Page 121
Chapter 9 Calculating Program Timing
I/O placed in the same chassis as the processor is called “processorresident” local I/O. These inputs and outputs are not updated during the remote I/O scan - they are updated during the housekeeping portion of the program scan. During housekeeping, the processor reads and writes the I/O across the chassis backplane. Thus, the update of processor-resident local I/O is synchronous to the program scan. Figure 9.1 shows timing loops for discrete data transfer in a PLC-5 processor.
Immediate I/O x y
Remote I/O Buffer
Data Exchange
I/O Image Table
Read Inputs Write Outputs
Rack 1
Adapter
Data Exchange x y
Remote I/O Scan Timing Loop
Processor- Resident Rack
IOT (x) IIN (y)
Housekeeping
Rack 2
Adapter
Rack 3
Adapter
Figure 9.1 Remote I/O Scan and Program Scan Timing Loops
Logic Scan
Program Scan Timing Loop
During the housekeeping portion of the program scan, both the remote I/O buffer and the processor-resident rack are updated. Remember that the I/O scanner is constantly updating the remote I/O buffer asynchronously to the program scan.
9-4
Page 122
Chapter 9 Calculating Program Timing
I/O Scanning Discrete and Block Transfer
A Classic PLC-5 processor can transfer discrete data and block data to/from processor-resident local I/O, extended-local I/O chassis, and remote I/O chassis.
Transferring Discrete Data The remote I/O system is scanned in a separate and asynchronous scan to the program scan. The remote I/O scan takes output data from the remote I/O buffer to output modules and puts input data into the remote I/O buffer from input modules. The remote I/O scan time can take 3, 6, or 10 ms per one rack in a chassis on the remote I/O link, depending on baud rate. The PLC-5 processor then exchanges the input and output image table data with the remote I/O buffer during the I/O-update portion of housekeeping.
Immediate I/O The processor responds to immediate input (IIN) and immediate output (IOT) requests during the logic scan. The logic scan is suspended at the request for immediate input/output data. The logic scan resumes after obtaining the data and fulfilling the request. IIN and IOT data transfers directly to and from I/O modules in processorresident I/O and extended-local I/O chassis. With remote I/O, only the remote I/O buffer is updated.
Transferring Block Data The exchange of block-transfer data and the logic scan run independently and concurrently. The following paragraphs explain block transfer for extended-local I/O and then for processor-resident I/O and remote I/O.
9-5
Page 123
Chapter 9 Calculating Program Timing
Remote I/O and Processor-Resident I/O The processor performs block transfers asynchronously to the program scan. The processor also interrupts the program scan asynchronously to momentarily access BTW and BTR data files. The processor performs one remote block transfer per addressed rack and per remote I/O scan. Figure 9.2 shows timing loops for block transfer from a Classic PLC-5 processor. Figure 9.2 Transferring Block Data to Local and Remote I/O
Remote I/O Scan ·
One transfer per I/O scan
Rack 7
A
Adapter
Remote I/O
Q = Queue A = Active Buffer BT Requests Q BTR or BTW Data ¶
BT Requests Q
One transfer per I/O scan
BTR or BTW Data
A
¶
Rack 6
Adapter
BT Requests Q
One transfer per I/O scan
BTR or BTW Data ¶
A
BTRequests
Adapter
Rack 5
One transfer per I/O scan
Q
BTR or BTW Data
A
¶
Logic Scan
Processor Resident Rack 0 ¶
Interrupt from Fault Routine. The adapter used in the remote I/O scan is the · 1771-ASB adapter.
9-6
Q Multiple Block Transfers per I/O Scan
A
I/O Scan
BT Requests BTR or BTW Data ¶
Program Scan
Page 124
Chapter 9 Calculating Program Timing
Instruction Timing and Memory Requirements
The time it takes for a processor to scan an instruction depends on the type of instruction, the type of addressing, the type of data, whether the instruction has to convert data, and whether the instruction is true or false. This section provides timing and memory requirements estimates with these assumptions: direct addressing integer data, except where noted no data-type conversions addresses within the first 4096 words of the data table of a PLC-5/10, -5/12, -5/15, or -5/25 processor execution times shown in µs Memory requirements refer to the number of words the instruction uses. In some cases, an instruction may have a range of memory requirements. The range of words exists because the instruction can use different types of data. Important: The tables are divided into instruction times and memory requirements that are specific to PLC-5/10, -5/12, -5/15, and -5/25 processors.
9-7
Page 125
Chapter 9 Calculating Program Timing
Bit and Word Instructions for PLC-5/10, -5/12, -5/15, and -5/25 Processors Table 9.N shows timing and memory requirements for bit and word instructions for PLC-5/10, -5/12, -5/15, and -5/25 processors. Table 9.N Timing and Memory Requirements for Bit and Word Instructions for PLC-5/10, -5/12, -5/15, and -5/25 Processors Category
Relay
Code
Title
Execution Time (µs) Integer
Execution Time (µs) Floating Point
True
False
True
1.3
0.8
Words of Memory2
False 11
XIC examine if closed
XIO examine if open
OTL output latch
OTU output unlatch
OTE output energize
1.6
1.6 branch end
0.8
0.8
1
(0.01 base)
39
27
2-3
(1.0 base)
44
28
(0.01 base)
30
43
(1.0 base)
30
51
RTO retentive timer on (0.01 base) (1.0 base)
39 44
24 24
CTU count up
32
34
CTD count down
34
RES reset
30
Branch
1.6 next branch branch start Timer and Counter
TON TOF timer on timer off
14
1 For every bit address above the first 256 words of memory in the data table, add 0.8 µs to the execution time and 1 wordd of memory to the requirements. 2 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
9-8
Page 126
Chapter 9 Calculating Program Timing
Category
Arithmetic
Logic
Move
Comparison
Code
Title
Execution Time (µs) Integer
Execution Time (µs) Floating Point
True
False
True
False
36
14
92
14
4-7
14
3-5
14
2-3
Words of Memory2
ADD add
SUB subtract
MUL multiply
41
14
98
DIV divide
49
14
172
SQR square root
82
14
212
NEG negate
28
14
36
CLE clear
18
14
23
TOD convert to BCD
52
14
3-5
FRD convert from BCD
44
AND and
36
14
4-7
OR or
XOR exclusive or
NOT not
27
14
3-5
MOV move
26
14
MVM masked move
55
14
EQU equal
32
14
42
14
3-5
NEQ not equal
LES less than
LEQ less than or equal
GRT greater than
GEQ greater than or equal
LIM limit test
42
14
60
14
4-7
MEQ mask compare if equal
41
14
35
14 6-9
2 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
9-9
Page 127
Chapter 9 Calculating Program Timing
Category
Compute
Code
CPT
Execution Time (µs) Integer
Execution Time (µs) Floating Point
True
False
True
False
67
34
124
34
6-9 multiply
73
34
130 divide
80
34
204 square root
113
33
244
34
5-7 negate
59
33
68 clear
49
30
55
34
4-5 move
58
33
5-7 convert to BCD
84 convert from BCD
75
AND
68
34
6-9
NOT
59
34
5-7 equal
63
34
Title add
Words of Memory2 subtract
OR XOR
Compare
CMP
73 not equal less than less than or equal greater than greater than or equal 2 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
9-10
34
Page 128
Chapter 9 Calculating Program Timing
File Instructions The instruction timing for file instructions depends on the data type, number of files acted on per scan, number of elements acted on per scan, and whether the instruction converts data between integer and floating point formats. Table 9.O shows PLC-5/10, -5/12, -5/15, and -5/25 processors. When you use these tables, keep these guidelines in mind: for integer to floating point conversion, add: 8 µs for each element address 10 µs for each file address (# prefix) for floating point to integer conversion add: 33 µs for each element address 44 µs for each file address (# prefix) Table 9.O Timing and Memory Requirements for File Instructions Category
File Arithmetic and Logic
Code
FAL
Time (µs) Integer
Time (µs) Floating point
Time (µs) Integer or Floating Point
True
True
False
98 + W[36.7 + N]
98 + W[95.1 + N]
54
7-12 multiply
98 + W[42.5 + N]
98 + W[101.2 + N] divide
98 + W[51.1 + N]
98 + W[180.3 + N] square root
98 + W[84.7 + N]
98 + W[220.5 + N]
54
6-10 negate
98 + W[29.2 + N]
98 + W[37.2 + N] clear
98 + W[18.4 + N]
98 + W[24.0 + N]
54
5-8 move
98 + W[27.3 + N]
98 + W[36.2 + N]
54
6-10 convert to BCD
98 + W[54.3 + N] convert from BCD
98 + W[45.4 + N]
AND
98 + W[37.2 + N]
54
7-12
OR
98 + W[37.2 + N]
XOR
98 + W[37.2 + N]
NOT
98 + W[28.2 + N]
54
6-10 all comparisons
93 + W[32.7 +N]
Title add
Words of Memory1 subtract
File Search and Compare
FSC
93 + W[43.3 +N]
W= number of elements acted on per scan
N=
2 x (number of integer file addresses) + 8 x (number of floating-point file addresses) + 6 x (number of timer, counter, or control file addresses) + ( number of conversions between integer and floating point formats)
1 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
9-11
Page 129
Chapter 9 Calculating Program Timing
Category
File
Shift Register
Diagnostic
Code
Title
Time (µs) Integer or Floating Point
True
True
False copy counter, timer, and control
88 + 2.7W 98 + 5.8W
104 + 3.8W
20
FLL fill
81 + 2/.1 W
100 + 3.1W
15 counter, timer, and control
97 + 4.4W
BSL bit shift left
74 + 3.4W
BSR bit shift right
78 + 3.0W
FFL
FIFO load
54
44
FFU
FIFO unload
68 + 3.2W
46
FBC file bit compare 75 + 6W
1 mismatch
130 + 6W
2 mismatches
151 + 6W
0 mismatch
71 + 6W
1 mismatch
150 + 6W
2 mismatches
161 + 6W 12 master control
Immediate I/O
IIN immediate input
57
31
31
18
1 2-3 local
196 remote
204
16 immediate output 16 local
202 remote
166
SQI sequencer input
57
14
5-9
SQL sequencer load
55
42
4-7
SQO sequencer output
77
42
5-9
JMP jump
45
15
2-3
JSR jump to subroutine
SBR
0 parameters
56
15
2-3
1 parameter
91 add per parameter
21
RET
LBL
3-5 return from sub. 0 parameters
48
1 parameter
70 add per parameter
21 label
12
W = number of elements acted on per scan 1 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
9-12
4-7 diagnostic detect
MCR
IOT
Words of Memory1
6-11
0 mismatch
Zone Control
Jump and Subroutine
Time (µs) Floating point
COP
DDT
Sequencer
Time (µs) Integer
13
1 2-3
12
3
Page 130
Chapter 9 Calculating Program Timing
Category
Miscellaneous
Code
Title
Time (µs) Integer
Time (µs) Floating point
Time (µs) Integer or Floating Point
True
True
False
Words of Memory1
1
END end negligible negligible
TND temporary end negligible
15
AFI always false
15
13
ONS one shot
28
30
2-3
DTR data transitional
41
41
4-7
BTD bit distributor
77
14
6-11
PID
PID loop control
608
34
5-9
BTR block transfer read
BTW block transfer write
MSG message
See Block Transfer BTR, BTW chapter See Message MSG chapter
W= number of elements acted on per scan
N=
2 x (number of integer file addresses) + 8 x (number of floating-point file addresses) + 6 x (number of timer, counter, or control file addresses) + ( number of conversions between integer and floating point formats)
1 Use the smaller number if all addresses are below word 4096; use the larger number if all addresses are above 4096.
Program Constants
Use program constants in compare, compute, and file instructions to improve instruction execution times. Integer constants and floating-point constants execute in less than 1 µs. Note that if you program using constants you must edit the program to change the constants. If you program using data table addresses, you can change the values by simply changing the value in the data table.
Direct and Indirect Elements
Directly Addressed Elements Additional execution time for directly addressed elements depends on: data types location in memory, referenced to the beginning of all data files (output file, word 0) whether data is stored at the source or destination address whether the instruction converts data Table 9.P lists times to add to instruction execution times.
9-13