The text of a manual · part 21 of 45
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Chapter 10 - Communicating with Devices on a Serial Link, pages 167 to 174
Pages 167 to 174 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 167
Communicating with Devices on a Serial Link
10-17
To create station lists, place each station address in an individual word in a poll file (normal and/or priority) starting at word 2. The poll file layout is as follows: This Word in a Poll File Word 0 Word 1
Contains this Information total number of stations in the list address location (poll offset) of the station currently being polled For example: a value of 1 means the station address stored in word 2 is being polled, 2 means the address stored in word 3 is being polled, etc.
Word 2 through word xx
This word is automatically updated by the master station as a new remote station is polled. remote station address in the order that the station should be polled
To place a station address in a poll file, do the following: 1. Access the data monitor in your programming software. 2. Specify the address of the integer file that is either the normal poll file or priority poll file (e.g., if the normal poll file is N11, then you specify N11:0). 3. Enter the station addresses of the remote stations you want in the poll list starting at word 2. Put them in the order you want them polled. IMPORTANT
Station addresses are octal addresses. The poll files are integer files. The default radix is decimal. To properly enter station addresses in a poll file, you must either: • change the radix of the file to octal • convert the octal station addresses to decimal before entering the addresses
Below is an example of a station list containing three stations: octal addresses 10, 11, and 12 have been entered. Station 12 (10 decimal) is being polled. Poll File
Word 0
Word 1
Word 2
Word 3
Word 4
N:11
3
3
08
09
10
N:xx total number of stations pointer showing the station address being polled (Station 12 in word 4 is being polled.)
address of first station in list address of second station in list address of third station in list
Publication 1785-UM012D-EN-P - July 2005
Page 168
10-18
Communicating with Devices on a Serial Link
Configure Channel 0 for User Mode (ASCII Protocol) To configure channel 0 for user mode, use the user mode configuration screen in your programming software.
configure the serial communications as user (ASCII)
specify the details
This Field
Specifies
Configure by Doing the Following
Diagnostic file
The file containing the channel’s status information
Enter an integer file number (10-999). ATTENTION: Assign a unique diagnostic file to each channel. Do not assign a diagnostic file that is the I/O status file you assigned or any other used integer file. Unpredictable machine action can result. Important: You must define a diagnostics file for a channel configured for anything but unused (even if you are not using the channel) if you want to get status information for that channel.
Remote mode change
Whether the remote mode change option is enabled
Select ENABLED or DISABLED.
Mode attention char.
The attention character for the system Enter a character. If the attention character you want to use is a control mode or the user mode character character, specify the ASCII equivalent.
System mode char.
The character for the mode attention character (above)
Enter a character. If the attention character you want to use is a control character, specify the ASCII. When the controller encounters the attention character and the system mode character, the controller sets channel 0 communication to system mode. The remote mode change option must be ENABLED.
Publication 1785-UM012D-EN-P - July 2005
Page 169
Communicating with Devices on a Serial Link
10-19
This Field
Specifies
Configure by Doing the Following
User mode char.
The character for the mode attention character (above)
Enter a valid attention character. If the attention character you want to use is a control character, specify the ASCII equivalent. When the controller encounters the attention character and the user mode character, the controller sets channel 0 communication to user mode. The remote mode change option must be ENABLED.
Serial Settings Baud rate
Communication rate for channel 0
Select 110, 300, 600, 1200, 2400, 4800, 9600, or 19.2k bps.
Configure all devices in the system for the same communication rate Parity
Parity setting for channel 0
Select NONE or EVEN.
Parity provides additional message packet error detection. Bits per character
Select the number of bits that make up Select 7 or 8. a transmitted character.
Error detect
Whether you want error detection set Select one of the following: to BCC or CRC BCC: the controller sends and accepts messages that end with a BCC byte for error checking. BCC is quicker and easier to implement in a computer driver. CRC: the controller sends and accepts messages with a 2-byte CRC for error checking. CRC is more complete checking Configure both stations to use the same type of error checking.
Stop bits
Match the number of stop bits to the device with which you are communicating
Select 1, 1.5, or 2.
Control line
Select the mode in which the driver operates.
Select a method appropriate for your system’s configuration: If you are not using a modem, choose NO HANDSHAKING. If you are using a full-duplex modem, choose FULL-DUPLEX.
Option Settings RTS send delay
The time delay between the time the RTS is asserted and the beginning of the message transmission
Enter a value between 0 and 255. Limits are defined in 20 ms intervals. For example to wait 40 ms, type 2. The recommended time elapse is 0, unless you are using a modem that automatically returns the CTS as soon as it receives the RTS. If this is the case, enter a delay time to make sure the modem is able to transmit before it attempts to send the message.
RTS off-delay
The time delay between the time the Enter a value between 0 and 255. Limits are defined in 20 ms intervals. end of the message transmission and For example to wait 40 ms, type 2. The recommended time elapse is 0, the RTS is de-asserted unless you are using a modem that automatically returns the CTS as soon as it receives the RTS. If this is the case, enter a delay time to make sure the modem is able to transmit before it attempts to send the message.
Publication 1785-UM012D-EN-P - July 2005
Page 170
10-20
Communicating with Devices on a Serial Link
This Field
Specifies
Configure by Doing the Following
Delete mode
Select how the controller responds to Select Ignore, CRT, or Printer. If you select Ignore, the controller ignores a delete character. the delete character. If you select CRT or Printer, the controller ignores the character it received immediately before the delete character. The controller then sends a signal to the CRT or printer to erase the deleted character. Select CRT or Printer only if you enable the echo mode.
XON/XOFF
Whether or not you want XON/XOFF enabled
As the controller receives characters, it constantly determines how many more it can receive without losing any. When XON/XOFF is enabled, the controller sends a “stop sending character,” XOFF. If the sending device has the XON/XOFF feature, it stops sending characters. When the controller has more room, it will send a “start sending” character (XON). Select ENABLED or DISABLED.
Echo
What the controller should do when it If you disable the echo mode, characters received by the controller are receives an ASCII delete character sent only to the echo counter and not to an output device, such as a CRT or printer. If you enable the echo mode, the controller sends any characters it receives through an ASCI read or read line instruction to a waiting output device. For example, if you want the controller to print a message to a LED marquee, enable the echo mode.
Termination 1 Termination 2
The termination characters you defined
Enter a maximum of two characters (hexadecimal). Use termination characters with the ASCII Read Line instruction or with the Test Buffer for Line (ABL) to indicate a line has been entered. The default character is the ASCII equivalent for [RETURN], 0x0D. You can also use the ASCII equivalent for LINE FEED (0x0A). To specify no character, enter \FF.
Append 1 Append 2
The append characters you defined
Enter a maximum of two characters (hexadecimal). Use append characters with the ASCII Write with Append (AWA) instruction to indicate the end of a line. Append characters are the last characters sent after a line of information. The default characters are the ASCII equivalent for [RETURN] (/0D) and LINE FEED (/0A). To specify no character, enter \FF.
Publication 1785-UM012D-EN-P - July 2005
Page 171
Communicating with Devices on a Serial Link
10-21
Configure Channel 0 for a Communication Mode Change You can configure channel 0 so that it switches from one communication mode to another upon receiving a control command. You define a mode attention character and either a system or user mode character. Character
Tells the Controller to
Default Character
Mode attention character expect a change communication mode command
System mode character switch the communication mode to system mode
S
User mode character switch the communication mode to the user mode
U
[Esc]
Every time the controller receives the mode attention character and either a system or user mode character, channel 0’s communication mode will be switched to the new mode. To configure channel 0 for a remote communication-mode change, follow the steps on the left: If You Want To
Select
Change the communication mode of channel 0 remotely
ENABLE
Not change the communication mode of channel 0 remotely
DISABLE
IMPORTANT
Make sure the remote mode change option is disabled if you do not want to change channel 0’s communication mode over a remote link. Having the mode disabled prevents an unexpected communication mode change.
The Mode Attention character tells the controller to expect a communication mode change. If you are using a control character, enter the ASCII equivalent in hexadecimal. With other characters, just enter the character. Do one of the following: Enter the character you want to use to tell the controller to switch communication modes for channel 0. If you are using a control character, use the ASCII equivalent in hexadecimal. With other characters, just enter the character.
Publication 1785-UM012D-EN-P - July 2005
Page 172
10-22
Communicating with Devices on a Serial Link
Monitoring Channel 0 Status
The channel 0 status screens display the information stored in the diagnostic file you specified when you configured channel 0.
Using the System Mode Status Display This section explains the status data displayed on system mode screens in your programming software: System Mode (DF1 Point-to Point) Status Screen
System Mode (DF1 Slave) Status Screen
Publication 1785-UM012D-EN-P - July 2005
Page 173
Communicating with Devices on a Serial Link
10-23
System Mode (DF1 Master) Status Screen
Descriptions of System Mode Status Screen Fields Status Field
Word Bit
Description
DCD recover
11
Displays the number of times the controller detects the DCD-handshaking line has gone low to high.
Messages sent
1
Displays the total number of DF1 messages sent by the controller (included message retry).
Messages received
2
Displays the number of messages the controller received with no error.
EOT received on first poll
8
Displays the number of times the master received an EOT in response to the first poll of a station.
Lost modem
12
Displays the number of times a modem was disconnected.
Messages retried
4
For slave and master mode, displays the number of messages resent.
Undelivered messages
3
Displays number of messages that were sent by controller but not received by the destination device.
Duplicate messages received
9
Displays the number of times the controller received a message packet identical to the previous message packet.
Bad packet/no ACK sent
7
Displays the number of incorrect data packets that the controller has received.
Last poll list scan last
5
The time it took to complete the previous scan of the normal station poll list.
Last priority poll list scan last
10
The time it took to complete the previous scan of the priority station poll list.
Max normal poll list scan
6
The maximum time taken to complete a scan of the normal station poll list.
Max priority poll list scan
13
The maximum time taken to complete a scan of the priority station poll list.
ENQs received
6
For point-to-point mode, displays the number of inquiries made by the destination device.
ENQs sent
4
For point-to-point mode, displays the number of inquiries made by the controller.
Received NAK
5
For Point-to-point and slave mode, displays the number of NAK messages received by the controller.
Lack of memory/sent NAK Lack of memory/no ACK sent
8
For point-to-point and slave mode, displays the number of times the controller could not receive a message because it did not have enough memory.
Polling received
6
For slave mode, displays number of times a DF1 master device has polled controller for a message.
Publication 1785-UM012D-EN-P - July 2005
Page 174
10-24
Communicating with Devices on a Serial Link
Status Field
Word Bit
Description
DTR
0: 4
Displays the status of the DTR handshaking line (asserted by the controller)
DSR
0: 2
Displays the status of the DSR handshaking line (received by the controller)
RTS
0: 1
Displays the status of the RTS handshaking line (asserted by the controller)
CTS
0: 0
Displays the status of the CTS handshaking line (received by the controller)
DCD
0: 3
Displays the status of the DCD handshaking line (received by the controller)
Modem Lines
Using the User Mode (ASCII) Status Display This section describes the user-mode status data displayed on the user mode (ASCII) status screen in your programming software. User Mode Status Screen
Descriptions of User Mode Status Screen Fields Status Field
Word Bit
Description
DCD recover
11
Displays the number of times the controller detects the DCD-handshaking line has gone low to high.
Character received with error
10
Displays the number of characters the controller received with parity or with errors and discarded
Lost modem
12
Displays the number of times a modem was disconnected.
DTR
0: 4
Displays the status of the DTR handshaking line (asserted by the controller)
DSR
0: 2
Displays the status of the DSR handshaking line (received by the controller)
RTS
0: 1
Displays the status of the RTS handshaking line (asserted by the controller)
CTS
0: 0
Displays the status of the CTS handshaking line (received by the controller)
DCD
0: 3
Displays the status of the DCD handshaking line (received by the controller)
Modem Lines
Publication 1785-UM012D-EN-P - July 2005