Page 83

Chapter

5

Starting Your Processor

Chapter Objectives

This chapter covers the initial start-up of your processor system. It explains how to: document the processor check the operation of your processor before supplying power understand hardware addressing start the processor system test the input and output devices

Verify Your System's Addresses

Verify your I/O devices’ and field wiring arms’ wire numbers using the Connection Diagram Addressing Worksheet (Figure 5.1).

5-1

Page 84

5-2

PROJECT NAME

(16-point modules)

DESIGNER

DATE

PAGE

Bulletin 1771 I/O chassis CONNECTION DIAGRAM ADDRESSING WORKSHEET

OF

Chapter 5 Starting Your Processor

Figure 5.1 Connection Diagram Addressing Worksheet

Page 85

Chapter 5 Starting Your Processor

Status Indicators for I/O Modules

Most I/O modules have status indicators on the front panel. Each indicator corresponds to a terminal on the I/O module’s field wiring arm (Figure 5.2). When status indicators on input modules light, power is present at the input terminal. When status indicators on 8-point output modules light, power is present at the output terminal. When status indicators on 16- and 32-point output modules light, logic to turn on the indicator is true; this does not mean that power is present at the output terminals. Figure 5.2 Status Indicators status indicators corresponds to terminals

12081

Status indicators help isolate the source of a fault in your hardware. A hardware fault can originate from: improper I/O device operation wiring error loss of external power to the I/O module loss of power/signal from the I/O device The user manual or installation instructions for each I/O module explains the operation of the module’s status indicators.

5-3

Page 86

Chapter 5 Starting Your Processor

Addressing Your Hardware

You must properly address your hardware so that it relates to your ladder diagram program. In the ladder diagram program, the input or output instruction address is associated with a particular I/O module terminal and is identified by a 5-digit address (Figure 5.3). Addressing links a hardware terminal to a data table location (input), and links a data table location to a terminal (output). Figure 5.3 Hardware/Data Table Addressing Relationships Concept

Example

Hardware Terminology Input (1) or Output (0)

Output: 0

Rack No. (1-7)

Rack No.: 1

I/O Group No. (0-7)

I/O Group No: 0

Terminal No. (00-07, 10-17)

Terminal No.: 12

X X X/XX Word Address

Hardware Terminology

Bit Address Data Table Terminology

0 1 0/12 Word Address

Instruction Address

Bit Address Data Table Terminology

10146–I

Concept XXX

XXX

XX

XX

Example

5-4

112

010

11

12

10327-I

Page 87

Chapter 5 Starting Your Processor

In Figure 5.3, reading from left to right, the: first number denotes the type of module: - 0 output - 1 input second number denotes the I/O rack: - In 2-slot addressing, the rack number is always 1. - In 1-slot addressing, the rack number is either 1 or 2. - In 1/2-slot addressing the rack number may be 1, 2, 3, or 4. third number denotes an I/O group (0 to 7). fourth and fifth numbers denote a terminal: - In 2-slot addressing, 00 through 07 for the left slot of the I/O group, 10 through 17 for the right slot of the I/O group. - In 1-slot addressing, 00 through 17 for each I/O group (slot). - In 1/2-slot addressing, 00 through 17 for the upper half of each I/O module (one group) and 00 through 17 for the lower half of each module (another group). 2-Slot Addressing The processor addresses two I/O module slots as one I/O group. Each physical 2-slot I/O group is represented by a word in the input image table and a word in the output image table. Each input terminal corresponds to a bit in the input image table word and each output terminal corresponds to a bit in the output image table word. The maximum number of bits available for one 2-slot I/O group is 32: 16 bits in the input image table word and 16 bits in the output image table word. The type of discrete I/O module you install, either 8-point (standard density) or 16-point (high-density, used in complementary mode) determines the number of bits in the words that are used. You select 2-slot addressing by setting switches 4 and 5 of the I/O chassis backplane switch assembly: Switch 4 to the OFF position Switch 5 to the OFF position

5-5

Page 88

Chapter 5 Starting Your Processor

Using 8-Point I/O Modules I/O modules generally provide eight input terminals or eight output terminals. Figure 5.4 illustrates the 2-slot I/O group concept with two 8-point input modules. Figure 5.5 illustrates the 2-slot I/O group concept with an 8-point input and an 8-point output module. Figure 5.4 Illustration of 2-Slot Addressing with Two 8-Point Input Modules 2-slot I/O group input terminals input terminals

10 11 12 13 14 15 16 17

00 01 02 03 04 05 06 07

Output image table word corresponding to the I/O group 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 unused Input image table word corresponding to the I/O group 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

11867

5-6

Page 89

Chapter 5 Starting Your Processor

Figure 5.5 Illustration of 2-Slot Addressing with 8-point Input and Output Modules 2-slot I/O group input terminals output terminals 10 11 12 13 14 15 16 17

00 01 02 03 04 05 06 07

Output image table word corresponding to the I/O group 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 output bits used Input image table word corresponding to the I/O group 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 input bits used

11868

Using 16-Point I/O Modules High-density (16-point) I/O modules provide 16 input terminals or 16 output terminals. 16-point I/O modules use a full word in the input or output image table. Important: 16-point modules may only be used in a complimentary fashion in 2-slot addressing mode. Two 16-point modules, one input and one output, can be used in a 2-slot I/O group (Figure 5.6).

5-7