For the Allen-Bradley 1772-LW /LWD, Allen-Bradley 1772-LWP, Allen-Bradley 1772-LX / LXP and Allen-Bradley 1772-LZP

Page 90

Chapter 5 Starting Your Processor

Figure 5.6 Illustration of 2-Slot Addressing with 16-Point Input and Output Modules 2-slot I/O group input terminals output terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

16-point input and output modules use two words (one input, one output) of the image table. Output image table word corresponding to the I/O group (all bits used) 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Input image table word corresponding to the I/O group (all bits used) 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 11869

Because these modules use a full word in the image table, the only type of module you can use in a 2-slot I/O group with a 16-point module is one that performs the opposite (complementary) function; an input module complements an output module and vice-versa. You can use an 8-point module with a 16-point module in a 2-slot group; however, it too must perform the opposite function. Eight bits in the I/O image table are unused. Important: 32-point modules will not work in 2-slot addressing mode.

5-8

Page 91

Chapter 5 Starting Your Processor

Assigning I/O Rack Numbers When you select 2-slot addressing, each pair of slots (one I/O group) is assigned to the corresponding pair of words in the input and output image tables. You assign one I/O rack number to eight I/O groups (Figure 5.7). Figure 5.7 I/O Image Table and Corresponding Hardware for One Assigned Rack Number for 2-Slot Addressing word # 0 1 2 3 4 5 6 7 output image table 0

1

2

3

4

5

6

7

When you select 2-slot addressing, each pair of slots is assigned an input image table word and an output image table word.

I O

I O

I O

I O

I O

I O

I O

I O word # 0 1 2 3 4 5 6 7 input image table 13075

5-9

Page 92

Chapter 5 Starting Your Processor

1-Slot Addressing The processor addresses one I/O module slot as one I/O group. Each 1-slot I/O group is represented by a word in the input image table and a word in the output image table. You have 16 input bits and 16 output bits available for each slot. This lets you use any mix of 8- and 16-point I/O modules in the I/O chassis in any order. 32-point modules must be used in complementary arrangements. Important: For full compatibility with 1-slot addressing you must use the series C, revision A (or later) 1770-T3 industrial terminal. You select 1-slot addressing by setting switches 4 and 5 of the I/O chassis backplane switch assembly: Switch 4 to the OFF position Switch 5 to the ON position The physical address of each I/O group (1-slot) corresponds to an input and an output image table word. The type of module you install (either 8-point or 16-point I/O) determines the number of bits in these words that are used. Figure 5.8 (on the next page) illustrates the 1-slot I/O group concept with one 16-point I/O module. This module group uses an entire word of the image table. You can use an 8-point I/O module with 1-slot addressing, but the module uses only 8 bits of the I/O image table word (8 bits in the I/O image table are unused).

5-10

Page 93

Chapter 5 Starting Your Processor

Figure 5.8 Illustration of 1-Slot Addressing with 16-Point I/O Modules 1-slot I/O group

1-slot I/O group input terminals output terminals

00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

OR

Output image table word corresponding to the I/O group. 17 16 15

1

4 03 02 01 00 unused Input image table word corresponding to the I/O group. 17 16 15

00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1

4 03 02 01 00

Output image table word corresponding to the I/O group. 17 16 15

1

4 03 02 01 00

Input image table word corresponding to the I/O group. 17 16 15

1

4 03 02 01 00 unused The corresponding opposite image table word is not used when 16-point modules are used.

15245

5-11

Page 94

Chapter 5 Starting Your Processor

Assigning I/O Rack Numbers When you select 1-slot addressing, each slot is an I/O group. You still assign one I/O rack number to eight I/O groups; therefore, in a 16-slot I/O chassis you now have two I/O racks (Figure 5.9). Figure 5.9 Assigning I/O Rack Numbers with 1-Slot Addressing I/O group number assigned I/O rack number 1 01

23

45 assigned I/O rack number 2 67

01

23

1771-A4B I/O chassis using 1-slot addressing.

45

67

13077

In Figure 5.3, we showed how the 5-digit input or output instruction is associated with a particular I/O module terminal. With two I/O racks you use the instruction address to identify which rack you are communicating with. Figure 5.10 illustrates addressing two modules, each in the same I/O group number but in different assigned racks of a single I/O chassis.

5-12

Page 95

Chapter 5 Starting Your Processor

Figure 5.10 Example of 1-Slot Addressing I/O group number rack 1 01

23

45

67

01

23

45

67

I/O group 1 address 121

I/O group 1 address 111 input rack rack 2

I/O group

13499

Using 32-Point I/O Modules 32-point I/O modules provide 32 input or 32 output terminals. 32-point I/O modules use two full words in the input or output image table. In 1-slot addressing mode, 32-point modules must be placed in a complimentary fashion; a 32-point input module must be next to any output module and vice versa. If 32-point modules are not placed in a complimentary fashion when in 1-slot addressing mode, the PROC RUN LED indicator will continuously blink green and the processor will not operate. Important: When addressing a block transfer module, it must be addressed by the lowest group number that it occupies and at slot 0. For example: a 2-slot block transfer module in rack 1, groups 2 and 3 (slots 3 and 4) would be addressed (by rack-group-slot) at location 120.

5-13

Page 96

Chapter 5 Starting Your Processor

1/2-Slot Addressing When you select 1/2-slot addressing, the processor addresses one-half of an I/O module slot as one I/O group. The physical address of each I/O slot corresponds to two input and two output image table words. The type of module you install (8, 16 or 32 I/O points) determines the number of bits in these words that are used. With 1/2-slot addressing, since 32 input bits and 32 output bits are set aside in the processor’s image table for each slot (16 input image table bits and 16 output image table bits times 2 groups per slot = 32 of each), you may use any mix of I/O modules (8, 16 or 32 point) in the I/O chassis. You select 1/2-slot addressing by setting switches 4 and 5 of the I/O chassis backplane switch assembly: Switch 4 to the ON position Switch 5 to the ON position Figure 5.11 illustrates the 1/2-slot addressing concept with a 32-point I/O module. A 32-point I/O module (two 1/2-slot I/O groups) uses two input or two output words of the image table. I/O group applies to the upper 16 points; I/O group 1 applies to the lower 16 points. You can use 8-point and 16-point I/O modules with 1/2-slot addressing but the rest of the bits are unused. They may be addressed through either I/O module group. Important: For full compatibility with 1/2-slot addressing you must use a series C, revision B (or later) 1770-T3 industrial terminal.