Page 301

Appendix

D

Instruction Set Quick Reference

Using This Chapter If You Want to Read About Relay instructions

D-2

Timer instructions

D-3

Counter instructions

D-4

Compare instructions

D-5

Compute instructions

D-7

Logical instructions

D-14

Conversion instructions

D-15

Bit modify and move instructions

D-16

File instructions

D-17

Diagnostic instructions

D-19

Shift register instructions

D-20

Sequencer instructions

D-21

Program control instructions

D-22

Process control and message instructions

D-25

Block Transfer instructions

D-25

ASCII instructions

D-27

Timing and memory requirements for bit and word instructions

D-30

Timing and memory requirements for file program control, and ASCII instructions

D-38

IMPORTANT

1

Go to Page

For a more detailed description of each of these instructions, see the PLC-5 Programming Software Instruction Set Reference, publication 1785-6.1.

Publication 1785-UM012D-EN-P - July 2005

Page 302

D-2

Instruction Set Quick Reference

Relay Instructions Instruction

Description Examine On XIC

Examine data table bit I:012/07, which corresponds to terminal 7 of an input module in I/O rack 1, I/O group 2. If this data table bit is set (1), the instruction is true.

Examine Off XIO

Examine data table bit I:012/07, which corresponds to terminal 7 of an input module in I/O rack 1, I/O group 2. If this data table bit is reset (0), the instruction is true.

O:013 ( ) 01

Output Energize OTE

If the input conditions preceding this output instruction on the same rung go true, set (1) bit O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3.

O:013

Output Latch OTL

If the input conditions preceding this output instruction on the same rung go true, set (1) bit O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3. This data table bit remains set even if the rung condition goes false.

O:013 (U ) 01

Output Unlatch OTU

If the input conditions preceding this output instruction on the same rung go true, reset (0) bit O:013/01, which corresponds to terminal 1 of an output module in I/O rack 1, I/O group 3. This is necessary to reset a bit that has been latched on.

01 ( IIN )

Immediate Input IIN

This instruction updates a word of input-image bits before the next normal input-image update. Address this instruction by rack and group (RRG). For a local chassis, program scan is interrupted while the inputs of the addressed I/O group are scanned; for a remote chassis, program scan is interrupted only to update the input image with the latest states as found in the remote I/O buffer.

01 ( IOT )

Immediate Output IOT

This instruction updates a word of output-image bits before the next normal output-image update. Address this instruction by rack and group (RRG). For a local chassis, program scan is interrupted while the outputs of the addressed I/O group are updated; for a remote chassis, program scan is interrupted only to update the remote I/O buffer with the latest states as found in the output image.

I:012 07 I:012 07

( L) 01

Publication 1785-UM012D-EN-P - July 2005

Page 303

Instruction Set Quick Reference

D-3

Timer Instructions Instruction TON TIMER ON DELAY Timer T4:1 1.0 Time Base Preset 15 Accum 0

Description Timer On Delay TON Status Bits: EN - Enable TT - Timer Timing DN - Done

If the input conditions go true, timer T4:1 starts incrementing in 1-second intervals. When the accumulated value is greater than or equal to the preset value (15), the timer stops and sets the timer done bit. EN

TT

DN

ACC

TON

15

14

13

Value

Status

False

0

0

0

0

Reset

True

1

1

0 increase

Timing

True

1

0

1

>= preset

Done

Rung Condition

See page F-8 for a description of prescan operation for this instruction. TOF TIMER OFF DELAY Timer T4:1 .01 Time Base Preset 180 Accum 0

Timer Off Delay TOF Status Bits: EN - Enable TT - Timer Timing DN - Done

If the input conditions are false, timer T4:1 starts incrementing in 10 1-ms intervals as long as the rung remains false. When the accumulated value is greater than or equal to the preset value (180), the timer stops and resets the timer EN

TT

DN

ACC

TOF

15

14

13

Value

Status

True

1

0

1

0

Reset

False

0

1

1 increase

Timing

False

0

0

0

>= preset

Done

Rung Condition

See page F-8 for a description of prescan operation for this instruction.

Publication 1785-UM012D-EN-P - July 2005

Page 304

D-4

Instruction Set Quick Reference

Instruction

Description

RTO RETENTIVE TIMER ON Timer T4:10 1.0 Time Base Preset 10 Accum 0

Retentive Timer On RTO

Status Bits: EN - Enable TT - Timer Timing DN - Done

Timer Reset RES

T4:1 ( RES )

If the input conditions go true, timer T4:10 starts incrementing i 1-second intervals as long as the rung remains true. When the rung goes false, the timer stops. If the rung goes true again, th timer continues. When the accumulated value is greater than o equal to the preset (10), the timer stops and sets the timer don bit. Rung Condition

EN 15

TT 14

DN 13

ACC Value

RTO Status

False

0

0

0

0

Disabled

True

1

1

0 increase

Timing

False

0

0

0 maintains

Disabled

True

1

0

1

>= preset

Done

If the input conditions go true, timer T4:1 is reset. This instruction resets timers and counters, as well as control blocks. This is necessary to reset the RTO accumulated value.

Counter Instructions Instruction

Description Count Up CTU

CTU COUNT UP Counter Preset Accum

C5:1 10 0

Status Bits: CU-Count Up CD-Count Down DN-Count Up done OV-Overflow UN-Underflow

If the input conditions go true, counter C5:1 starts counting, incrementing by 1 every time the rung goes from false-to-true. When the accumulated value is greater than or equal to the preset value (10), the counter sets the counter Rung Condition

CU 15

DN 13

OV 12

ACC Value

CTU Status

False

0

0

0

0

Disabled

Toggle True

1

0

0 incr by 1

Counting

True

1

1

0

>= preset

Done

True

1

1

1

>32767

Overflow

See page F-8 for a description of prescan operation for this instruction.

Publication 1785-UM012D-EN-P - July 2005

Page 305

Instruction Set Quick Reference

Instruction

Description

CTD COUNT DOWN Counter Preset Accum

D-5

Count Down CTD

If the input conditions go true, counter C5:1 starts counting, decrementing by 1 every time the rung goes from false-to-true. When the accumulated value is less than the preset value (10), the counter resets the counter done bit.

Status Bits: CU-Count Up CD-Count Down DN-Count Down done OV-Overflow UN-Underflow

Rung Condition

CD 14

DN 13

UN 11

ACC Value

CTD Status

False

0

0

0

0

Disabled

C5:1 10 35

False

0

1

0

>= preset

Preload

Toggle True

1

1

0 dec by 1

Counting

True

1

0

0

< preset

Done

True

1

0

1

< -32768

Underflow

See page F-8 for a description of prescan operation for this instruction.

Compare Instructions Instruction

Description

LIM LIMIT TEST (CIRC) Low limit N7:10 3 Test N7:15 4 High limit N7:20 22

Mask Compare Equal MEQ

MEQ MASKED EQUAL Source Mask Compare

Limit Test LIM

D9:5 0000 D9:6 0000 D9:10 0000

If the Test value (N7:15) is >= the Low Limit (N7:10) and <= the High Limit (N7:20), this instruction is true. Low Limit

Test

High Limit

LIM

0

0

10

T

-5

5

10

T

5

11

10

F

10

0

0

T

10

5

-5

F

10

11

5

T

The controller takes the value in the Source (D9:5) and passes that value through the Mask (D9:6). Then the controller compare the result to the Compare value (D9:10). If the result and this comparison values are equal, the instruction is true. Source

Mask

Compare

MEQ

0008

0008

0009

T

0008

0001

0001

F

0087

000F

0007

T

0087

00F0

0007

F

Publication 1785-UM012D-EN-P - July 2005

Page 306

D-6

Instruction Set Quick Reference

Instruction

Description Compare CMP

CMP COMPARE Expression N7:5 = N7:10 xxx xxxxxxxxxxxxx Source A Source B

Publication 1785-UM012D-EN-P - July 2005

If the expression is true, this input instruction is true. The CMP instruction can perform these operations: equal (=), less than (<), less than or equal (<=), greater than (>), greater than or equal (>=), not equal (<>), and complex expressions (up to 80 characters). Source A

Source B

EQU

GEQ

GRT

LEQ

LES

NEQ

10

10

T

T

F

T

F

F

5

6

F

F

F

T

T

T

21

20

F

T

T

F

F

T

-30

-31

F

T

T

F

F

T

-15

-14

F

F

F

T

T

T

N7:5 3 N7:10 1

Equal to EQU

If the value in Source A (N7:5) is = to the value in Source B (N7:10), this instruction is true.

Greater than or Equal GEQ

If the value in Source A (N7:5) is > or = the value in Source B (N7:10), this instruction is true.

Greater than GRT

If the value in Source A (N7:5) is > the value in Source B (N7:10), this instruction is true.

Less than or Equal LEQ

If the value in Source A (N7:5) is < or = the value in Source B (N7:10), this instruction is true.

Less than LES

If the value in Source A (N7:5) is < the value in Source B (N7:10), this instruction is true.

Not Equal NEQ

If the value in Source A (N7:5) is not equal to the value in Source B (N7:10), this instruction is true.

Page 307

Instruction Set Quick Reference

D-7

Compute Instructions Instruction

Description Compute CPT

CPT COMPUTE Dest

N7:3 3

The CPT instruction can perform these operations: add (+), subtract (-), multiply (*), divide (|), convert from BCD (FRD), convert to BCD (TOD), square root (SQR), logical and (AND), logical or (OR), logical not (NOT), exclusive or (XOR), negate (-) clear (0), and move, X to the power of Y (**), radians (RAD), degrees (DEG), log (LOG), natural log (LN), sine (SIN), cosine (COS), tangent (TAN), inverse sine (ASN), inverse cosine (ACS) inverse tangent (ATN), and complex expressions (up to 80 characters)

Expression N7:4 - (N7:6 * N7:10)

Arc cosine ACS

ACS ARCCOSINE Source Dest

If the input conditions go true, evaluate the Expression N7:4 (N7:6 * N7:10) and store the result in the Destination (N7:3).

F8:19 0.7853982 F8:20 0.6674572

If input conditions go true, take the arc cosine of the value in F8:19 and store the result in F8:20. Status Bit

Description

C always resets

V otherwise resets

Z S

Addition ADD

ADD ADD Source A Source B Dest

N7:3 3 N7:4 1 N7:12 4 sets if overflow is generated; sets if the result is zero;

otherwise resets always resets

When the input conditions are true, add the value in Source A (N7:3) to the value in Source B (N7:4) and store the result in the Destination (N7:12). Status Bit C

Description sets if carry is generated;

otherwise resets sets if overflow is generated;

V otherwise resets

Z otherwise resets

S otherwise resets sets if the result is zero;

sets if the result is negative;

Publication 1785-UM012D-EN-P - July 2005

Page 308

D-8

Instruction Set Quick Reference

Instruction

Description Arc sine ASN

ASN ARCSINE Source Dest

F8:17 0.7853982 F8:18 0.9033391

When input conditions go true, take the arc sine of the value in F8:17 and store the result in F8:18. Status Bit

Description

C always resets

V sets if overflow is generated;

otherwise resets Z sets if the result is zero;

otherwise resets always resets

S ATN ARCTANGENT Source F8:21 0.7853982 Dest

Arc tangent ATN

F8:22 0.6657737

When input conditions go true, take the arc tangent of the value in F8:21 and store the result in F8:22. Status Bit

Description

C always resets

V sets if overflow is generated;

otherwise resets Z sets if the result is zero;

otherwise resets S sets if the result is negative;

otherwise resets Average AVE

AVE AVERAGE FILE File Dest Control Length Position

#N7:1 N7:0 R6:0 4 0

Status Bits: EN - Enable DN - Done bit ER - Error Bit

When the input conditions go from false-to-true, take the average of the file #N7:1 and store the result in N7:0. Status Bit

Description

C always resets

V sets if overflow is generated;

otherwise resets Z sets if the result is zero;

otherwise resets S

Publication 1785-UM012D-EN-P - July 2005 sets if the result is negative;

otherwise resets

Page 309

Instruction Set Quick Reference

Instruction

Description Clear CLR

CLR CLR Dest

D9:34 0000

Cosine COS

COS COSINE Source Dest

D-9

F8:13 0.7853982 F8:14 0.7071068

When the input conditions are true, clear decimal file 9, word 3 (set to zero). Status Bit

Description

C always reset

V always reset

Z always set

S always reset

When input conditions go true, take the cosine of the value in F8:13 and store the result in F8:14. Status Bit

Description

C always resets

V sets if overflow is generated;

otherwise resets Z sets if the result is zero;

otherwise resets S sets if the result is negative;

otherwise resets

Instruction

Description Division DIV

DIV DIVIDE Source A Source B Dest

N7:3 3 N7:4 1 N7:12 3

When the input conditions are true, divide the value in Source A (N7:3) by the value in Source B (N7:4) and store the result in the Destination (N7:12). Status Bit

Description

C always resets

V sets if division by zero or overflow; otherwise resets

Z sets if the result is zero; otherwise resets; undefined if overflow is set

S sets if the result is negative; otherwise resets; undefined if overflow is set

Publication 1785-UM012D-EN-P - July 2005

Page 310

D-10

Instruction Set Quick Reference

Instruction

Description Natural log LN

LN NATURAL LOG Source Dest

N7:0 5

F8:20 1.609438

When input conditions go true, take the natural log of the va in N7:0 and store the result in F8:20. Status Bit

Description

C always resets sets if overflow is generated;

V otherwise resets sets if the result is zero;

Z otherwise resets sets if the result is negative;

S

LOG LOG BASE 10 Source Dest otherwise resets

When input conditions go true, take the log base 10 of the value in N7:2 and store the result in F8:3. N7:2 5

F8:3 0.6989700

Status Bit

Description

C always resets

V otherwise resets

Z

S

Multiply MUL

MUL MULTIPLY Source A Source B Dest

Publication 1785-UM012D-EN-P - July 2005

N7:3 3 N7:4 1 N7:12 3 sets if overflow is generated; sets if the result is zero;

otherwise resets sets if the result is negative;

otherwise resets

When the input conditions are true, multiply the value in Source A (N7:3) by the value in Source B (N7:4) store the result in the Destination (N7:12). Status Bit

Description

C always resets

V sets if overflow is generated; otherwise resets

Z sets if the result is zero; otherwise resets

S sets if the result is negative; otherwise resets