Page 21
Chapter 2 Choosing Hardware
Table 2.A Guidelines for Selecting I/O Modules Choose this type of I/O module:
For these types of field devices or operations (examples):
Explanation:
Discrete input module and block I/O module1
Selector switches, pushbuttons, photoelectric eyes, limit switches, circuit breakers, proximity switches, level switches, motor starter contacts, relay contacts, thumbwheel switches
Input modules sense ON/OFF or OPENED/ CLOSED signals. Discrete signals can be either ac or dc.
Discrete output module and block I/O module1
Alarms, control relays, fans, lights, horns, valves, motor starters, solenoids
Output module signals interface with ON/OFF or OPENED/CLOSED devices. Discrete signals can be either ac or dc.
Analog input module
Temperature transducers, pressure transducers, load cell transducers, humidity transducers, flow transducers, potentiometers
Convert continuous analog signals into input values for PLC processor.
Analog output module
Analog valves, actuators, chart recorders, electric motor drives, analog meters
Interpret PLC processor output to analog signals (generally through transducers) for field devices.
Specialty I/O modules
Encoders, flow meters, I/O communication, ASCII, RF type devices, weigh scales, bar-code readers, tag readers, display devices
Are generally used for specific applications such as position control, PID, and external device communication.
1
A 1791 block I/O module is a remote I/O device that has a power supply, remote I/O adapter, signal conditioning circuitry, and I/O connections. A block I/O module does not require a chassis mount. It is used to control concentrated discrete remote I/O such as control panels, pilot lights, and status indications.
Important: Determine addressing in conjunction with I/O module selection. The selection of addressing and the selection of I/O module density are mutually dependent.
Selecting I/O Module Density The density of an I/O module is the number of processor input or output image table bits to which it corresponds. A bidirectional module with 8 input bits and 8 output bits has a density of 8. Table 2.B provides guidelines for selecting I/O module density. Table 2.B Guidelines for Selecting I/O Module Density
2-2
Choose this I/O density:
If you:
8-point I/O module
• currently use 8-point modules • need integral, separately-fused outputs • want to minimize cost per module
16-point I/O module
• currently use 16-point modules • need separately fused outputs with a special wiring arm
32-point I/O module
• currently use 32-point modules • want to minimize number of modules • want to minimize the space required for I/O chassis • want to minimize cost per I/O point
Page 22
Chapter 2 Choosing Hardware
Master/Expander I/O Modules Some I/O modules (called “masters”) communicate with their expanders over the backplane. These master/expander combinations either: can time-share the backplane, or cannot time-share the backplane For masters that can time-share the backplane, you can use two masters in the same chassis. For a master/expander combination that cannot time-share the backplane, you cannot put another master/expander combination in the same I/O chassis. Example: The stepper-controller module (cat. no. 1771-M1, part of a 1771-QA assembly) and the servo-controller module (cat. no. 1771-M3, part of a 1771-QC assembly) always act as masters and cannot time-share the backplane. Therefore, you cannot put a second master module in the same chassis with either of these modules. Table 2.C summarizes the compatibility of master modules within a single I/O chassis. Table 2.C Compatibility of Master Modules within a Single I/O Chassis 1st Master Module
1771-IX1
1771-IX1
1771-IF1
2nd Master Module 1771-OF1 1771-M1
Valid2
Valid2
1771-IF1
Valid2
Valid2
Valid2
1771-OF1
Valid2
Valid2
Valid2
1771-M3
1771-M1 1771-M3 1
These modules have been superseded by 1771-IXE, -IFE, and OFE master modules that do not exhibit the master/expander conflict in a chassis as 1771-IX, -IF, and OF master modules shown in this table.
2
These are the only master combinations that you can use in a single I/O chassis. These combinations are valid with or without the module's associated expanders (1771-M1 and -M3 have expander modules). You can use a maximum of two masters in the same chassis; you can use any other intelligent I/O modules not shown here with these masters.
Important: Density is not relevant to an expander module because it communicates only with its master; an expander module does not communicate directly with an adapter.
2-3
Page 23
Chapter 2 Choosing Hardware
Selecting I/O Adapter Modules
Select I/O adapter modules to interface your PLC-5 processor with I/O modules. Use Table 2.D as a guide when you select I/O adapter modules. Table 2.D Guidelines for Selecting Adapter Modules
ASB
ALX
Choose:
When your requirements are:
1771-AS or 1771-ASB1 Remote I/O Adapter Module (or 1771-AM1, -AM2 chassis with integral power supply and adapter module)
a remote I/O link with: • 57.6 kbps with a distance of up to 10,000 cable feet or • timing that isn't critical enough to place I/O modules in a processor local I/O chassis or an extended-local I/O chassis
1771-ALX Extended-Local I/O Adapter Module an extended-local I/O link with timing that is critical and all extended-local I/O chassis are located within 100 ft of the processor.
11771-ASB series C and later have 230.4 kbps communication rate in addition to 57.6 kbps and 115.2 kbps.
17 71-AS/ASB Remote I/O Adapter Modules Table 2.E shows the I/O density per module and addressing modes you can use with I/O chassis and remote I/O adapter modules. Table 2.E I/O Chassis/Adapter Module Combinations Addressing
Remote I/O Adapter Module Cat. No.
I/O Density per Module
2-Slot
1-Slot
1/2-Slot
1771-AS
8 16 32
Yes --1 No
No No No
No No No
1771-ASB Series A
8 16 32
Yes --1 No
Yes Yes --1
No No No
1771-ASB Series B, C, and D
8 16 32
Yes --1 No
Yes Yes --1
Yes Yes Yes
1771-AM2
8 16 32
-- -- --
Yes Yes --1
Yes Yes Yes
1 Conditional module placement; you must use an input module and an output module in two adjacent slots (even/odd pair) of the I/O chassis beginning with slot 0. If you cannot pair the modules this way, leave the adjacent slot empty.
Using the 1771-ASB Series C or D adapter module, you can choose one of three communication rates: 57.6 kbps, 115.2 kbps, or 230.4 kbps.
2-4
Page 24
Chapter 2 Choosing Hardware
1771-ALX Extended-Local I/O Adapter Module Table 2.F shows the I/O density per module and addressing modes you can use with I/O chassis and extended-local I/O adapter modules. Table 2.F I/O Chassis/Extended -Local I/O Adapter Module Combinations Module Cat. No. 1771-ALX Series A 1
Addressing
I/O Density per Module
2-Slot
1-Slot
1/2-Slot
8 16 32
Yes --1 No
Yes Yes --1
Yes Yes Yes
Conditional module placement; you must use an input module and an output module in two adjacent slots (even/ odd pair) of the I/O chassis beginning with slot 0. If you cannot pair the modules this way, leave the adjacent slot empty.
Other Devices on an I/O Link Other devices that you can use on a remote I/O link are: PLC-5 processor in adapter mode PLC-5/250 remote scanner in adapter mode PLC interface module for digital ac and dc drives remote I/O adapter for Bulletin 1336 drives RediPANELt pushbutton and keypad modules Datalinert PanelView (see operator interface) F30D option module (for T30 plant-floor terminal) 8600 or 9/SERIES CNC with remote I/O adapter option CVIMt in adapter mode Pro-Spect 6000 Fastening System with remote I/O adapter option 1747-DCM module (to SLC-500 rack) 1771-DCM module 1771-GMF robot (remote I/O interface module) See the appropriate Allen-Bradley product catalog for more information on these devices.
2-5
Page 25
Chapter 2 Choosing Hardware
Selecting I/O Chassis
An I/O chassis is a single, compact enclosure for the processor, power-supply modules, remote and extended-local I/O adapter modules, and I/O modules. The left-most slot of the I/O chassis is reserved for the processor or adapter module. Consider the following when selecting a chassis: When you determine the maximum number of I/O in your application, allow space for the I/O slots dedicated to power-supply modules, communication modules, and other intelligent I/O modules.
4-Slot
You must use series B or later chassis with 16- and 32-point I/O modules. Allow space for future addition of I/O modules to chassis.
1771-A1B
I/O chassis available are: 4-slot (1771-A1B) 8-slot (1771-A2B) 12-slot - rack mount (1771-A3B), panel mount (1771-A3B1) 16-slot (1771-A4B) You can also choose a chassis with an integral power supply and remote I/O adapter (show at left). The two types are: 1771-AM1 1771-AM2
Selecting an Operator Interface
2-6
1-slot (1771-AM1) 2-slot (1771-AM2)
PanelView and ControlView are operator interface products or packages that communicate with a PLC-5 processor. Use Table 2.G as a guideline when selecting either PanelView or ControlView for your PLC-5 programmable controller system. Use Table 2.H for a comparison of PanelView and ControlView features.
Page 26
Chapter 2 Choosing Hardware
Table 2.G Guidelines for Selecting an Operator Interface Choose this operator interface:
For these types of operations (examples):
Explanation:
PanelView1
Starts/stops, auto/manual operations, Used as an operator window to enter commands that make process adjustments such setpoints, outputs, alarms as starts/stops and loop changes. Can also be used for alarming operations. Can communicate with a single PLC-5 processor on a remote I/O link. Has a fixed number of devices and amount of data that it can handle. Has built-in error checking. Is an industrial-hardened CRT with pushbuttons, solid state memory and processor, and no moving parts (i.e., disk drive). Utilizes pass through, which is the ability to download/upload via DH+/remote I/O links.
ControlView1
Store, display, and manipulate data on process performance (i.e., trends, process graphics, formulas, reports, and journals)
Used as an operator window that communicates with a PLC-5 processor on Data Highway Plus (DH+) link. Designed for use as an information link. Can communicate to multiple PLC processors. ControlView is a software package that runs on an IBMr DOS-based personal computer.
1 Refer to your local Allen-Bradley sales office or Allen-Bradley distributor for more information on PanelView and ControlView.
Table 2.H Comparison of PanelView and ControlView Features Category
PanelView
Communication with PLC processor
Remote I/O
Graphics
Character graphics Create screens with PanelBuilder software Monochrome or color (8 of 16 colors displayed at a time)
ControlView
DH+ link 5 block transfers per terminal maximum (32 words per transfer) Data Highway Data Highway II Native Mode 1 discrete transfer per terminal (64 words maximum, one way) This is 8 racks of transfer Pixel Graphics Create screens with Mouse Grafix editor option or C Toolkit EGA, VGA, or equivalent with 256K RAM Monochrome or color monitor
Number of 8 to 12 screens of medium complexity typical Screens per 200 objects maximum per screen Terminal/Workstation Limited by terminal memory size: 128 Kbytes
Limited only by hard disk capacity 50 data entry locations per screen 50 tags per command list per screen 300 tags/points maximum per screen
Data Capacity
200 objects maximum per screen
10,000 points maximum in database
Communication Rate
Limited by block-transfer and discrete-transfer timing
8 scan classes, each with user-configurable foreground and background update times; limited by performance of Data Highway, DH+, or Data Highway II link
Hardware
Keypad or Touchscreen terminals, color or monochrome
Depends on PLC processor and remote I/O link size Allen-Bradley, IBM, or compatible computer required for PanelBuilder software
Programming
PanelBuilder software Menu-driven with fill-in-the-blank information entry Use PanelBuilder to create application file that defines screens, messages, alarms, then download application file to PanelView terminal
A-B, IBM, or compatible computer with 286 or 386 processor, math coprocessor, hard disk required at each operator station Create data base online via the menu. Menu-driven, fill-in-the-blank information entry, or import data via the ASCII import capability Create screens with the mouse GRAFIX editor option or C toolkit option
Messages
496 maximum per terminal
Not Applicable
Alarms
496 maximum per terminal
2000 points with Alarming option
Security
8 levels
16 levels with individual operator login capability Individual objects with security Screen lockout
Options
Remote serial port EEPROM or EPROM memory
Lots of software options
2-7
Page 27
Chapter 2 Choosing Hardware
For more information on selecting and configuring PanelView, see: PanelView Operator Terminal and PanelBuilder Development Software User Manual, cat. no. 2711-ND002 version C, PN40061-139-01 - request latest revision Replacing Node Adapter Firmware for PanelView Terminals Installation Data, PN40062-236-01 - request latest revision For more information on selecting and configuring ControlView, see: ControlView Core User Manual, publication 6190-6.5.1 ControlView Allen-Bradley Drivers User Manual, publication 6190-6.5.5 ControlView Networking User Manual, publication 6190-6.5.9
Other Operator Interfaces You can use the following as operator interfaces in your PLC-5 processor system: RediPANEL pushbutton and keypad modules Dataliner 1784-T47 and 1784-T53 programming terminals See the appropriate Allen-Bradley product catalog for more information on these operator interfaces.
2-8
Page 28
Chapter 2 Choosing Hardware
Choosing a Classic PLC-5 Processor for Your Application Processor/ Cat. No. PLC-5/10 (1785-LT4) PLC-5/12 (1785-LT3)
Maximum User Memory Words
6K
6K
PLC-5/15 (1785-LT)
6 K expandable to 10 K or 14 K
PLC-5/25 (1785-LT2)
13 K expandable to 17 K or 21 K
Choose from the following PLC-5 processors. Table 2.I Classic PLC-5 Processor Selection Chart Part 1
EEPROM Module Memory (Words) & Module Number
Total I/O Maximum (any mix)
Analog I/O Max
Program Scan Time / K Word
I/O Scan time/Rack (in a single Chassis, ext-local or remote)
Multiple MCPs / Quantity
8 K (1785-MJ)
• 512 (32-I/O modules) • 256 (16-I/O modules) • 128 (8-I/O modules)
256
2 ms (discrete logic) 8 ms (typical)
N/A
No / 1
8 K (1785-MJ)
• 512 (32-I/O modules) • 256 (16-I/O modules) • 128 (8-I/O modules)
256
2 ms (discrete logic) 8 ms (typical)
• 10 ms @ 57.6 kbps (remote)
No / 1
8 K (1785-MJ)
• 512 (any mix) or • 512 in + 512 out (complementary)
512
2 ms (discrete logic) 8 ms (typical)
• 10 ms @ 57.6 kbps (remote)
No / 1
8 K (1785-MJ) or 16 K (1785-MK)
• 1024 (any mix) or • 1024 in + 1024 out (complementary)
1024
2 ms (discrete logic) 8 ms (typical)
• 10 ms @ 57.6 kbps (remote)
No / 1
Table 2.J Classic PLC-5 Processor Selection Chart Part 2 Maximum Number of I/O Chassis Total
Ext Local
Remote
Number of RS-232/ 422/ 423 ports
1
1
0
0
0
--
2.5A
• 1 DH+ • 1 Remote I/O (Adapter Only)
4
1
0
0
0
57.6 kbps
2.5A
PLC-5/15 (1785-LT)
• 1 DH+ • 1 Remote I/O (Adapter or Scanner)
4
13
0
12
0
57.6 kbps
2.5A
PLC-5/25 (1785-LT2)
• 1 DH+ • 1 Remote I/O (Adapter or Scanner)
8
17
0
16
0
57.6 kbps
2.5A
Processor/ Cat. No.
Number of Remote I/O, Extended-Local I/O, and DH+ Ports
Maximum Number of I/O Racks
PLC-5/10 (1785-LT4)
• 1 DH+
PLC-5/12 (1785-LT3)
Selecting Power Supplies
Remote I/O Transmission Rates1
Backplane Current Load
Use the following steps as guidelines for selecting a power supply for a chassis that contains a PLC-5 processor, a 1771-AS or -ASB remote I/O adapter module, or a 1771-ALX extended-local I/O adapter module. 1.
Determine the input voltage for the power supply.
2.
Calculate the total backplane current draw for I/O modules by adding together the backplane current draw for each I/O module in that chassis.
1771-P7
2-9
Page 29
Chapter 2 Choosing Hardware
3.
4.
5.
Add to the total of the I/O module backplane current draw either: a.
3.3 Amps when the chassis will contain a PLC-5 processor (maximum current draw for any PLC-5 processor) or b.
1.2 Amps when the chassis will contain either a remote I/O 1771-AS or -ASB module or a 1771-ALX extended-local I/O adapter module
If you leave slots available in your chassis for future expansion: a.
list backplane current draw for future I/O modules b.
add the total current draw for all expansion I/O modules to the total calculated in step 3.
Determine whether the available space for the power supply is in the chassis or mounted external to the chassis.
Choose your power supply from Table 2.K or Table 2.L using the input voltage requirement and the total backplane current draw as determined in the previous steps, 1 through 5. See the Automation Products Catalog, publication AP100, for more information on power supplies.
Powering a Chassis Containing a PLC-5 Processor Table 2.K lists the power-supply modules that you can use with a Classic PLC-5 processor.
2-10
Page 30
Chapter 2 Choosing Hardware
Table 2.K Powering a Chassis Containing a Classic PLC-5 processor Power Supply
Input Power
Output Current (in Amps)
1771-P3
120V ac
1771-P4
Output Current (in Amps) When Parallel with: P4S1 P5
P6S
Power Supply P6S1 Location
P3
P4
P4S
3
6
11
11 chassis, 1-slot
120V ac
8
11
16
16 chassis, 2-slot
1771-P4S
120V ac
8
11
16
16 chassis, 1-slot
1771-P4S1
100V ac
8
1771-P4R
120V ac
8/16/241
1771-P5
24V dc
8
1771-P6S
220V ac
8
1771-P6S1
200V ac
8
1771-P6R
220V ac
8/16/241
1771-P7
120/220V ac
16
1771-PS7
120/220V ac
16
16
16 chassis, 2-slot 16 chassis, 1-slot 16 external2
1 See publication 1771-2.136 for more information. 2 You cannot use an external power supply and a slot-based power supply module to power the same chassis; they are not compatible.
2-11