable chassis, this represents connection to both the chassis and the GND terminal. In many applications, a second transformer provides power to the input circuits and power supplies for isolation from the output circuits. 10301

4-8

Page 48

Chapter 4 Installing Your Programmable Controller

Second Transformer Allen-Bradley power supplies have circuits which suppress electromagnetic interference from other equipment. However, it is useful to isolate output circuits from power supplies and input circuits to guard against output transients from being induced into inputs and power supplies. Therefore, in many applications, power is provided to the input circuits and power supplies through a second transformer as in Figure 4.3. In some applications, a special kind of transformer is used for the second transformer. Isolation Transformer For installations near particularly excessive electrical noise generators, an isolation transformer (for the second transformer) will provide further suppression of electromagnetic interference from other equipment. The output devices being controlled should draw power from the same ac source as the isolation transformer, but not from the secondary of the isolation transformer (Figure 4.3). Constant-Voltage Transformer In applications where the ac power source is especially “soft” and subject to unusual variations, a constant-voltage transformer can stabilize the ac power source to the controller, thereby minimizing shutdowns. However, the constant-voltage transformer must provide a sinusoidal output. If the controller power supply receives its ac power through a constant-voltage transformer, the input devices connected to the I/O chassis must also receive their ac power through the same constant-voltage transformer. If the inputs receive their ac power through another transformer, the ac source voltage could go low enough that erroneous input data enters memory while the constant-voltage transformer prevents the power supply from shutting down the controller. The output devices being controlled should draw power from the same ac source as the constant-voltage transformer, but not from the secondary of the constant-voltage transformer (Figure 4.3).

4-9