Page 131
Chapter 9 Calculating Program Timing
Table 9.P Additional Execution Time Based on Source and Destination Addresses Data Type
Source (integer to floating point)
Destination (floating point to integer)
0-2K
2-4K
4K+
0-2K
2-4K
4K+
Integer
0
1
2
0
1
2
Floating point
0
3
4
0
3
4
Data conversion
8
9
10
33
34
35
When file addresses (# prefix) in the expression or destination address contain indirect addresses for file numbers, add: 45 µs 48 µs 48 µs when the indirect address is integer type when the indirect address is floating point type when the indirect address is timer, counter, or control type
When file addresses in the expression or destination contain indirect addresses for element numbers, add: 45 µs 46 µs 46 µs when the indirect address is integer type when the indirect address is floating point type when the indirect address is timer, counter, or control type
If the file address contains two indirect addresses, add only one value (the largest). For example, for #F[N7:20][N7:30], add 48 µs (indirect floating point file address). Multiply the additional time by the number of elements in the file for any type of file or file address. For one FAL example: Expression:
#N[N7:100]/10 * F8:20 add 10 for converting to floating point add 45 for indirect address
Destination:
#N7:30 add 35 for converting to integer
FAL multiply:
98 + W[42.5 + N + indirect addressing] N = 2(2) +8 (1) + 6(0) + 10 + 35 = 57 W = 16
Execution time in ALL mode:
9-14
98 + 16[42.5 + 57 +45] 2410 µs
Page 132
Chapter 9 Calculating Program Timing
Indirect Bit or Elements Addresses Additional execution times for indirectly addressed bits and elements depends on the number of variable (indirect) addresses in the overall address. Table 9.Q lists the additional times. Table 9.Q Additional Execution Times for Indirectly Addressed Bits and Elements Data Type
Time (µs) for Variable File or Element
Time (µs) for Variable File and Element
Bit in binary file
57
60
Bit in integer file
60
63
Bit in timer, counter, or control file
64
66
Integer (N)
42
42
Timer, counter, or control file
43
44
Floating point (F)
61
64
Converting integer to floating point
71
77
Converting timer, counter, or control to floating point
85
81
9-15
Page 133
Chapter
10
Maximizing System Performance
Chapter Objectives
This chapter explains how to calculate throughput and provides methods for optimizing remote I/O scan time in PLC-5/11, -5/20, -5/30, -5/40, -5/40L, -5/60, -5/60L, and -5/80 processors. If you want to read about:
Go to page:
Components of throughput
10-1
Input and output modules delay
10-1
I/O backplane transfer
10-2
Remote I/O scan time
10-2
Processor time
10-6
Calculating throughput
10-6
For information on the time that it takes the processor to execute a specific instruction, see chapter 9.
System Design Determined
Choosing Hardware
Selecting Interrupt Routines
Placing System Hardware
Transferring Discrete and Block Data
Assigning Addressing Mode, Racks, and Groups
Calculating Program Timing
Choosing Communication
Maximizing System Performance
Planning Your System Programs
Components of Throughput
Throughput is the time that it takes for an output to be energized after its associated input has been energized. You need to consider the following components when evaluating throughput: input and output module delay I/O backplane transfer remote I/O scan time processor time
Input and Output Modules Delay
All input and output modules have a “delay time” - the time that it takes the module to transfer information to/from the I/O backplane through the I/O module to/from the field device. Depending on the type of modules you are using, these delay times vary; but the times must be taken into account when calculating system throughput. Choose modules that perform the function that you need with the lowest possible delay times.
10-1
Page 134
Chapter 10 Maximizing System Performance
I/O Backplane Transfer
The I/O backplane transfer time is the time it takes for the 1771-ASB adapter module to exchange data with the I/O modules in the same chassis, generally 1-2 ms for a full I/O rack. This time is fairly insignificant compared to total system throughput but can be optimized in situations where there are empty slots or modules that only use backplane power in the chassis. For example, if the last four slots of a rack contain a 1785-KA module and power supply (with 2 empty slots), the 1771-ASB can be configured to ignore those last four slots. For more information on configuring your ASB module, refer to the 1771 Remote I/O Adapter Module User Manual, publication 1771-6.5.83.
Remote I/O Scan Time
Rack 1
Remote I/O Buffer
Data Exchange
I/O Image Table
Read Inputs Write Outputs
Data Exchange x y
IOT (x) IIN (y)
Housekeeping
Adapter Adapter
Rack 2
Immediate I/O x y
Adapter
Rack 3
The remote I/O scan time is the time it takes for the scanner to communicate with each device in the remote I/O system.
Processor- Resident Rack
Remote I/O Scan
Logic Scan
Program Scan
Three factors that affect the remote I/O scan time are: communication rate number of chassis block transfers
Communication Rate The baud rate determines the time it takes for the scanner to communicate with each individual entry in its scan list. Table 10.A lists the amount of time required to communicate to a device at each communication rate.
10-2
Page 135
Chapter 10 Maximizing System Performance
Table 10.A Communication Times at Different Communication Rates Communication Rate (kbps)
Time (ms)
57.6
10
115.2
7
230.4
3
Note that these are full rack times. Smaller racks will decrease this time.
If there are four full-rack entries in the scan list, the I/O scan for that channel at 57.6 kbps is 4 x 10 = 40 ms. If you change the baud rate to 230.4 kbps, the I/O scan decreases to 4 x 3 = 12 ms. Important: All devices on the network must support the baud rate you chose and must be within the required cable lengths.
Number of Rack Entries You determine the total remote I/O scan time in the remote I/O system by taking the number of rack entries in the scan list and multiplying by the time per rack at the baud rate that you are using (see Table 10.A). If one channel has twice as many racks as another, for example, the scan time for the first channel is twice as long. To optimize this scan time, divide your I/O racks between multiple channels. Place your most time-critical I/O on one channel, and nontime-critical I/O on the other channel. Since all I/O channels are independent, a long remote I/O scan on one channel will not affect the remote I/O scan on another channel.
Block Transfers A block transfer is an interruption of the normal remote I/O scan in order to transfer a block of data to a specific I/O module. Most of the time that the processor spends in performing the block transfer is for the handshaking that occurs between the processor and the block-transfer module; this handshaking is embedded in the discrete I/O transfer and has no effect on the remote I/O scan. The remote I/O scan is affected when the actual transferring of data is occurring. The amount of time that the block transfer interrupts the remote I/O scan depends on the number of words being transferred and the baud rate: Communication Rate (kbps)
ms/Word
Overhead (ms)
57.6
.28
3
115.2
.14
2.5
230.4
.07
2
10-3
Page 136
Chapter 10 Maximizing System Performance
If the communication rate is 115.2 kbps and you want to block transfer 10 words, for example, the interruption of the remote I/O scan is: (10 x .14) + 2.5 = 1.4 + 2.5 = 3.9 ms For the particular remote I/O scan in which the block transfer takes place, 3.9 ms will be added to the remote I/O scan time.
Calculating Worst-Case Remote I/O Scan Time Since it is impossible to predict which remote I/O scan a block transfer will occur within, you can only calculate the worst-case remote I/O scan time. To calculate the worst case, determine the normal I/O (without block transfers) then add the time of the longest block transfer to each entry in the scan list. (The processor can only perform 1 block transfer per entry in the scan list per I/O scan.) For example, if your system is: Rack 1 PLC
BT BT 10 20 words words
115.2 kbps
Rack 2 No BTs Rack 3
Worst-case I/O scan: (3 x 6)
3 racks at 115.2 kbps normal I/O scan
+ (20 x .14) + 2.5 longest BT in rack 1
+ 0 no BTs in rack 2
+ (30 x .14) + 2.5 longest BT in rack 2
18 + 5.3 + 0 + 6.7 = 30 ms
BT 30 words
Optimizing Remote I/O Scan Time The best way to optimize your scan time is to place your most time-critical I/O on a separate channel from non-critical I/O. If you only have one channel available for I/O, however, you can still optimize the scanning by using the processor’s configurable scan list. In a normal 4-rack system, the scan list would be:
rack 1 rack 2 rack 3 rack 4
If you are using 57.6 kbps, the normal I/O scan is 4 racks x 10ms - 40ms. Each entry is of equal priority, so each rack is scanned every 40 ms.
10-4
Page 137
Chapter 10 Maximizing System Performance
However, if rack 2 has the most time-critical I/O, use the configurable scan rack 1 list to specify: rack 2 rack 3 rack 2 rack 4 rack 2
Using this scan list, rack 2 is scanned every other rack. There are 6 entries, so the normal I/O scan time is 6 x 10 ms = 60 ms. Since rack 2 is scanned every other rack, however, the rack 2 effective scan time is 2 x 10 ms = 20 ms. The remaining racks are scanned every 60ms. Thus, the tradeoff for the more frequent scanning of rack 2 (every 20 ms) means that the other racks are scanned only every 60 ms. You can also optimize block transfers within the channel. You block transfer to only one block transfer module per entry in the scan list per I/O scan. If you have three block-transfer modules in one I/O rack, it takes a minimum of three I/O scans to complete the block transfers to all of the modules: System Optimized for Discrete-Data Transfer
BT BT BT
Maximum scan time
= 3 discrete scans + 1 block transfer = 3D + 1BT
Adapter
PLC
Adapter
With this arrangement, there is only one block transfer to each BT module for every 3 discrete I/O scans.
Minimum time to complete a block transfer to all modules
Adapter
= 3 * (3D + 1BT) = 9D + 3BT
If you place the three block-transfer modules in different racks, however, you can block transfer to all three modules in one I/O scan. To optimize your system layout for block-data transfers, use an arrangement similar to the following: System Optimized for Block-Data Transfer
Adapter Adapter
PLC
Adapter
With this arrangement, there is a block transfer to each BT module every discrete I/O scan. BT
Maximum scan time
= 3 discrete scans + 3 block transfers = 3D + 3BT
BT
Minimum time to complete a block transfer to all modules BT
= 1 * (3D + 3BT) = 3D + 3BT
10-5
Page 138
Chapter 10 Maximizing System Performance
Processor Time
The processor time is the time needed to process the inputs and set the corresponding outputs. This processor time varies for different processors and is based on input buffering, program scan, etc. In a PLC-5 system, both inputs and outputs are buffered between the I/O image table and the I/O scanner. The movement of inputs from the scanner to the input buffer is asynchronous to the movement of data from the input buffer to the input image table. The worst-case processor time is: Periodic input buffer update
= 10 ms
One program scan to guarantee inputs received
= xx ms
One program scan to guarantee outputs received
= xx ms
.18 ms times the number of racks
= xx ms
For a 3-rack system with a 20 ms program scan, the worst-case processor time is: 10 + 20 + 20 + .54 = 50.54 ms.
Calculating Throughput Input Card Delay
+
To calculate throughput, use the following equation:
I/O Backplane
+
Worst-Case Remote I/O Scan Time
+
Worst-Case + Processor Time
Worst-Case Remote I/O Scan Time
+
An example of a worst-case update time calculation: Input card delay
= 20 ms (typical)
I/O backplane
= 1 ms
Worst-case remote I/O scan time
= 30 ms
Worst-case processor time
= 50.54 ms
Worst-case remote I/O scan time
= 30 ms
I/O backplane
= 1 ms
Output card delay
= 8.8 ms (typical) Total
10-6
141.34 ms
I/O Backplane
Output + Card Delay
Page 139
Appendix
A
Selecting Switch Settings
Chassis Backplane with Classic PLC-5 Processor
Make the following switch selections for Classic PLC-5 processors. Switch
Last State
1
Always Off
ON
Outputs of this I/O chassis remain in their last state when a hardware failure occurs. 1
OFF
Outputs of this I/O chassis are turned off when a hardware failure occurs. 1
Switches
Addressing
4
5
OFF
OFF
2 -slot
OFF
ON
1 -slot
ON
OFF
1/2 - slot
ON
ON
Not allowed
Switches 6 OFF
7 OFF
ON
ON
ON
OFF
EEPROM Transfer EEPROM memory transfer to processor memory at powerup. 2 EEPROM memory transfers to processor memory if processor memory not valid. EEPROM memory does not transfer to processor memory. 3
Switch 8
RAM Memory Protection
OFF
RAM memory protection disabled.
ON
RAM memory protection enabled. 4
Pressed in at top ON (closed) Pressed in at bottom OFF (open)
1. Regardless of this switch setting, outputs are reset when either of the following occurs: • processor detects a runtime error • an I/O chassis backplane fault occurs • you select program or test mode • you set a status file bit to reset a local rack 2. If an EEPROM module is not installed and processor memory is valid, the processor's PROC LED indicator blinks, and the processor sets S:11/9, bit 9 in the major fault status word. 3. A processor fault occurs if processor memory (solid red PROC LED) is not valid.
19309
4. You cannot clear processor memory when this switch is on
A-1
Page 140
Appendix A Selecting Switch Settings
Chassis Backplane with Adapter Module
Make the following switch selections for a 1771-AS, -ASB, or -ALX adapter module. Switch
Last State
1
Always Off
Always Off
ON
Outputs of this I/O chassis remain in their last state when a communication fault is detected by this I/O adapter. 1
OFF
Outputs of this I/O chassis are turned off when a comunication fault is detected by this I/O adapter.
Switch
Processor Restart Lockout
2 ON
Processor can restart the I/O chassis after a communication fault. 2
OFF
You must manually restart the I/O chassis with a switch wired to the 1771-AS or -ASB.
Switches
Addressing
5
6
OFF
OFF
2-slot
ON
OFF
1-slot 3
OFF
ON
1/2-slot 3
ON
ON
Not allowed
Pressed in at top Closed (ON) Pressed in at bottom Open (OFF)
1. ATTENTION: If you set this switch to the ON position, when a communication fault is detected, outputs connected to this chassis remain in their last state to allow machine motion to continue. We recommed that you set switch 1 to the OFF position to de-energize outputs wired to this chassis when a fault is detected. Also, if outputs are controlled by inputs in a different rack and a remote I/O rack fault occurs (in the inputs rack), the inputs are left in their last non-faulted state. The outputs may not be properly controlled and potential personnel and machine damage may result. If you want your inputs to be anything other than their last non-faulted state, then you need to program a fault routine. 2. Set this switch to ON if you plan to use I/O rack auto-configuration. 3. The 1771-ASB series A adapter does not support 1/2-slot addressing.
A-2
19308