Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Chapter 11 - Communicating with Devices on an Ethernet Network, pages 205 to 212
Pages 205 to 212 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 205
Communicating with Devices on an Ethernet Network
Scenario
11-31
Multihop Path originating PLC-5 with Ethernet interface to ControlLogix controller in chassis 1 originating PLC-5 with Ethernet interface to PLC-5 (station 76) on DH+ link (link 12) Note: Both 1756-DHRIO modules need routing tables that show a path to both link 12 and the link ID that is configured for the Ethernet port of the originating PLC-5 controller.
originating PLC-5 with Ethernet interface to ControlNet PLC-5 (node 1)
Publication 1785-UM012D-EN-P - July 2005
Page 206
11-32
Communicating with Devices on an Ethernet Network
Comparing Multihop and Non-Multihop Messages Over Ethernet When an outbound connection's inactivity timer has expired and a MSG is pending on that connection, the MSG receives an error. On a multihop connection, the error is 0x18 (Broken Connection). On a non-multihop connection, the error is 0x16 (Connection Timeout). For non-multihop connections, the Connection Inactivity Timeout is user configurable. For multihop connections, it is not configurable. Instead, it uses a default timeout value of 17 seconds.
Communicating with ControlLogix Devices
To communicate through a ControlLogix 1756-ENET module, you configure the multihop feature of a MSG instruction from the Ethernet PLC-5 controller (or PLC-5 controller with 1785-ENET sidecar module) to the target device. You need RSLogix 5 programming software. For more information, see the MSG instruction in the PLC-5 Programmable Controller Instruction Set Reference Manual, publication 1785-6.1. If you want to go through the ControlLogix 1756-ENET module and out the 1756-DHRIO module to the target device, you: • use Gateway configuration software to configure the 1756-DHRIO module routing table in the ControlLogix system. • specify a Link ID number on channel properties for channel 2/3A of the Ethernet PLC-5 controller (or PLC-5 controller with a 1785-ENET sidecar module). For more information about configuring a PLC-5 channel or specifying the path of the MSG instruction, see the documentation for your programming software.
TCP/IP
Publication 1785-UM012D-EN-P - July 2005
TCP/IP communications have been updated for enhanced UDP message support and super-netting.
Page 207
Communicating with Devices on an Ethernet Network
Interpreting Error Codes
11-33
When the controller detects an error during the transfer of message data, the controller sets the .ER bit and enters an error code: Code - Hexadecimal Description (word 1 of the control block) (displayed on the data monitor screen) 0010
No IP address configured for the network
0011
Already at maximum number of connections
0012
Invalid internet address or host name
0013
No such host
0014
Cannot communicate with the name server
0015
Connection not completed before user-specified timeout
0016
Connection timed out by the network
0017
Connection refused by destination host
0018
Connection was broken
0019
Reply not received before user-specified timeout
001A
No network buffer space available
0037
Message timed out in local controller
0083
Controller is disconnected
0089
Controller’s message buffer is full
0092
No response (regardless of station type)
00D3
You formatted the control block incorrectly
00D5
Incorrect address for the local data table
1000
Illegal command from local controller
2000
Communication module not working
4000
Controller connected but faulted (hardware)
5000
You used the wrong station number
6000
Requested function is not available
7000
Controller is in program mode
8000
Controller’s compatibility file does not exist
Publication 1785-UM012D-EN-P - July 2005
Page 208
11-34
Communicating with Devices on an Ethernet Network
Code - Hexadecimal Description (word 1 of the control block) (displayed on the data monitor screen)
Interpreting Ethernet Status Data
Publication 1785-UM012D-EN-P - July 2005
9000
Remote node cannot buffer command
B000
Controller is downloading so it is inaccessible
F001
Controller incorrectly converted the address
F002
Incomplete address
F003
Incorrect address
F006
Addressed file does not exist in target controller
F007
Destination file is too small for number of words requested
F00A
Target controller cannot put requested information in packets
F00B
Privilege error, access denied
F00C
Requested function is not available
F00D
Request is redundant
F011
Data type requested does not match data available
F012
Incorrect command parameters
F01A
File owner active – the file is being used
F01B
Program owner active – someone is downloading, online editing, or set the program owner with APS in the WHO Active screen
Monitor the status of Ethernet PLC-5 controllers by accessing the Ethernet channel 2 status screen of your programming software. The diagnostic counter data displayed is stored in the diagnostic file defined on the Ethernet channel 2 configuration screen.
Page 209
Communicating with Devices on an Ethernet Network
11-35
Monitoring general Ethernet status
Status Field
Bytes
Displays the Number of
In Octets
28-31
Octets received on the channel
Out Octets
32-35
Octets sent on the channel
In Packets
36-39
Packets received on the channel, including broadcast packets
Out Packets
40-43
Packets sent on the channel, including broadcast packets
Excessive collisions
56-59
Frames for which a transmission fails due to excessive collisions
Excessive deferrals
60-63
Frames for which transmission is deferred for an excessive period of time
Alignment errors
44-47
Frames received on the channel that are not an integral number of octets in length
FCS errors
48-51
Frames received on the channel that do not pass the FCS check
MAC receive errors
64-67
Frames for which reception on an interface fails due to internal MAC sublayer receive error
MAC transmit errors
68-71
Frames for which reception on an interface fails due to internal MAC sublayer transmit error
Single collisions
72-75
Successfully transmitted frames for which transmission was delayed because of collision.
Multiple collisions
76-79
Successfully transmitted frames for which transmission was delayed more than once because of collision.
Deferred transmission
80-83
Frames for which the first transmission attempt is delayed because the medium is busy
Late collisions
84-87
Times that a collision is detected later than 512 bit-times into the transmission of a packet
Multiple collisions
88-89
Network storms encountered
Ethernet Address
90-95
Ethernet Hardware Address
IP Address
96-99
Assigned Internet Protocol Address
Carrier sense errors
52-55
Times that the carrier sense condition was lost or never asserted while trying to transmit a frame
Publication 1785-UM012D-EN-P - July 2005
Page 210
11-36
Communicating with Devices on an Ethernet Network
Monitoring Ethernet commands
Status Field
Bytes
Displays the Number of
Sent
0-3
Commands sent by the channel
Received
4-7
Commands received by the channel
Monitoring Ethernet replies
Status Field
Bytes
Displays the Number of
Sent
8-11
Replies sent by the channel
Received
12-15
Replies received by the channel
Sent with error
16-19
Replies containing errors sent by the channel
Received with error
20-23
Replies containing errors received by the channel
Timed out
24-27
Replies not received within the specified timeout period
Publication 1785-UM012D-EN-P - July 2005
Page 211
Communicating with Devices on an Ethernet Network
Ethernet PLC-5 Performance Considerations
11-37
Actual performance of an Ethernet PLC-5 controller varies according to: • size of Ethernet messages • frequency of Ethernet messages • network loading • the implementation of and performance of your controller application program The following charts show performance of the Ethernet PLC-5 controller, depending on packet size.
Performance: Host to Ethernet PLC-5 Controller
Personal Computer
Publication 1785-UM012D-EN-P - July 2005
Page 212
11-38
Communicating with Devices on an Ethernet Network
Performance: Ethernet PLC-5 Controller to Ethernet PLC-5 Controller
PLC-5 Controller Typed Write - Packet Size
Publication 1785-UM012D-EN-P - July 2005