Page 1

Technical Data

Control and Load Switch Specifications Bulletin Number 194E, 194L Topic

Page

Product Line Overview

2

194E General Specifications

3

194E Approximate Dimensions

5

194L Circuit Diagrams

13

194L General Specifications

17

Approximate Dimensions

20

Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource

Description

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Page 2

194 Control and Load Switches

Product Type Current Range Main Applications

Functionality

Mounting Styles

Product Overview

Bulletin 194E

Bulletin 194L

Inductive load-rated load switch

Inductive load-rated control/load switch

16…100 A

12…40 A

UL, CSA ratings "suitable as at-motor disconnect"

UL, CSA ratings "suitable as at-motor disconnect"

3- or 6-pole switch configurations for OFF-ON or changeover applications (16…100 A switches)

1- to 6-pole multifunction switch control configurations for OFF-ON, changeover, Star-Delta (Wye-Delta), reversing, ammeter, voltmeter, and step switch applications Also available in custom control configurations up to 16 circuits for any unique control switching application.

Front/door or base/DIN Rail mounting

Front/door or base/DIN Rail mounting

Handles

Handle colors in grey/black and red/yellow and padlockable versions Legend plates available in 0-I international markings and text styles

Uniformly styled handles: selector knob, disk style, rectangular style, and key-operated versions (Type 1/12, IP66) Handle colors in grey/black and red/yellow and padlockable versions Legend plates available in 0-I international markings and text styles

Open Switch or Enclosed

Open switch (large frame Bul. 194E, open style only) Enclosed: IP66 thermoplastic enclosure or UL/CSA rated enclosure

UL/CSA Electrical Ratings: Rated Voltage Ue

Open switch

600V AC

600V AC

16…100 A @ 600V

12…40 A @ 600V

Rated Power Pe [FLA]

Varies w/ 1- or 3-phase switch, voltage

Varies w/ 1- or 3-phase switch, voltage

Short-Circuit Ratings

5 kA

5 kA

Switching Rate [ops/h]

120

120

Rated Current Ie

Mechanical Life [ops]

1 million

0.2 million (16…100 A switches)

IEC Rated Current Ie AC-1

16…100 A @ 600V

12…40 A @ 600V

AC-21A

16…100 A @ 600V

12…40 A @ 600V

AC-22A

16…100 A @ 600V

12…40 A @ 600V

-25…+60 °C (-13…+140 °F)

-25…+60 °C (-13…+140 °F)

Ambient Operational Temp. Ambient Enclosed Temp.

-20…+60 °C (-4…+140 °F)

-20…+60 °C (-4…+140 °F)

Ambient Storage Temp.

-40…+80 °C (-40…+176 °F)

-40…+80 °C (-40…+176 °F)

Protection class per IEC 529

Switch bodies: IP2

Switch bodies: IP2

Optional Accessories

IP66 handles Multi-length shafts and shaft extension kits Terminal covers

Multi-length shafts and shaft extension kits Terminal covers

Standards/Certifications

UL 508 CSA C22.2, No. 14 IEC 60947-3 Low Voltage Switchgear and Controlgear part 3 CE

UL 508 CSA C22.2, No. 14 IEC 60947-3 Low Voltage Switchgear and Controlgear part 3 CE

2

Rockwell Automation Publication 194-TD002B-EN-P

Page 3

Specifications

194E Load Switches

Electrical Ratings Performance Data

16 A

25 A

32 A

40 A

63 A

80 A

100 A

IEC Applications

Aux. Contacts

Rated operational voltage (Ue):

[V]

690

690

690

690

690

690

690

690

Rated operational voltage (Ue): UL, CSA

[V]

600

600

600

600

600

600

600

600

Rated isolation voltage (Ui): IEC/UL, CSA

[V]

Rated impulse voltage (Uimp): UL, CSA

[kV]

8

8

8

8

8

8

8

8

Test voltage, (Ui) 1 minute

[kV]

2.5

2.5

2.5

2.5

2.5

2.5

2.5

2.5

690/600 690/600 690/600 690/600 690/600 690/600 690/600

690/600

Lost power per pole

[W]

0.58

1.0

1.5

1.6

2.4

3.6

5.5

0.4

Rated frequency

[Hz]

50/60

50/60

50/60

50/60

50/60

50/60

50/60

50/60

Conventional free air thermal current

[A]

25

40

50

63

75

100

120

12

Conventional enclosed thermal current

[A]

20

32

40

50

63

80

100

10

[A]

16

25

32

40

63

80

100

10

230V

[kW]

5.5

7.5

7.5

15

18.5

22

30, 400V

[kW]

7.5

11

15

22

30

37

55, 690V

[kW]

7.5

11

15

18.5

22

37

45, 230V

[kW]

4

5.5

7.5

11

15

18.5

22, 400V

[kW]

5.5

7.5

11

15

18.5

30

37, 690V

[kW]

5.5

7.5

11

15

18.5

30

22, [kA]

20

20

15

20

15

30

25, Rated current AC-1/

Non-inductive or only slightly inductive loads

AC-21A

Switching of resistive loads with slight overload

Rated power Pe AC-23A

AC-3

Occasional switching of 3Ø motors and other highly inductive loads (criterion for selecting main switches) Squirrel-cage motors; starting and stopping of running motors

Short circuit current (co-ordination type 2) Rated conditional short-circuit current Maximum fuse rating of circuit (type g,G) Rated short-time current Icw (1 s) Rated breaking capacity AC23A (cosφ 0.45)

[A]

20

25

35

50

63

80

100, [A]

800

900

900

1300

1300

2500

2500, 230V

[A]

156

296

296

484

484

780

780, 400V

[A]

120

256

256

504

504

800

800, 690V

[A]

70

136

136

196

196

376

376, 24/48V

400/415V

DC switching capacity

Rated current Ie

DC-21A

For resistive loads, T ≤ 1 ms Ue max = 660V

[A]

20

25

32

40

63

80

100

1 pole 110V

[A]

5

5

6

8

10

16

20

220V

[A]

1

1

1

1.5

15

3

3

440V

[A]

0.5

0.5

0.5

0.6

0.6

0.7

0.7

96V

[A]

20

25

32

40

63

80

100

2 poles 110V in 220V series 440V

[A]

20

23

25

32

50

70

80

[A]

5

5

6

8

10

16

20

[A]

1

1

1

1.5

1.5

3

3

600V

[A]

0.6

0.6

0.6

0.8

0.8

1

1

110V

[A]

20

25

32

40

63

80

100

3 poles 220V in series 440V 600V

[A]

13

13

15

20

28

50

63

[A]

2.2

2.2

2.2

3.6

3.6

6.5

6.5

[A]

1.3

1.5

1.5

2

2

3

3

1

1.3

1.5

2.9

4.1

5.1

7.2, - - Rated power Pe DC-23A, DC-3, DC-5 For inductive loads, T ≤ 15 ms

90V

[kW]

3 poles 110V in series 220V

[kW]

1

1.1

1.3

2.2

3.3

5.5

7

[kW]

0.8

0.9

1.1

1.7

2

3.5

4.4

440V

[kW]

0.6

0.6

0.6

0.9

0.9

1.1

1.1

600V

[kW]

0.4

0.4

0.4

0.5

0.5

0.9

0.9, See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-NonFused-Disconnect-Switches#specifications

Rockwell Automation Publication 194-TD002B-EN-P

3

Page 4

194E Load Switches

Specifications

Electrical Ratings, Continued Performance Data

16 A

25 A

32 A

40 A

63 A

80 A

100 A

UL/CSA Applications Continuous current Heavy Pilot Duty

[A]

16

25

32

40

63

80

100, [AC]

A600

A600

A600, - - - A600 Q600

Standard Duty

[DC], - - - - - - Motor rating 60 Hz

[FLA]

16

16

16

24

34

56

80

120V, 1P 240V, 1P

Single-phase (2 poles)

480V, 1P 600V, 1P 120V, 3P 240V, 3P

Three-phase 480V, 3P 600V, 3P

Aux. Contacts

[Hp]

1

1

1

2

3

5

7.5

[FLA]

12

12

17

17

28

50

68

[Hp]

2

2

3

3

5

10

15

[FLA]

8.5

8.5

14

21

26

34

68

[Hp]

3

3

5

7.5

10

15

30

[FLA]

11.2

11.2

11.2

16

20

27

44

[Hp]

5

5

5

7.5

10

15

25

[FLA]

13.6

13.6

19.2

30.4

40

56

84

[Hp]

2

2

3

5

7.5

10

15

[FLA]

9.6

15.2

22

28

42

68

80

[Hp]

3

5

7.5

10

15

25

30

[FLA]

11

14

21

27

34

52

65

[Hp]

7.5

10

15

20

25

40

50

[FLA]

11

11

17

22

27

52

52

[Hp]

10

10

15

20

25

50

50, - Mechanical Data 16 A

25…32 A

40…63 A

80…100 A

Aux. Contacts handles

IP66

IP66

IP66

IP66

IP66 switch bodies

IP20

IP20

IP20

IP20

IP20

0.2

0.2

0.2

0.2

0.2

Performance Data Protection class according to IEC 529 Motor rating 60 Hz

Mechanical life

[million operations]

Max wire gauges Terminal size per IEC 947-1

A4

A6

A7

A9

2xA2 rigid wire

[AWG] [mm2]

16…10 1…10

14…8 1.5…16

12…4 2.5…25

10…1 4…50

18…14 0.75…2.5 fine strands

[AWG] [mm2]

16…8 1.5…6

14…8 1.5…10

12…4 2.5…16

10…1 4…35

18…14 0.5…2.5

[N•m]/[lb•in]

1.4/12.2

1.4/12.2

2.8/24.5

5.6/50

1/8.8

Tightening torque

Environmental Data

4

Storage

-40…+80 °C (-40…+176 °F)

Operation

-25…+60 °C (-13…+140 °F)

Rockwell Automation Publication 194-TD002B-EN-P

Page 5

Approximate Dimensions

194E Load Switches

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Front Installation Cat. No. 194E-E…

1 (3/64)…5 (13/64)

Dia. 3.3 (1/8)

9.5 (3/8) 6-Pole 3-Pole Handles Cat. No.

P

Q

194L-HE4A

28 (1-7/64)

48 x 48 (1-57/64 x 1-57/64) 48 x 48 (1-57/64 x 1-57/64)

194L-HE4I

28 (1-7/64)

194E-HE4N

34 (1-11/32)

54 x 54 (2-1/8 x 2-1/8)

194E-HE4G

34 (1-11/32)

54 x 54 (2-1/8 x 2-1/8)

194L-HE6A

28 (1-7/64)

64 x 64 (2-33/64 x 3-5/64)

194L-HE6I

28 (1-7/64)

64 x 64 (2-33/64 x 3-5/64)

194L-HE6N

34 (1-11/32)

67 x 67 (2-41/64 x 2-41/64)

194L-HE6G

34 (1-11/32)

67 x 67 (2-41/64 x 2-41/64)

Switch Body Use with Cat. No.

B2

F

H

L‡

G

194E-E16

28 (1-7/64)

N/A

36 (1-37/64)

63 (2-31/64)

51 (2)

90 (3-35/64)

194E-E25/32

36 (1-27/64)

N/A

45 (1-25/32)

64 (2-33/64)

60 (2-3/8)

90 (3-1/2)

194E-E40/63

48 (1-57/64)

36 (1-27/64)

54 (2-1/8)

72 (2-27/32)

74 (2-29/32)

108 (4-1/4)

194E-E80/100

48 (1-57/64)

36 (1-27/64)

72 (2-27/32)

90 (3-35/64)

90 (3-35/64)

144 (5-11/16)

Does not apply to 194E-40/63A, 6-Pole Switches. Use B2 dimensions for 6-pole devices. ‡ For 6-pole switches, add 1 in. to the "L" dimension.

Cat. No. 194E-E Switch Body with Cat. No. 194L-HC4A Handle for 22.5 mm Hole Mounting Style

Type

L

194E-E16

76 (3)

194E-E25/32

84.5 (3-21/64)

194E-E40/63

98.5 (3-7/8)

194E-E80/100

114.5 (4-33/64)

Rockwell Automation Publication 194-TD002B-EN-P

5

Page 6

194E Load Switches

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Base Mounting Cat. No. 194E-A…

6-Pole 3-Pole

Handles Cat. No.

P

Q

194L-HE4A

28 (1-7/64)

48 x 48 (1-57/64 x 1-57/64)

194L-HE4I

28 (1-7/64)

48 x 48 (1-57/64 x 1-57/64)

194L-HE4S

28 (1-7/64)

48 x 62 (1-57/64 x 2-7/16)

194E-HE4N

34 (1-11/32)

54 x 54 (2-1/8 x 21/8)

194E-HE4G

34 (1-11/32)

54 x 54 (2-1/8 x 21/8)

194L-HE6A

28 (1-7/64)

64 x 64 (2-33/64 x 3-5/64)

194L-HE6I

28 (1-7/64)

64 x 64 (2-33/64 x 3-5/64)

194L-HE6S

28 (1-7/64)

64 x 78 (2-33/64 x 3-5/64)

194L-HE6N

34 (1-11/32)

67 x 67 (2-41/64 x 2-41/64)

194L-HE6G

34 (1-11/32)

67 x 67 (2-41/64 x 2-41/64) Cover Requirements

For Use With

Y min.

X≥

Y max.

X≥

194E-A16

5 (13/64)

142 (5-19/32)

9.5 (3/8)

90 (3-35/64)

194E-A25/32

5 (13/64)

142 (5-19/32)

9.5 (3/8)

90 (3-35/64)

194E-A40/63

2.5 (7/64)

150 (5-29/32)

9.5 (3/8)

90 (3-35/64)

194E-A80/100

2.5 (7/64)

150 (5-29/32)

9.5 (3/8)

90 (3-35/64)

Switch Body Use With Cat. No.

D3

E

F1

F2

G

H

L‡

J

194E-A16

4.5 (3/16)

70 (2-49/64)

12.5 (31/64)

23.5 (59/64)

90 (3-35/64)

63 (2-31/64)

80 (3-5/32)

36 (1-27/64)

194E-A25/32

4.5 (3/16)

70 (2-49/64)

30 (1-3/16)

15 (19/32)

90 (3-1/2)

64 (2-33/64)

59 (2-5/16)

45 (1-25/32)

194E-A40/63

4.5 (3/16)

80 (3-5/32)

37 (1-15/32)

17 (43/64)

108 (4-1/4)

72 (2-27/32)

73 (2-55/64)

54 (2-1/8)

194E-A80/100

5.6 (7/32)

95 (3-3/4)

48.5 (1-29/32)

23.5 (59/64)

144 (5-11/16)

90 (3-35/64)

89 (3-1/2)

72 (2-27/32)

‡ For 6-pole switches, add 1 in. to the "L" dimension.

6

Rockwell Automation Publication 194-TD002B-EN-P

Page 7

Approximate Dimensions

194E Load Switches

Base Mounting Cat. No. 194E-A… Cat. No. 194E-A… Switch Body with Cat. No. 194L-G2853 Shaft Extension Shaft extensions

Switch body

Switch Body Cat. No.

194E-A 16

194E-A 25/32

194E-A 40/63

194E-A 80/100

With 1 shaft extension

79 (3-7/64)

88 (3-15/32)

102 (4-1/32)

118 (4-21/32)

With 2 shaft extensions

103 (4-37/64)

112 (4-27/64)

126 (4-31/32)

142 (5-19/32)

With 3 shaft extensions

127 (5)

136 (5-23/64)

150 (5-29/32)

166 (6-35/64)

With 4 shaft extensions

151 (6-61/64)

160 (6-5/16)

174 (6-55/64)

190 (7-31/64)

With 5 shaft extensions

175 (7-57/64)

184 (7-1/4)

198 (7-51/64)

214 (8-7/16)

With 6 shaft extensions

199 (8-27/32)

208 (8-13/64)

222 (8-3/4)

238 (9-3/8)

For 6-pole switches, add 1 in. to the "L" dimension. Shaft

Y

194L-G2830

2.5…9.5 (7/64…3/8)

Type

B

Q

P

194L-G3194

9…18 (23/64…23/32)

194L-HE4A

36 (1-27/64)

48 x 48 (1-57/64 x 1-57/64)

28 (1-7/64)

194L-G3195

14…23 (9/16)…(29/32)

194L-HE4I

36 (1-27/64)

48 x 48 (1-57/64 x 1-57/64)

28 (1-7/64)

194E-HE4G

28 (1-7/64)

54 x 54 (2-1/8 x 2-1/8)

34 (1-11/32)

194E-HE4N

28 (1-7/64)

54 x 54 (2-1/8 x 2-1/8)

34 (1-11/32)

194L-HE6A

48 (1-57/64)

64 x 64 (2-33/64 x 2-33/64)

28 (1-7/64)

194L-HE6I

48 (1-57/64)

64 x 64 (2-33/64 x 2-33/64)

28 (1-7/64)

194L-HE6N

48 (1-57/64)

67 x 67 (2-41/64 x 2-41/64)

34 (1-11/32)

194L-HE6G

48 (1-57/64)

67 x 67 (2-41/64 x 2-41/64)

34 (1-11/32)

Handles

Rockwell Automation Publication 194-TD002B-EN-P

7

Page 8

194E Load Switches

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Base Installation Cat. No. 194E-A… Cat. No. 194E-A Switch Body with Metal Shaft Extension

Cat. No.

A

Cat. No.

194L-G3393

110…235 (4-11/32…9-1/4)

194E-A16

51 (2)

194L-G3394

230…350 (9-1/16…13-25/32)

194E-A25/32

60 (2-3/8)

194E-A40/63

74 (2-59/64)

194E-A80/100

90 (3-35/64)

For 6-pole switches, add 1 in. to the "L" dimension.

Base and Front Installation Cat. No. 194E… with Auxiliary Contact Block Installed

Contacts

M

1 N.O. + 1 N.C.

9 (23/64)

2 N.O. + 2 N.C.

18 (23/32)

Cat. No. 194E… with 4-Pole, Ground and Neutral Terminals

8

Cat. No.

M

194E-16

12.5 (31/64)

194E-25/32

14 (9/16)

194E-40/63

17.5 (11/16)

194E-80/100

22 (7/8)

Rockwell Automation Publication 194-TD002B-EN-P

Page 9

Approximate Dimensions

194E Load Switches

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Base Mounting Cat. No. 194E-A… Thermoplastic Enclosures

Complete Switches

Enclosures ABS

Cat. No.

Poles 3 and 4

Mounting Holes§

Noryl Cat. No.

Height A

Width B

Knockouts‡ ØD1

120 (4-23/32)

70 (2-3/4)

M16/M20 16/20 mm M25/M30 25/30 mm

194E-Y16

F

Depth H

PG11/PG16 18.5/22.5 mm

50 (1-31/32)

105 (4-9/64)

70 (2-49/65)

PG21/PG29 28.5/37.5 mm

On Center

145 (5-23/32)

105 (4-1/8)

6

194E-G3663 194E-G3664

180 (7-3/32)

125 (4-59/64)

3 and 4

194L-G3572 194L-G3576

150 (5-29/32)

95 (3-3/4)

PG16/PG21 22.5/28.5 mm

60 (2-3/8)

115 (4-17/32)

86 (3-3/8)

6

194E-G3663 194E-G3664

180 (7-3/32)

125 (4-59/64)

PG21/PG29 28.5/37.5 mm

On Center

145 (5-23/32)

105 (4-1/8)

3 and 4

194E-G3663 194E-G3664

180 (7-3/32)

125 (4-59/64)

PG21/PG29 28.5/37.5 mm

On Center

145 (5-23/32)

105 (4-1/8)

6

194E-G3665 194E-G3666

230 (9-1/16)

175 (6-57/64)

PG29/PG36 37.5/47.5 mm

155 (6-3/32)

195 (7-43/64)

120 (4-47/64)

3 and 4

194E-G3665 194E-G3666

230 (9-1/16)

175 (6-57/64)

PG29/PG36 37.5/47.5 mm

155 (6-3/32)

195 (7-43/64)

120 (4-47/64)

194E-Y25/32

194E-Y40/63

194E-Y80/100

E

Empty enclosures not available for purchase. ‡ Cat. No. 194E-A16 units have 1 knockout on each end. all others have 2 knockouts on each end. A letter "M" in the catalog number indicates metric knockouts; the unit is otherwise supplied with PG knockouts. § All mounting holes have a 4.2 mm (5/32 in. ) diameter. Cat. No. 194E-A 20/32…

Cat. No. 194E-A 40/63…

Cat. No. 194E-A 80/00…

With 1 extension

No. of Extensions

96 (3-25/32)

107 (4-7/32)

114 (4-31/64)

With 2 extensions

120 (4-23/32)

131 (5-5/32)

138 (5-7/16)

With 3 extensions

144 (5-43/64)

155 (6-7/64)

162 (6-3/8)

With 4♣ extensions

168 (6-39/64)

179 (7-3/64)

186 (7-21/64)

With 5♣ extensions

192 (7-9/16)

203 (8)

210 (8-17/64)

With 6♣ extensions

216 (8-1/2)

227 (8-15/16)

234 (9-7/32)

♣ When more than four modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853).

Dimensions are shown in (millimeters) inches. Dimensions are not intended to be used for manufacturing purposes.

Rockwell Automation Publication 194-TD002B-EN-P

9

Page 10

194E Load Switches

Approximate Dimensions

194E Enclosed Switches with 194R Handles 160.0 (6.30) 139.9 (5.51) 100.1 (3.94)

199.64 (7.86) 50.8 (2.00) 62.48 (2.46)

124.97 89.92 (4.92) 109.98 (3.54) (4.33)

1.02 (0.04)

150.11 (5.91)

87.37 (3.44)

87.37 (3.44)

100.1 (3.94)

49.02 (1.93)

Cat. Nos. 194E-KA-16..63

237.24 (9.34)

240.03 (9.45) 210.06 (8.27)

150.11 119.89 (5.91) (4.72)

50.8 (2.00)

100.07 (3.94)

199.9 (7.87) 180.09 (7.09)

1.02 (0.04)

150.11 (5.91)

4.57 (0.18) 186.94 (7.36)

279.91 (11.02) 299.97 (11.81) 1.02 (0.04)

99.57 (3.92)

55.11 (2.17)

9.91 (0.39)

31.75 (1.25)

Cat. Nos. 194E-KA-16X...63X, 194E-KA-80...00

241.3 (9.50) 222.25 (8.75) 210.31 (8.28) 158.75 (6.25)

210.57 (8.29) 50.8 (2.00)

13.71 (0.54)

167.38 127 (5.00)

107.95 159.51 (6.59) (4.25) (6.28)

107.95 (4.25)

14.22 (0.56) 3.81 (0.15) 36.32 (1.43)

2.28 (0.09) 159.77 (6.29)

16.51 (0.65)

152.4 (6.00) 215.9 (8.50)

Cat. Nos. 194E-AA-16X...63X, 194E-AA-80...00, 194E-FA-16X...63X, 194E-FA-80...00

10

Rockwell Automation Publication 194-TD002B-EN-P

Page 11

Approximate Dimensions

194E Load Switches 249.17 (9.81) 230.12 (9.06) 208.53 (8.21) 162.81 (6.41)

127 101.6 (5.00) (4.00)

209.29 (8.24) 50.8 (2.00)

101.6 (4.00)

180.59 (7.11) 168.40 (6.63)

3.05 (0.12) 13.71 (0.54)

14.22 (0.56)

2.28 (0.09) 158.50 (6.24)

45.97 (1.81)

160.27 (6.31) 223.77 (8.81) 249.17 (9.81)

Cat. Nos. 194E-CA-16X...63X, 194E-CA-80...00

191.62 (7.53) 197.10 (7.76)

172.21 (6.78) 158.49 (6.24) 108.71 (4.28)

50.8 (2.00)

13.71 (0.54)

57.15 115.57 107.95 (2.25) (4.55) (4.25)

76.2 50.8 (3.00) (2.00)

2.28 (0.09)

3.81 (0.15) 10.16 (0.40) 146.30 (5.76)

36.32 (1.43)

16.51 (0.65)

102.36 (4.03) 165.86 (6.53) 191.62 (7.53)

Cat. Nos. 194E-AA-16...63, 194E-FA-16...63

190.5 (7.50) 171.45 (6.75) 157.99 (6.22)

160.53 (6.32) 50.8 (2.00)

107.95 (4.25)

76.2 50.8 (3.00) (2.00)

57.15 (2.25)

124.46 117.60 (4.90) (4.63)

78.99 (3.11)

13.71 (0.54)

95.25 (3.75)

39.62 (1.56)

2.28 (0.09)

3.56 (0.14) 109.73 (4.32)

14.22 (0.56)

101.6 (4.00) 165.1 (6.50) 190.5 (7.50)

Cat. Nos. 194E-CA-16...63

Rockwell Automation Publication 194-TD002B-EN-P

11

Page 12

194E Load Switches

Approximate Dimensions 171.45 (6.75) 157.99 (6.22)

160.53 (6.32)

139.7 (5.50) 107.95 (4.25)

50.8 (2.00)

101.6 127 (4.00) (5.00)

168.13 (6.62)

177.8 (7.00)

3.56 (0.14)

2.28 (0.09)

13.71 (0.54)

47.50 (1.87)

39.62 (1.56)

109.73 (4.32)

14.22 (0.56)

101.6 (4.00) 165.1 (6.50) 190.5 (7.50)

Cat. Nos. 194E-DA-16...63

190.5 (7.50) 171.45 (6.75) 157.99 (6.22)

160.53 (6.32) 50.8 (2.00)

107.95 (4.25)

76.2 50.8 (3.00) (2.00)

57.15 (2.25)

124.46 117.60 (4.90) (4.63)

78.99 (3.11)

13.71 (0.54)

95.25 (3.75)

39.62 (1.56)

14.22 (0.56)

101.6 (4.00) (

12

2.28 (0.09)

3.56 (0.14)

)

Cat. Nos. 194E-GA-16...63

Rockwell Automation Publication 194-TD002B-EN-P

109.73 (4.32)