The text of a manual · part 15 of 19
Classic 1785 PLC-5 Programmable Controllers User Manual (1785-LT, -LT2, -LT3, -LT4), pages 141 to 150
Pages 141 to 150 of 186
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1785-LT2, Allen-Bradley 1785-LT3, Allen-Bradley 1785-LT4 and Allen-Bradley 1785-LT B
Page 141
Appendix A Selecting Switch Settings
Chassis Configuration Plug for Power Supply
Position the configuration plug for the power supply you add to your chassis.
Y N
USING POWER SUPPLY MODULE IN THE CHASSIS?
Y N
Set Y when you install a power supply module in the chassis.
Y N
Set N when you use an external power supply.
1.
Locate the chassis configuration plug (between the first two left most slots of the chassis).
2.
Set the I/O chassis configuration plug. The default setting is N (not using a power supply module in the chassis).
IMPORTANT: You cannot power a single I/O chassis with both a power supply module and an external power supply.
17075
A-3
Page 142
Appendix A Selecting Switch Settings
Remote I/O Adapter Module 1771-ASB Series C without Complementary I/O
Select the switches to determine I/O rack, group, transmission rate, link response, and scan for your adapter module without complementary I/O.
Pressed in at top Closed (ON) Pressed in at bottom Open (OFF)
SW–1 O 1 N O F F
2
3
I/O Rack Number (see next page)
4
5
6
7
8 O 1 N O F F
2
First I/O Group Number (see below) Switch
A-4 on = closed off = open
SW–2 3
4
5
6
Link Response: ON for series B emulation OFF for unrestricted
1
2
Maximum Chassis Distance
ON OFF OFF ON
OFF OFF ON ON
57.6 Kbps 10,000 ft 115.2 Kbps 5,000 ft 230.4 Kbps 2,500 ft Not used
Scan: ON for all but last 4 slots OFF for all slots
First I/O Group Number
7
8
0 on on
2 on off
4 off on
6 off off
Page 143
Appendix A Selecting Switch Settings
Remote I/O Adapter Module (1771-ASB Series C) I/O Rack Number without Complementary I/O Rack
1
2
3
4
5
6
01 on on on on on off
02 on on on on off on
03 on on on on off off
04 on on on off on on
05 on on on off on off
06 on on on off off on
07 on on on off off off
10 on on off on on on
11 on on off on on off
12 on on off on off on
13 on on off on off off
14 on on off off on on
15 on on off off on off
16 on on off off off on
17 on on off off off off
20 on off on on on on
21 on off on on on off
22 on off on on off on
23 on off on on off off
24 on off on off on on
25 on off on off on off
26 on off on off off on
27 on off on off off off
PLC-5/15 processors racks 01-03; PLC-5/25 processors racks 01-07;
A-5
Page 144
Appendix A Selecting Switch Settings
Remote I/O Adapter Module 1771-ASB Series C with Complementary I/O
Select the switches to determine I/O rack, group, transmission rate, link response, and scan for your adapter module using complementary I/O.
Pressed in at top Closed (ON) Pressed in at bottom Open (OFF) S W -1 O 1 N O F F
2
3
4
5
SW–2 6
7
O 1 N O F F
8
ON Primary Chassis OFF Complementary Chassis I/O Rack Number First I/O Group Number
Switch
3
4
5
6
Link Response: ON for series B emulation
1
2
Maximum Chassis Distance
ON
OFF
57.6 Kbps 10,000 ft
OFF
OFF
115.2 Kbps 5,000 ft
OFF ON
ON ON
230.4 Kbps 2,500 ft not used
OFF for unrestricted ON scans for all but 4 last slots OFF scans for all slots ON Primary Chassis OFF Complementary Chassis
I/O Rack Number
4
5
6
1 on on off
2 on off on
3 on off off
41 off on on
51 off on off
61 off off on
71 off off off
1 Valid for PLC-5/25 processors only. Only seven racks can be complemented in a PLC-5 system.
A-6
2
For First I/O Group Number
7
8
0 on on
2 on off
4 off on
6 off off
Page 145
Appendix A Selecting Switch Settings
SW1
Set SW1 switch assembly switches 1 through 6 for the DH+ station number. Switch 7 is not used. Set switch 8 for scanner or adapter mode. T op V iew of M odule
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
S w itch A ssem bly S W 1 To select:
Set switch:
To:
DH+ Station Number
1 through 6
(see below)
Switch 7 not used
7 off
Scanner mode
8 off
Adapter
8 on
Switch
DH+ Station Number
1
2
3
4
5
0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37 on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on on on on on off off off off off off off off on on on on on on on on off off off off off off off off on on on on on on on on on on on on on on on on off off off off off off off off off off off off off off off off
Switch
6
DH+ Station Number
1
2
3
4
5
6 on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on
40 41 42 43 44 45 46 47 50 51 52 53 54 55 56 57 60 61 62 63 64 65 66 67 70 71 72 73 74 75 76 77 on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on off off off off on on on on on on on on off off off off off off off off on on on on on on on on off off off off off off off off on on on on on on on on on on on on on on on on off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off off
A-7
Page 146
Appendix A Selecting Switch Settings
Adapter-Mode Processors SW2 in a PLC-5 or Scanner Module
Set SW2 switch assembly switches for an adapter-mode PLC-5 processor in a PLC-5 processor or scanner module. Set switches 2 through 8 for number of words communicated from the host processor to the adapter processor, for the I/O group, and for the rack number of the I/O group of the adapter processor, respectively. Switch 1 is unused. Switch Assembly SW2
Bottom View of Module
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
1234
Switch Assembly SW3 If you want:
Set switch:
To:
Switch 1 is always unused.
1 off
The host processor to use 8 words to communicate with the adapter PLC-5 processor
2 off
The host processor to use 4 words to communicate with the adapter PLC-5 processor
2 on
First I/O group to be 0
3 on
First I/O group to be 4
3 off
4 through 8 see table below
Select the I/O rack number of the adapter PLC-5 processor
A-8
Rack
4
5
6
7
8
Rack
4
5
6
7
8
01 on on on on off
15 on off off on off
02 on on on off on
16 on off off off on
03 on on on off off
17 on off off off off
04 on on off on on
20 off on on on on
05 on on off on off
21 off on on on off
06 on on off off on
22 off on on off on
07 on on off off off
23 off on on off off
10 on off on on on
24 off on off on on
11 on off on on off
25 off on off on off
12 on off on off on
26 off on off off on
13 on off on off off
27 off on off off off
14 on off off on on
Page 147
Appendix A Selecting Switch Settings
Adapter-Mode Processors SW2 in a PLC-2/20, -2/30, or Sub I/O Scanner Module System
Set SW2 switch assembly switches for an adapter-mode PLC-5 processor in a PLC-2/20 or -2/30 processor system or sub I/O scanner module system. Set switches 2 through 8 for the number of words communicated from host processor to adapter processor, for the I/O group, and for the rack number of the I/O group of the adapter processor, respectively. Switch 1 is unused. Switch Assembly SW2
Bottom View of Module
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
1234
Switch Assembly SW3 If you want:
Set switch:
To:
Switch 1 is always unused.
1 off
The host processor to use 8 words to communicate with the adapter PLC-5
2 off
The host processor to use 4 words to communicate with the adapter PLC-5
2 on
First I/O group to be 0
3 on
First I/O group to be 4
3 off
4 through 8 see below
Select the I/O rack number of the adapter PLC-5 processor Rack
4
5
6
7
8
01 on on on on on
02 on on on on off
03 on on on off on
04 on on on off off
05 on on off on on
06 on on off on off
07 on on off off on
A-9
Page 148
Appendix A Selecting Switch Settings
Adapter-Mode Processors SW2 in a PLC-3 or PLC-5/250 System with 8-Word Groups
Set SW2 switch assembly switches for an adapter-mode PLC-5 processor in a PLC-3 or PLC-5/250 processor system. Set switch 2 for the number of words communicated from host processor to the adapter processor. Set switches 3 through 8 for the I/O rack number of the adapter processor. Switch 1 is unused. Switch Assembly SW2
Bottom View of Module
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
1234
Switch Assembly SW3 If you want:
Set switch:
To:
Switch 1 is always unused.
1 off
The host processor to use 8 words to communicate with the adapter PLC-5 processor
2 off
3 through 8 see below
Select the I/O rack number of the adapter PLC-5 processor
Switch
I/O Rack No.
3
4
5
6
7
8
0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 20 21 22 23 24 25 on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on on off off off off off off on on on on on on on on off off off off off off off off on on on on on on on on on on off off off off on on on on off off off off on on on on off off on on off off on on off off on on off off on on off off on on off off on on on off on off on off on off on off on off on off on off on off on off on off
A-10
Switch
I/O Rack No.
3
4
5
6
7
8
26 27 30 31 32 33 34 35 36 37 40 41 42 43 44 45 46 47 50 51 52 on on on on on on on on on on off off off off off off off off off off off off off off off off off off off off off on on on on on on on on on on on on on off off off off off off off off on on on on on on on on off off off off off on on on on off off off off on on on on off off off off on on on off off on on off off on on off off on on off off on on off off on on off on off on off on off on off on off on off on off on off on off on off on
Switch
I/O Rack No.
3
4
5
6
7
8
53 54 55 56 57 60 61 62 63 64 65 66 67 70 71 72 73 74 75 76 off off off off off off off off off off off off off off off off off off off off on on on on on off off off off off off off off off off off off off off off off off off off off on on on on on on on on off off off off off off off on off off off off on on on on off off off off on on on on off off off off on on off off on on off off on on off off on on off off on on off off on off on off on off on off on off on off on off on off on off on
Page 149
Appendix A Selecting Switch Settings
Adapter-Mode Processors SW2 in a PLC-3 or PLC-5/250 System with 4-Word Groups
Set SW2 switch assembly switches for an adapter-mode PLC-5 processor in a PLC-3 or PLC-5/250 processor system. Set switch 2 for the number of words communicated from the host processor to the adapter processor. Set switch 3 for I/O group. Set switches 4 through 8 for the I/O rack number of the adapter processor. Switch 1 is unused. Switch Assembly SW2
Bottom View of Module
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
1234
Switch Assembly SW3 If you want:
Set switch:
To:
Switch 1 is always unused.
1 off
The host processor to use 4 words to communicate with the adapter PLC-5 processor
2 on
First I/O group to be 0
3 on
First I/O group to be 4
3 off
4 through 8 see below
Select the I/O rack number of the adapter PLC-5 processor
Switch
Switch
I/O Rack Number
4
5
6
7
8
I/O Rack Number
4
5
6
7
8
0 1 2 3 4 5 6 7 10 11 12 13 14 15 16 17 on on on on on on on on on on on on on on on on on on on on on on on on off off off off off off off off on on on on off off off off on on on on off off off off on on off off on on off off on on off off on on off off on off on off on off on off on off on off on off on off
20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37 off off off off off off off off off off off off off off off off on on on on on on on on off off off off off off off off on on on on off off off off on on on on off off off off on on off off on on off off on on off off on on off off on off on off on off on off on off on off on off on off
A-11
Page 150
Appendix A Selecting Switch Settings
SW3
Set SW3 switch assembly switches to terminate either a DH+ link or a remote I/O link. Switches 3 and 4 are unused.
Bottom View of Module
1234
Side View toggle pushed toward bottom on (closed) toggle pushed toward top off (open)
12345678
Switch Assembly SW3
If the processor is:
A-12
Set switch:
To:
An end device on the remote I/O link
1 on
Not an end device on the remote I/O link
1 off
An end device on the DH+ link
2 on
Not an end device on the DH+ link
2 off
Switch 3 unused
3 off
Switch 4 unused
4 off