Enhanced and Ethernet PLC-5 Programmable Controllers User Manual: Appendix A - System Specifications
Pages 269 to 274 of 388, from Enhanced and Ethernet PLC-5 Programmable Controllers User Manual
The original document is the PDF (5.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-L20B and Allen-Bradley 1785-L40B
Page 269
Appendix
A
System Specifications Controller Specifications For all controller-related specifications, please refer to the related installation instructions: • Enhanced PLC-5 Controllers Installation Instructions, publication 1785-IN062 • Ethernet PLC-5 Programmable Controllers Installation Instructions, publication 1785-IN063 To get this documentation, you can either: • view or download an electronic version from the internet at www.rockwellautomation.com/literature • contact your local distributor or Rockwell Automation representative to place an order
1
Publication 1785-UM012D-EN-P - July 2005
Page 270
A-2
System Specifications
Memory and Channel Specifications Controller/ Cat. No.
Maximum User Memory Words
Total I/O Maximum (Any Mix)
Types of Communication Ports
Maximum Maximum Number of I/O Number of Chassis I/O Racks (Rack Addresses)
PLC-5/11 (1785-L11B)
8K
512 (any mix) or
1 DH+/Remote I/O (Adapter or Scanner)
4 (0-3)
384 in + 384 out (complementary)
PLC-5/20 (1785-L20B)
16K
PLC-5/26 (1785-L26B)
Total
Ext Local
Remote
5
0
4 (must be rack 3)
4 (0-3)
13
0
12
4 (0-3)
13
0
12
8 (0-7)
29
0
28
16 (0-17)
61
0
60
16 (0-17)
61
0
60
16 (0-17)
61
16
60
1 serial port, configurable for RS-232 and 423 and RS-422A compatible
512 (any mix) or
1 DH+ (Fixed)
512 in + 512 out (complementary)
1 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible
PLC-5/20E (1785-L20E)
16K
512 (any mix) or
1 DH+ (Fixed)
512 in + 512 out (complementary)
1 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 channel Ethernet only
PLC-5/30 (1785-L30B)
32 K
1024 (any mix) or 1024 in and 1024 out (complementary)
PLC-5/40 (1785-L40B)
48 K(1)
2048 in + 2048 out (complementary)
PLC-5/46 (1785-L46B) PLC-5/40E (1785-L40E)
2048 (any mix) or
48 K1
2048 (any mix) or 2048 in + 2048 out (complementary)
2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 4 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 channel Ethernet only 1 serial port, configurable for RS-232 and 423 and RS-422A compatible
PLC-5/40L (1785-L40L)
48 K1
2048 (any mix) or 2048 in + 2048 out (complementary)
2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 Extended-Local I/O
Publication 1785-UM012D-EN-P - July 2005
Page 271
System Specifications
Controller/ Cat. No.
Maximum User Memory Words
Total I/O Maximum (Any Mix)
Types of Communication Ports
Maximum Maximum Number of I/O Number of Chassis I/O Racks (Rack Addresses)
PLC-5/60 (1785-L60B)
64 K(2)
3072 (any mix) or
4 DH+/Remote I/O (Adapter or Scanner)
24 (0-27)
93
0
92
24 (0-27)
81
16
64
24 (0-27)
93
0
92
24 (0-27)
65
0
64
3072 in + 3072 out (complementary)
PLC-5/60L (1785-L60L)
3072 (any mix) or
64 K2
3072 in + 3072 out (complementary)
A-3
1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 Extended Local I/O
PLC-5/80 (1785-L80B)
100 K
(3)
3072 in + 3072 out (complementary)
PLC-5/86 (1785-L86B) PLC-5/80E (1785-L80E)
3072 (any mix) or
100 K3
3072 (any mix) or 3072 in + 3072 out (complementary)
4 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 2 DH+/Remote I/O (Adapter or Scanner) 1 serial port, configurable for RS-232 and 423 and RS-422A compatible 1 channel Ethernet only
1
The PLC-5/40, -5/40E, -5/40L controllers have a limit of 32K words per data table file.
2
The PLC-5/60 and -5/60L controllers have a limit of 56K words per program file and 32K words per data table file.
3 The PLC-5/80, -5/80E controllers have 64K words of total data table space with a limit of 56K words per program file and 32K words per data table file.
(1) (2) (3)
Publication 1785-UM012D-EN-P - July 2005
Page 272
A-4
System Specifications
Battery Specifications Enhanced and Ethernet PLC-5 programmable controllers use 1770-XYC batteries that contain 0.65 grams of lithium. Battery Life Estimates In these Controllers
At this Temperature
Power Off 100%
Power Off 50%
Battery Duration Aafter the LED Lights1
PLC-5/11B, -5/20B and -5/20E
60°C
256 days
1.4 years
11.5 days
25°C
2 years
4 years
47 days
60°C
84 days
150 days
5 days
25°C
1 year
1.2 years
30 days
PLC-5/30B -5/40B, -5/40E, -5/40L, -5/60B, -5/60L, -5/80B and -5/80E 1
The battery indicator (BATT) warns you when the battery is low. These durations are based on the battery supplying the only power to the controller (power to the chassis is off) once the LED first lights.
Memory Backup Devices
You can add an EEPROM to the PLC-5 controller to provide backup memory for your program in case the controller loses power. These memory cards are available: Catalog Number
For This Product
Memory Size
1785-ME16
Enhanced PLC-5 controllers
16K words
1785-ME32
Enhanced PLC-5 controllers
32K words
1785-ME64
Enhanced PLC-5 controllers
64K words
1785-ME100
Enhanced PLC-5 controllers
100K words
Use your programming software to save a program currently in the controller to the EEPROM card. If you restore a program from the EEPROM to controller memory and controller memory is bad, the restore changes the date and time in the controller status file to the date and time the EEPROM was saved. If you restore a program from the EEPROM to controller memory and controller memory is valid, the status file retains its current date and time.
EEPROM Compatibility EEPROM compatibility is related to:
Publication 1785-UM012D-EN-P - July 2005
Page 273
System Specifications
Area
Description
ControlNet PLC-5 controllers
EEPROM memory cannot be loaded to a non-ControlNet PLC-5 controller if the EEPROM was saved on a ControlNet PLC-5 controller.
A-5
EEPROM memory cannot be loaded to a ControlNet PLC-5 controller if the EEPROM was burned on a non-ControlNet PLC-5 controller. PLC-5 catalog numbers
EEPROM memory can be loaded to a PLC-5 controller if its I/O memory size is greater than or equal to the I/O memory of the PLC-5 controller from which the EEPROM was saved. The I/O memory sizes are: PLC-5/11, -5/204 racks PLC-5/308 racks PLC-5/4016 racks PLC-5/60, -5/8024 racks EEPROM memory can be loaded to a PLC-5 controller if its user memory is greater than or equal to the user memory used on the PLC-5 controller from which the EEPROM was saved. The available user memory is: PLC-5/118,192 words PLC-5/2016,384 words PLC-5/3032,768 words PLC-5/4065,536 words PLC-5/80102,400 words
Firmware release compatibility
EEPROM memory saved on a series D, revision B PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release. EEPROM memory saved on a series E, revision A PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release. EEPROM memory saved on a series E, revision B PLC-5 controller cannot be loaded on a PLC-5 controller with an earlier firmware release.
Publication 1785-UM012D-EN-P - July 2005
Page 274
A-6
System Specifications
Notes
Publication 1785-UM012D-EN-P - July 2005