Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Appendix A - System Specifications

Pages 269 to 274 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual

The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B

Page 269

Appendix

A

System Specifications Controller Specifications For all controller-related specifications, please refer to the related installation instructions: • Enhanced PLC-5 Controllers Installation Instructions, publication 1785-IN062 • Ethernet PLC-5 Programmable Controllers Installation Instructions, publication 1785-IN063 To get this documentation, you can either: • view or download an electronic version from the internet at www.rockwellautomation.com/literature • contact your local distributor or Rockwell Automation representative to place an order

1

Publication 1785-UM012D-EN-P - July 2005

Page 270

A-2

System Specifications

Memory and Channel Specifications Controller/ Cat. No.

Maximum User Memory Words

Total I/O Maximum (Any Mix)

Types of Communication Ports

Maximum Maximum Number of I/O Number of Chassis I/O Racks (Rack Addresses)

PLC-5/11 (1785-L11B)

8K

512 (any mix) or

1 DH+/Remote I/O (Adapter or Scanner)

4 (0-3)

384 in + 384 out (complementary)

PLC-5/20 (1785-L20B)

16K

PLC-5/26 (1785-L26B)

Total

Ext Local

Remote

5

0

4 (must be rack 3)

4 (0-3)

13

0

12

4 (0-3)

13

0

12

8 (0-7)

29

0

28

16 (0-17)

61

0

60

16 (0-17)

61

0

60

16 (0-17)

61

16

60

1 serial port, configurable for RS-232 and 423 and RS-422A compatible

512 (any mix) or

1 DH+ (Fixed)

512 in + 512 out (complementary)

1 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible

PLC-5/20E (1785-L20E)

16K

512 (any mix) or

1 DH+ (Fixed)

512 in + 512 out (complementary)

1 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 channel Ethernet only

PLC-5/30 (1785-L30B)

32 K

1024 (any mix) or 1024 in and 1024 out (complementary)

PLC-5/40 (1785-L40B)

48 K(1)

2048 in + 2048 out (complementary)

PLC-5/46 (1785-L46B) PLC-5/40E (1785-L40E)

2048 (any mix) or

48 K1

2048 (any mix) or 2048 in + 2048 out (complementary)

2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 4 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 channel Ethernet only 1 serial port, configurable for RS-232 and 423 and RS-422A compatible

PLC-5/40L (1785-L40L)

48 K1

2048 (any mix) or 2048 in + 2048 out (complementary)

2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 Extended-Local I/O

Publication 1785-UM012D-EN-P - July 2005

Page 271

System Specifications

Controller/ Cat. No.

Maximum User Memory Words

Total I/O Maximum (Any Mix)

Types of Communication Ports

Maximum Maximum Number of I/O Number of Chassis I/O Racks (Rack Addresses)

PLC-5/60 (1785-L60B)

64 K(2)

3072 (any mix) or

4 DH+/Remote I/O (Adapter or Scanner)

24 (0-27)

93

0

92

24 (0-27)

81

16

64

24 (0-27)

93

0

92

24 (0-27)

65

0

64

3072 in + 3072 out (complementary)

PLC-5/60L (1785-L60L)

3072 (any mix) or

64 K2

3072 in + 3072 out (complementary)

A-3

1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 Extended Local I/O

PLC-5/80 (1785-L80B)

100 K

(3)

3072 in + 3072 out (complementary)

PLC-5/86 (1785-L86B) PLC-5/80E (1785-L80E)

3072 (any mix) or

100 K3

3072 (any mix) or 3072 in + 3072 out (complementary)

4 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 channel Ethernet only

1

The PLC-5/40, -5/40E, -5/40L controllers have a limit of 32K words per data table file.

2

The PLC-5/60 and -5/60L controllers have a limit of 56K words per program file and 32K words per data table file.

3 The PLC-5/80, -5/80E controllers have 64K words of total data table space with a limit of 56K words per program file and 32K words per data table file.

(1) (2) (3)

Publication 1785-UM012D-EN-P - July 2005

Page 272

A-4

System Specifications

Battery Specifications Enhanced and Ethernet PLC-5 programmable controllers use 1770-XYC batteries that contain 0.65 grams of lithium. Battery Life Estimates In these Controllers

At this Temperature

Power Off 100%

Power Off 50%

Battery Duration Aafter the LED Lights1

PLC-5/11B, -5/20B and -5/20E

60°C

256 days

1.4 years

11.5 days

25°C

2 years

4 years

47 days

60°C

84 days

150 days

5 days

25°C

1 year

1.2 years

30 days

PLC-5/30B -5/40B, -5/40E, -5/40L, -5/60B, -5/60L, -5/80B and -5/80E 1

The battery indicator (BATT) warns you when the battery is low. These durations are based on the battery supplying the only power to the controller (power to the chassis is off) once the LED first lights.

Memory Backup Devices

You can add an EEPROM to the PLC-5 controller to provide backup memory for your program in case the controller loses power. These memory cards are available: Catalog Number

For This Product

Memory Size

1785-ME16

Enhanced PLC-5 controllers

16K words

1785-ME32

Enhanced PLC-5 controllers

32K words

1785-ME64

Enhanced PLC-5 controllers

64K words

1785-ME100

Enhanced PLC-5 controllers

100K words

Use your programming software to save a program currently in the controller to the EEPROM card. If you restore a program from the EEPROM to controller memory and controller memory is bad, the restore changes the date and time in the controller status file to the date and time the EEPROM was saved. If you restore a program from the EEPROM to controller memory and controller memory is valid, the status file retains its current date and time.

EEPROM Compatibility EEPROM compatibility is related to:

Publication 1785-UM012D-EN-P - July 2005

Page 273

System Specifications

Area

Description

ControlNet PLC-5 controllers

EEPROM memory cannot be loaded to a non-ControlNet PLC-5 controller if the EEPROM was saved on a ControlNet PLC-5 controller.

A-5

EEPROM memory cannot be loaded to a ControlNet PLC-5 controller if the EEPROM was burned on a non-ControlNet PLC-5 controller. PLC-5 catalog numbers

EEPROM memory can be loaded to a PLC-5 controller if its I/O memory size is greater than or equal to the I/O memory of the PLC-5 controller from which the EEPROM was saved. The I/O memory sizes are: PLC-5/11, -5/204 racks PLC-5/308 racks PLC-5/4016 racks PLC-5/60, -5/8024 racks EEPROM memory can be loaded to a PLC-5 controller if its user memory is greater than or equal to the user memory used on the PLC-5 controller from which the EEPROM was saved. The available user memory is: PLC-5/118,192 words PLC-5/2016,384 words PLC-5/3032,768 words PLC-5/4065,536 words PLC-5/80102,400 words

Firmware release compatibility

EEPROM memory saved on a series D, revision B PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release. EEPROM memory saved on a series E, revision A PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release. EEPROM memory saved on a series E, revision B PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release.

Publication 1785-UM012D-EN-P - July 2005

Page 274

A-6

System Specifications

Notes

Publication 1785-UM012D-EN-P - July 2005