For the Allen-Bradley 1772-LW /LWD, Allen-Bradley 1772-LWP, Allen-Bradley 1772-LX / LXP and Allen-Bradley 1772-LZP

Page 97

Chapter 5 Starting Your Processor

Figure 5.11 Illustration of 1/2-Slot Addressing Using a 32-Point I/O Module 32-point Input Module

1/2-slot I/O Group 0

1/2-slot I/O Group 1

Bit # 01 03 05 07 11 13 15 17 01 03 05 07 11 13 15 17 -

Bit # 00 02 04 06 10 12 14 16 00 02 04 06 10 12 14 16 -

Input Word 0 17 1/2-slot I/O Group 0

10

7

0

Output Word 0 17

10

7

0

Image Table Words Allocated for I/O Group 0

Unused

Input Word 1 1/2-slot I/O Group 1

17

10

7

0

Output Word 1 17

10

7

0

Image Table Words Allocated for I/O Group 1

Unused

10335-I

5-15

Page 98

Chapter 5 Starting Your Processor

Assigning I/O Rack Numbers When you select 1/2-slot addressing, each slot corresponds to two I/O groups. You still assign one rack number to eight groups; however, with 1/2-slot addressing this requires only four slots. Thus, in a 16-slot chassis, you now can have four I/O racks (Figure 5.12). Figure 5.12 Assigning I/O Rack Numbers with 1/2-Slot Addressing I/O group number

Rack 1 0-3

I/O Groups 0,1 I/O Groups 2,3

4-7

Rack 2 0-3

4-7

Rack 3 0-3

4-7

0-3

4-7

I/O Groups 6,7 I/O Groups 4,5 1771-A4B I/O Chassis using 1/2-slot addressing

5-16

Rack 4

15246

Page 99

Chapter 5 Starting Your Processor

Figure 5.13 illustrates addressing 4 modules, each with the same I/O group number, but in the four different racks of a single I/O chassis. Figure 5.13 Group Address of a Module in Four Different Racks 10337-I

I/O group number

Rack 1 0-3

I/O group 1 address 111 input rack

4-7

Rack 2 0-3

4-7

I/O group 1 address 121

Rack 3 0-3

4-7

I/O group 1 address 131

Rack 4 0-3

4-7

I/O group 1 address 141

15247

I/O group

Important: When addressing a block transfer module, it must be addressed by the lowest group number that it occupies and at slot 0. For example: a 1-slot block transfer module in rack 1, groups 2 and 3 (slot 2) would be addressed (by rack-group-slot) at location 120. Be aware that this module is occupying group 2, slots 0 and 1, and group 3, slots 0 and 1.

5-17

Page 100

Chapter 5 Starting Your Processor

Before You Supply AC Power ATTENTION: Unexpected machine motion during system start-up can damage equipment and injure personnel.

Disconnect any device that might cause machine motion to occur when it is energized. Before you supply ac power to your processor do the following: 1.

Measure the ac line voltage and make sure it corresponds to the system power supply. Verify the L1, L2 and Chassis Gnd connections (L1 = ac high, L2 = ac return).

2.

Check the wiring of: main disconnect switch or circuit breaker master control relay emergency stop switches

Testing Output Devices

3.

Check the power cable connections. Make sure plugs are securely held in their sockets.

4.

Check the location and chassis positioning of each I/O module. All I/O chassis latches must be snapped down. All field wiring arms must be connected with their corresponding I/O modules.

5.

Disconnect all motors to ensure that no power-driven machine can start when you first apply power to the processor. Alternatively, disconnect the output device at its terminal strip.

6.

Test each output point and input point of each module in accordance with the suggestions of the following sections.

There are four ways to test output devices, using: a pushbutton (you supply the pushbutton) force functions (through the industrial terminal). (See chapter 26.) using the 1771-SIM switch/indicator module bit monitor/manipulation (SEARCH 53). (See chapter 25.)

5-18

Page 101

Chapter 5 Starting Your Processor

Using Pushbuttons ATTENTION: Use only trained personnel to conduct this test. Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.

To use a pushbutton to test your output devices, do the following: 1.

Connect a normally-open/momentary-close pushbutton switch as an input device to an input module.

2.

Connect the industrial terminal to your processor. (See chapter 4.)

3.

Select the RUN mode of operation.

4.

Use an examine-on address corresponding to the address of the pushbutton. Use an energize address corresponding to the output device being tested. For example, enter a rung similar to this one: 111

014

14

00

ATTENTION: Test only one rung at a time. Do not program multiple rungs; unpredictable machine operation can occur.

5.

Close the pushbutton switch and see if the input and output address instructions are intensified

6.

If the output instruction is not intensified, verify your test setup and the input address.

7.

Make sure that the output module’s status indicator lights. If the indicator lights, repeat the setup procedure for another output device.

8.

If the indicator does not light, check the following: power source for the output device I/O chassis power supply connections to the field wiring arm address of the output I/O module (rack, group, slot, terminal) examine-on address of the pushbutton switch

5-19

Page 102

Chapter 5 Starting Your Processor

Using the 1771-SIM Module The Switch/Indicator module is compatible with any 1771 I/O chassis. It has 8 switches to simulate 8 inputs and it has 8 LED’s to indicate when an addressed output is active. It requires no external power. See publication 1771-2.106 for more information.

Testing Input Devices ATTENTION: Use only trained personnel to conduct this test. Have a trained person at appropriate emergency stop switches to de-energize output devices that could cause hazardous operation.

To test your input devices, do the following:

ATTENTION: Do not reach into a machine to actuate a switch since unexpected machine motion can occur. Use a wooden stick or other nonconductive device to guard against electrical shock. Failure to observe this warning may injure personnel.

1.

Connect the industrial terminal to your processor (see chapter 4).

2.

Select the TEST mode of operation.

3.

Use an examine-on address corresponding to your input device address. Use an energize-output address that is an internal storage bit. For example, enter a rung similar to this one:

4.

5-20

111

200

14

00

Manually turn on one input device and observe that the input instruction is intensified and the input module’s status indicator lights. If both do, repeat this procedure for another input device. Continue until all devices are tested.

Page 103

Chapter 5 Starting Your Processor

5.

If the instruction does not intensify, then: repeat the test procedure check your input module call your Allen-Bradley sales engineer or distributor

6.

If the indicator does not light, check: power source for the input device wiring from the input device connection to the field wiring arm’s terminal input device verify the address of the input device input terminal

Using The 1771-SIM The Switch/Indicator module is compatible with any 1771 I/O chassis. It has 8 switches to simulate 8 inputs and it has 8 LED’s to indicate when an addressed output is active. It requires no external power. See publication 1771-2.106 for more information.

5-21