Page 31

Chapter 2 Choosing Hardware

Powering a Remote I/O Chassis Containing a 1771-AS or 1771-ASB or an Extended-Local I/O Chassis Containing a 1771-ALX Table 2.L lists the power supply modules that you can use with a remote I/O chassis or an extended-local I/O chassis. Table 2.L Powering a Remote I/O Chassis (Containing a 1771-AS or -ASB) or an Extended-Local I/O Chassis (Containing a 1771-ALX) Power Supply

Input Power

Output Current (in Amps)

1771-P3

120V ac

1771-P4

Output Current (in Amps) When Parallel with: P4S1 P5

P3

P4

P4S

3

6

11

11 chassis, 1-slot

120V ac

8

11

16

16 chassis, 2-slot

1771-P4S

120V ac

8

11

16

16 chassis, 1-slot

1771-P4S1

100V ac

8

1771-P4R

120V ac

8/16/24 1

1771-P5

24V dc

8

1771-P6S

220V ac

8

1771-P6S1

200V ac

8

1771-P6R

220V ac

8/16/24 1

1771-P1

120/220V ac

6.5

1771-P2

120/220V ac

6.5

1771-P7

120/220V ac

16

1771-PS7

120/220V ac

16

1777-P2

120/220V ac

9

1777-P4

24V dc

9

16

16

1 See publication 1771-2.136 for more information. 2 You cannot use an external power supply and a slot-based power supply module to power the same chassis; they are not compatible.

2-12

P6S

Power Supply P6S1 Location chassis, 2-slot 16 chassis, 1-slot 16 external 2

Page 32

Chapter 2 Choosing Hardware

Selecting Memory Modules

Select a memory module from Table 2.M for your PLC-5 processor. Table 2.M PLC-5 Processor Memory Modules Nonvolatile Memory Backup (EEPROM)

Selecting a Replacement Battery

RAM Memory (CMOS)

Words

Catalog Number (and Processor)

Words

Catalog Number (and Processor)

8K

1785-MJ

4K

1785-MR (PLC-5/15 and -5/25)

16 K

1785-MK (PLC-5/25)

8K

1785-MS (PLC-5/15 and -5/25)

A battery ships with your PLC-5 processor. Select a replacement battery using Table 2.N and Table 2.O. See the Allen-Bradley Guidelines for Handling Lithium Batteries, publication ICCG-5.14, for more information.

Table 2.N Processor Batteries Processor

Battery1

Function

PLC-5/10, -5/12, -5/15, and -5/25

1770-XY, AA lithium

Retains the processor memory and the memory in an optional CMOS RAM module if the processor is not powered.

1 The 1770-XY is a 3.6 Volt AA size lithium thionyl chloride battery manufactured by Tadiran as their part number TL 5104 and type AEL/S.

Table 2.O Average Battery Life

Selecting Complementary I/O

Battery

Temperature

Power Off 100% (Average)

Power Off 50% (Average)

1770-XY

60° C 25° C

329 days 2 years

1.4 years 3.3 years

You configure complementary I/O by assigning an I/O rack number of one I/O chassis (primary) to another I/O chassis (complementary). You complement I/O functions in the primary chassis with opposite functions in the complementary chassis. Use chapter 4, “Assigning Addressing Mode, Racks, and Groups,” in conjunction with the following selection of complementary I/O hardware.

2-13

Page 33

Chapter 2 Choosing Hardware

Use the following modules in either primary or complementary I/O chassis opposite any type of module: Communication Adapter Module (1771-KA2) Communication Controller Module (1771-KE) PLC-2 Family/RS-232-C Interface Module (1771-KG) Fiber Optics Converter Module (1771-AF) DH/DH+ Communication Adapter Module (1785-KA) DH+/RS-232C Communications Interface Module (1785-KE) Use the following modules in either primary or complementary I/O chassis opposite any type of module. However, these modules do not work as standalone modules; each one has an associated master module. Use care when placing the master modules in the I/O chassis (refer to the paragraph on Master/Expander I/O modules): Analog Input Expander Module (1771-E1, -E2, -E3) Analog Output Expander Module (1771-E4) Servo (Encoder Feedback) Expander Module (1771-ES) Pulse Output Expander Module (1771-OJ)

Selecting a PLC-5 Processor Backup System

A PLC-5 processor backup system contains two of each of the following hardware components: Classic PLC-5 processor module Processor

Catalog Number

PLC-5/15

1785-LT Series B

PLC-5/25

1785-LT2

1785-BCM Series C Backup Control Module (for 2 channels) 1785-BEM Backup Expansion Module (for 2 additional channels) Power supply Local chassis Important: The PLC-5 backup system does not back up I/O in the processor-resident local chassis. Do not install I/O in the processorresident local chassis of a backed up system. Refer to the PLC-5 Backup Communication Module User Manual, publication 1785-6.5.4, for more information on configuring a PLC-5 processor backup system.

2-14

Page 34

Chapter 2 Choosing Hardware

Selecting Link Terminators

Terminate remote I/O links by setting switch assembly SW3. If you cannot use an 82-Ohm terminator because of devices that you place on your I/O link (see the table below for a list of these devices), you must use 150-Ohm terminators. Using the higher resistance reduces the quantity of devices to 16 that you can place per remote I/O link. Also, this limits your communication rates to 57.6 kbps and 115.2 kbps.

DH+ Network Terminator Terminate your DH+ network with a 150-Ohm, 1/2-watt terminator. If you have this processor:

Terminate a DH+ link by:

PLC-5/10, -5/12, -5/15, or -5/25

Setting switch assembly SW3 of the PLC-5 processor (refer to your Classic 1785 PLC-5 Family Programmable Controllers Hardware Installation Manual, publication 1785-6.6.1).

Connecting a Programming Terminal to a Processor Module

Connect the programming terminal directly to the processor through the D-shell DH+ COMM INTFC connector on the front panel. You can also connect the programming terminal remotely to a DH+ link through the 3-pin connector or at a remote station.

Choosing Cables

Select cables from the options listed below. See chapter 3, “Placing System Hardware,” to determine the lengths that you will need for cables in your system.

Remote I/O Link Use Belden 9463 twinaxial cable (1770-CD) to connect your PLC-5 processor to remote I/O adapter modules. Connect your I/O devices using: single-conductor wire (analog and some discrete applications) multi-conductor cable (analog and some discrete applications) multi-conductor shielded cable (some specialty I/O modules and low-voltage dc discrete modules)

2-15

Page 35

Chapter 2 Choosing Hardware

See the Classic 1785 PLC-5 Programmable Controllers Hardware Installation Manual, publication 1785-6.6.1, and the installation data for the I/O modules that you have selected for more information on I/O wiring. Also, see Allen-Bradley Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1, and Control, Communication and Information Reference Guide, publication ICCG-1.2, for more information.

Programming Terminal The cable that you use to connect a processor to a programming terminal depends on the communication device used. Table 2.P lists the cables that you need for different configurations. Table 2.P Cables for Connecting a Classic PLC-5 Processor and Programming Terminal If you have this device:

With this communication device:

Use this cable:

PLC-5/10, -5/12, -5/15, or -5/25

1784-KT, -KT2 1784-KL, -KL/B

1784-CP

1784-KTK1

1784-CP5

1784-PCMK

1784-PCM5

6160-T60, 6160-T70, 6121 IBM PC/AT (or compatible)

1785-KE

1784-CAK

1784-T47, 6123, 6124 IBM PC/XT (or compatible)

1785-KE

1784-CXK

6120, 6122

1785-KE

1784-CYK

You can also use a 1770-KF2/B communication interface to connect to a PLC-5 processor. You build your own cables to connect your programming terminal via the COM1 or COM2 serial ports to the 1770-KF2/B. For the cable pin assignments, see the Classic 1785 PLC-5 Programmable Controller Hardware Installation Manual, publication 1785-6.6.1.

2-16

Page 36

Chapter

3

Placing System Hardware

Chapter Objectives

A well-planned layout is essential to the proper installation of your Classic PLC-5 programmable controller system. Read this chapter for information on placing hardware. If you want to read about:

System Design Determined

Go to page:

Proper environment

3-1

Protecting your system

3-4

Avoiding electrostatic damage

3-4

Planning your raceway layout

3-4

Planning your cabling

3-6

Grounding your system

3-7

Choosing Hardware Placing System Hardware Assigning Addressing Mode, Racks, and Groups Choosing Communication

Selecting Interrupt Routines Transferring Discrete and Block Data Calculating Program Timing

Planning Your System Programs

Determining the Proper Environment

Place the processor in an environment with conditions that fall within the guidelines described in Table 3.A. Table 3.A Proper Environmental Conditions For Your Processor Environmental Condition

Acceptable Range

Operating temperature

0 to 60° C (32 to 140° F)

Storage temperature

-40 to 85° C (-40 to 185° F)

Relative humidity

5 to 95% (without condensation)

Separate your programmable controller system from other equipment and plant walls to allow for convection cooling. Convection cooling draws a vertical column of air upward over the processor. This cooling air must not exceed 60° C (140° F) at any point immediately below the processor. If the air temperature exceeds 60° C, install fans that bring in filtered air or recirculate internal air inside the enclosure, or install air-conditioning/heatexchanger units.

3-1

Page 37

Chapter 3 Placing System Hardware

To allow for proper convection cooling in enclosures containing a processor-resident chassis and remote I/O chassis, follow these guidelines.

Minimum spacing requirements for a processor-resident chassis: • Mount the I/O chassis horizontally.

Area reserved for disconnect. transform er, control relays, m otor starters or other user devices.

• Allow 153 mm (6 in) above and below the chassis. • Allow 102 mm (4 in) on the sides of each chassis. • Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips.

153mm (6")

51mm (2") 102mm (4")

102mm (4")

51mm(2")

• Leave any excess space at the top of the enclosure, where the temperature is the highest.

153mm (6")

Wiring Duct 13081

3-2

Page 38

Chapter 3 Placing System Hardware

Minimum spacing requirements for a remote I/O chassis: Area reserved for disconnect. transformer, control relays, mo t o r starters or other user devices.

102mm (4")

153mm (6")

153mm (6 ")

• Allow 153 mm (6 in) above and below all chassis. When you use more than one chassis in the same area, allow 152.4 mm (6 in) between each chassis. • Allow 102 mm (4 in) on the sides of each chassis. When you use more than one chassis in the same area, allow 101.6 mm (4 in) between each chassis. • Allow 51 mm (2 in) vertically and horizontally between any chassis and the wiring duct or terminal strips.

51mm (2") Wiring Duct 51mm (2")

102mm (4")

• Mount the I/O chassis horizontally.

• Leave any excess space at the top of the enclosure, where the temperature is the highest.

102mm (4") 153mm (6")

Wiring Duct 18749

3-3

Page 39

Chapter 3 Placing System Hardware

Protecting Your Processor

You provide the enclosure for your processor system. This enclosure protects your processor system from atmospheric contaminants such as oil, moisture, dust, corrosive vapors, or other harmful airborne substances. To help guard against EMI/RFI, we recommend a steel enclosure. Mount the enclosure in a position where you can fully open the doors. You need easy access to processor wiring and related components so that troubleshooting is convenient. When you choose the enclosure size, allow extra space for transformers, fusing, disconnect switch, master control relay, and terminal strips.

Avoiding Electrostatic Damage

ATTENTION: Under some conditions, electrostatic discharge can degrade performance or damage the processor module. Read and observe the following precautions to guard against electrostatic damage. Wear an approved wrist strap grounding device when handling the processor module. Touch a grounded object to discharge yourself before handling the processor module. Do not touch the backplane connector or connector pins. When not handling the processor module, keep it in its protective packaging.

Laying Out Your Cable Raceway

3-4

The raceway layout of a system reflects where the different types of I/O modules are placed in I/O chassis. Therefore, you should determine I/O-module placement prior to any layout and routing of wires. When planning your I/O-module placement, however, segregate the modules based on the conductor categories published for each I/O module so that you can follow these guidelines. These guidelines coincide with the guidelines for “the installation of electrical equipment to minimize electrical noise inputs to controllers from external sources” in IEEE standard 518-1982.

Page 40

Chapter 3 Placing System Hardware

To plan a raceway layout, do the following: categorize conductor cables route conductor cables

Categorize Conductors Segregate all wires and cables into categories as described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. See the installation data for each I/O module that you are using for information about its classification.

Route Conductors To guard against coupling noise from one conductor to another, follow the general guidelines for routing cables described in the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. You should follow the safe grounding and wiring practices called out in the National Electrical Code (NEC, published by the National Fire Protection Association, in Quincy, Massachusetts), and local electrical codes.

Planning Cabling

DH+ Link Cabling At a DH+ transmission rate of 57.6 kbps, do not exceed 3,048 cable-m (10,000 cable-ft) for a trunkline cable length or 30.5 cable-m (100 cable-ft) for a dropline cable length.

Remote I/O Link Cabling Refer to Table 3.B for remote I/O link trunkline cable length restrictions. Table 3.B Maximum Cable Lengths per Communication Rate Transmission Rate

Maximum Cable Length

57.6 kbps

3,048 m (10,000 ft)

115.2 kbps

1,524 m (5000 ft)

230.4 kbps

762 m (2500 ft)

Important: All devices on the remote I/O link must be communicating at the same transmission rate.

3-5