Page 41

Chapter 3 Placing System Hardware

Laying Out the Backpanel Spacing

Use 6.35 mm (0.25 inch) mounting bolts to attach the I/O chassis to the enclosure backpanel. Figure 3.1 Chassis Dimensions (Series B)

1771-A1B 1771-A2B 1771-A3B1 1771-A4B

591mm (23.25") 337mm (13.25")

193mm1 (7.60")

Side

464mm (18.25") 210mm (8.25")

315mm (12.41")

16-slot 1771 12-slot 8-slot 4-slot

254mm (10")

Power Connector

171mm (6.75")

483mm (19.01") 229mm (9.01")

1771-A3B 217mm1 (8.54")

465mm (18.31")

610mm (24.01")

16-slot 1771-A4B

356mm (14.01")

8-slot 1771-A2B

12-slot 1771-A3B1 4-slot 1771-A1B

484mm (19")

9mm (.34")

26mm (1.02") 178mm (7")

Side

339mm (13.53")

Front

130mm (5.10") 12450-I 1Total maximum depth dimension per installation will be dependent upon module wiring and connectors.

3-6

Page 42

Chapter 3 Placing System Hardware

Figure 3.2 I/O Chassis and 1771-P2 Power Supply Dimensions Use .25" dia mounting bolts (4 places)

315mm (12.41")

591mm (23.25")

16-slot

337mm (13.25")

464mm (18.25")

12-slot

210mm (8.25")

4-slot

8-slot

1771-P1 1771-P2 1771-P7 1771-PS7 Power Supply

91mm (3.6")

254mm (10")

483mm (19.01")

610mm (24.01")

16-slot 1771-A4B 12-slot 1771-A3B1

356mm (14.01") 229mm (9.01") Clearance depth is 204 mm (8 in) for 8 I/O connection points per module.

Grounding Configuration

8-slot 1771-A2B 4-slot 1771-A1B 12451-I

See Figure 3.3 for the recommended grounding configuration for remote I/O systems. Figure 3.3 Recommended Grounding Configuration for Remote I/O Systems Enclosure Ground Bus

Grounding Electrode Conductor

To Grounding Electrode System I/O Chassis Wall Ground Lug Nut Star Washer Ground Lug 15561

3-7

Page 43

Chapter

4

Assigning Addressing Modes, Racks, and Groups

Chapter Objectives

This chapter conveys basic hardware addressing concepts and gives you guidelines with which to choose the addressing modes (including complementary I/O), racks, and groups to use in your system.

If you want to read about:

Go to page:

Placing I/O modules in chassis

4-1

Understanding terms

4-2

Choosing I/O addressing mode

4-3

Rack number assignments

4-9

Addressing complementary I/O

4-12

System Design Determined

Choosing Hardware Placing System Hardware Assigning Addressing Mode, Racks, and Groups

Selecting Interrupt Routines Transferring Discrete and Block Data Calculating Program Timing

Choosing Communication Planning Your System Programs

Placing I/O Modules in Chassis

Place I/O modules in a chassis depending on the electrical characteristics of the modules. The placement is made left to right, with the left-most position being closest in the chassis to the PLC-5 processor or the I/O adapter module. The placement order is as follows: 1. 2. 3. 4. 5.

block-transfer modules (all types) dc input modules, placed left to right from lowest to highest voltages dc output modules, placed left to right from lowest to highest voltages ac input modules, placed left to right from lowest to highest voltages ac output modules, placed left to right from lowest to highest voltages

4-1

Page 44

Chapter 4 Assigning Addressing Modes, Racks, and Groups

The following guidelines are for placing block-transfer modules. Place as many modules as possible for which you need fast block-transfer times in your processor-resident local I/O chassis . Place modules that need fast block-transfer times (but space is not available in processor-resident local I/O chassis) in an extended-local I/O chassis. Place modules in which timing is not as critical as in other block-transfer modules in remote I/O chassis. ac output modules should always be the furthest I/O modules from any block-transfer modules in the same chassis.

Understanding the Terms Used in this Chapter

Become familiar with the following terms and their definitions: An I/O group is an addressing unit that corresponds to an input image-table word (16 bits) and an output image-table word (16 bits). An I/O group can contain up to 16 inputs and 16 outputs; and it can occupy 2-, 1-, or 1/2-module slots for addressing purposes.

Input Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

Output Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

2-Slot I/O Module Group (I/O Group #0)

4-2

Output or Input Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

1-Slot I/O Module Group 13073 (I/O Group #0)

Page 45

Chapter 4 Assigning Addressing Modes, Racks, and Groups

An I/O rack is an addressing unit that corresponds to 8 input image-table words and 8 output image-table words. A rack contains 8 I/O groups. I/O Group Numbers .

0

1

2

3

4

5

6

7

13074

Depending on I/O chassis size and I/O group size, an I/O rack can occupy a fraction of an I/O chassis, a full I/O chassis, or multiple I/O chassis.

Choosing the Addressing Mode

Select an addressing mode for each chassis independently, based on the type and density of the I/O modules contained therein. When you select addressing mode, limit the number of remote I/O adapters and I/O modules to the maximum number that the PLC-5 processor can support.

Using 2-Slot Addressing When you select 2-slot addressing, the processor addresses two I/O module slots as one I/O group. Each physical 2-slot I/O group corresponds to one word (16 bits) in the input image table and one word (16 bits) in the output image table. The type (unidirectional or bidirectional) and density of a module that you install determines the number of bits that are used in each word. Important: You cannot use 32-point I/O modules with 2-slot addressing.

4-3

Page 46

Chapter 4 Assigning Addressing Modes, Racks, and Groups

8-Point I/O Modules Eight-point digital discrete I/O modules have a maximum of eight inputs or up to eight outputs. Because they do not interfere with each other’s I/O image, you can place any mix of 8-point I/O modules (including bidirectional modules, such as block-transfer modules) in any order.

2-Slot I/O Group with One 8-pt Input Module and One 8-pt Output Module

2-Slot I/O Group with Two 8-pt Input Modules

2-Slot I/O G roup

2-Slot I/O G roup

Input Terminals 00 01 02 03 04 05 06 07

Input Terminals 10 11 12 13 14 15 16 17

Input Terminals 00 01 02 03 04 05 06 07

Output Terminals 10 11 12 13 14 15 16 17

Output Image-Table Word Corresponding to the I/O Group. Output Image-Table Word Corresponding to the I/O Group.

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 Unused Output Bits Used

Input Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Unused

Input Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Always 0

This I/O group uses 16 bits of the input image table. 11867

4-4

Input Bits Used

This I/O group uses 8 bits of the input image table and 8 bits of the output image table.

14965

Page 47

Chapter 4 Assigning Addressing Modes, Racks, and Groups

16-Point I/O Modules Sixteen-point digital discrete I/O modules have up to 16 inputs or up to 16 outputs. A 16-point I/O module uses a full word in the input or output image table. 2-Slot I/O Group with One 16-pt Input Module and One 16-pt Output Module

Word # Output Image Table 0 1 2 3 4 5 6 7

2-Slot I/O G roup 0

1

2

3

4

5

6

7

I/O Group Designation I/O Chassis Containing 16-pt Modules

Input Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

Output Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

I OI OI OI OI OI OI OI O

Input/Output Designation Word # Input Image Table 0 1 2 3 4 5 6 7

Output Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Input Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Because each 16-pt module uses a full word in the image table, the only type of module that you can install in a 2-slot I/O group with a 16-pt input module is an 8- or 16-pt output module that performs a complementary function (inputs and outputs complement each other). Since all block-transfer modules are bidirectional, they cannot be used to complement either input or output modules.

This I/O group uses 16 bits of the input image table and 16 bits of the output image table.

15559

4-5

Page 48

Chapter 4 Assigning Addressing Modes, Racks, and Groups

Using 1-Slot Addressing When you select 1-slot addressing, the processor addresses one I/O module slot as one I/O group. Each physical slot in the chassis corresponds to an input and output image-table word. The type (unidirectional or bidirectional) and density of module that you install determines the number of bits used in these words. 8-Point I/O Modules You can place any mix of 8- or 16-point I/O modules (including bidirectional modules such as block-transfer modules) in any order with 1-slot addressing. The 8- or 16-point modules do not interfere with the I/O image of the other 8- or 16-point modules.

1-Slot I/O Group with One 16-pt Digital Discrete I/O Module 1-Slot I/O G roup

1-Slot I/O G roup

Input Terminals 0 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17

Output Terminals 00 01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 or

16-Point I/O Modules A single 16-point module uses an entire word of the processor image table. Block-Transfer Module Addressing To address a single-slot block transfer module in a 1-slot I/O group, use the assigned I/O rack and group numbers of the slot (in which the module resides) and 0 for the module number. To address a double-slot block-transfer module, use the assigned I/O rack number, the lower assigned I/O group number, and 0 for the module number.

Output Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

Input Image-Table Word Corresponding to the I/O Group. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

A single 16-pt module uses an entire word of image table.

4-6

11869

Page 49

Chapter 4 Assigning Addressing Modes, Racks, and Groups

32-Point I/O Modules To use 32-point I/O modules with 1-slot addressing, you must install, as a pair, an input module and an output module in two adjacent slots (even/odd pair) of the I/O chassis, beginning with I/O slot 0. If you cannot pair the modules in this way, one of the two slots of the pair must be empty. For example, if I/O slot 0 holds a 32-point input module, I/O slot 1 must hold an 8-, 16-, or 32-point output module (or a module using the backplane for power only); otherwise the slot must be empty. 1-Slot I/O Group with 32-pt I/O Modules

Word # 0 1 2 3 4 5 6 7 01 2 34 567

Output Image Table

I/O Group Designation

I/O Chassis with 1-Slot Addressing

I O I O I O IO

Slot 0 Input Module I/O Group 0, 1

Input/Output Designation Input Image Table Word # 0 1 2 3 4 5 6 7

Slot 1 Output Module I/O Group 0, 1 Output Image-Table Words Corresponding to I/O Groups 0 and 1. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 000 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00 001 Input Image-Table Words Corresponding to I/O Groups 0 and 1. 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

000

17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00

001 14258

4-7

Page 50

Chapter 4 Assigning Addressing Modes, Racks, and Groups

Using 1/2-Slot Addressing When you select 1/2-slot addressing, the processor addresses one-half of an I/O module slot as one I/O group. Each physical slot in the chassis corresponds to two input and two output image-table words. The type (unidirectional or bidirectional) and density of the module that you install determines the number of bits that are used in each word. 1/2-Slot I/O Group with One 32-pt Input Module Input Word 0 17

10

7

0

Im age- Table W ords Allocated for I/O G roup 0

Output Word 0 17

Input # 01 03 05 07 1/2-Slot I/O G roup 0 11 13 15 17 01 03 1/2-S lot I/O G roup 05 1 07 11 13 15 17 -

10 7 Unused

0

You can mix 8-, 16- and 32-pt I/O modules in any order in the I/O chassis because 32 input bits and 32 output bits are available in the image table for each I/O slot. When you use 8- and 16-pt I/O modules with 1/2-slot addressing, however, you use fewer total I/O bits in our image table.

Input # 00 02 04 06 1/2-Slot I/O Group 10 0 12 14 16 00 02 04 1/2- S lot I/O Group 06 1 10 12 14 16 -

Word # 0 1 2 3 4 5 6 7 024 6 135 7

Output Image Table Not Used

I/O Group Designation

I/O Chassis with 1/2-Slot Addressing

I I OO

Input/Output Designation Word # 0 1 2 3 4 5 6 7

Input Image Table

Always 0 14974

Input Word 1 17

10

7

0

Output Word 1 17

10 7 Unused

0

Im age- Table W ords Allocated for I/O Group 1

This I/O group uses two words of the image table.