The text of a spec sheet · part 1 of 2
Control and Load Switch Specifications, Bulletin Number 194E, 194L, pages 1 to 12
Pages 1 to 12 of 26: Control and Load Switch Specifications; Product Overview; 194E Load Switches
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 194L
Page 1
Technical Data
Control and Load Switch Specifications Bulletin Number 194E, 194L Topic
Page
Product Line Overview
2
194E General Specifications
3
194E Approximate Dimensions
5
194L Circuit Diagrams
13
194L General Specifications
17
Approximate Dimensions
20
Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource
Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Page 2
194 Control and Load Switches
Product Type Current Range Main Applications
Functionality
Mounting Styles
Product Overview
Bulletin 194E
Bulletin 194L
Inductive load-rated load switch
Inductive load-rated control/load switch
16…100 A
12…40 A
UL, CSA ratings "suitable as at-motor disconnect"
UL, CSA ratings "suitable as at-motor disconnect"
3- or 6-pole switch configurations for OFF-ON or changeover applications (16…100 A switches)
1- to 6-pole multifunction switch control configurations for OFF-ON, changeover, Star-Delta (Wye-Delta), reversing, ammeter, voltmeter, and step switch applications Also available in custom control configurations up to 16 circuits for any unique control switching application.
Front/door or base/DIN Rail mounting
Front/door or base/DIN Rail mounting
Handles
Handle colors in grey/black and red/yellow and padlockable versions Legend plates available in 0-I international markings and text styles
Uniformly styled handles: selector knob, disk style, rectangular style, and key-operated versions (Type 1/12, IP66) Handle colors in grey/black and red/yellow and padlockable versions Legend plates available in 0-I international markings and text styles
Open Switch or Enclosed
Open switch (large frame Bul. 194E, open style only) Enclosed: IP66 thermoplastic enclosure or UL/CSA rated enclosure
UL/CSA Electrical Ratings: Rated Voltage Ue
Open switch
600V AC
600V AC
16…100 A @ 600V
12…40 A @ 600V
Rated Power Pe [FLA]
Varies w/ 1- or 3-phase switch, voltage
Varies w/ 1- or 3-phase switch, voltage
Short-Circuit Ratings
5 kA
5 kA
Switching Rate [ops/h]
120
120
Rated Current Ie
Mechanical Life [ops]
1 million
0.2 million (16…100 A switches)
IEC Rated Current Ie AC-1
16…100 A @ 600V
12…40 A @ 600V
AC-21A
16…100 A @ 600V
12…40 A @ 600V
AC-22A
16…100 A @ 600V
12…40 A @ 600V
-25…+60 °C (-13…+140 °F)
-25…+60 °C (-13…+140 °F)
Ambient Operational Temp. Ambient Enclosed Temp.
-20…+60 °C (-4…+140 °F)
-20…+60 °C (-4…+140 °F)
Ambient Storage Temp.
-40…+80 °C (-40…+176 °F)
-40…+80 °C (-40…+176 °F)
Protection class per IEC 529
Switch bodies: IP2
Switch bodies: IP2
Optional Accessories
IP66 handles Multi-length shafts and shaft extension kits Terminal covers
Multi-length shafts and shaft extension kits Terminal covers
Standards/Certifications
UL 508 CSA C22.2, No. 14 IEC 60947-3 Low Voltage Switchgear and Controlgear part 3 CE
UL 508 CSA C22.2, No. 14 IEC 60947-3 Low Voltage Switchgear and Controlgear part 3 CE
2
Rockwell Automation Publication 194-TD002B-EN-P
Page 3
Specifications
194E Load Switches
Electrical Ratings Performance Data
16 A
25 A
32 A
40 A
63 A
80 A
100 A
IEC Applications
Aux. Contacts
Rated operational voltage (Ue):
[V]
690
690
690
690
690
690
690
690
Rated operational voltage (Ue): UL, CSA
[V]
600
600
600
600
600
600
600
600
Rated isolation voltage (Ui): IEC/UL, CSA
[V]
Rated impulse voltage (Uimp): UL, CSA
[kV]
8
8
8
8
8
8
8
8
Test voltage, (Ui) 1 minute
[kV]
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
690/600 690/600 690/600 690/600 690/600 690/600 690/600
690/600
Lost power per pole
[W]
0.58
1.0
1.5
1.6
2.4
3.6
5.5
0.4
Rated frequency
[Hz]
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
Conventional free air thermal current
[A]
25
40
50
63
75
100
120
12
Conventional enclosed thermal current
[A]
20
32
40
50
63
80
100
10
[A]
16
25
32
40
63
80
100
10
230V
[kW]
5.5
7.5
7.5
15
18.5
22
30, 400V
[kW]
7.5
11
15
22
30
37
55, 690V
[kW]
7.5
11
15
18.5
22
37
45, 230V
[kW]
4
5.5
7.5
11
15
18.5
22, 400V
[kW]
5.5
7.5
11
15
18.5
30
37, 690V
[kW]
5.5
7.5
11
15
18.5
30
22, [kA]
20
20
15
20
15
30
25, Rated current AC-1/
Non-inductive or only slightly inductive loads
AC-21A
Switching of resistive loads with slight overload
Rated power Pe AC-23A
AC-3
Occasional switching of 3Ø motors and other highly inductive loads (criterion for selecting main switches) Squirrel-cage motors; starting and stopping of running motors
Short circuit current (co-ordination type 2) Rated conditional short-circuit current Maximum fuse rating of circuit (type g,G) Rated short-time current Icw (1 s) Rated breaking capacity AC23A (cosφ 0.45)
[A]
20
25
35
50
63
80
100, [A]
800
900
900
1300
1300
2500
2500, 230V
[A]
156
296
296
484
484
780
780, 400V
[A]
120
256
256
504
504
800
800, 690V
[A]
70
136
136
196
196
376
376, 24/48V
400/415V
DC switching capacity
Rated current Ie
DC-21A
For resistive loads, T ≤ 1 ms Ue max = 660V
[A]
20
25
32
40
63
80
100
1 pole 110V
[A]
5
5
6
8
10
16
20
220V
[A]
1
1
1
1.5
15
3
3
440V
[A]
0.5
0.5
0.5
0.6
0.6
0.7
0.7
96V
[A]
20
25
32
40
63
80
100
2 poles 110V in 220V series 440V
[A]
20
23
25
32
50
70
80
[A]
5
5
6
8
10
16
20
[A]
1
1
1
1.5
1.5
3
3
600V
[A]
0.6
0.6
0.6
0.8
0.8
1
1
110V
[A]
20
25
32
40
63
80
100
3 poles 220V in series 440V 600V
[A]
13
13
15
20
28
50
63
[A]
2.2
2.2
2.2
3.6
3.6
6.5
6.5
[A]
1.3
1.5
1.5
2
2
3
3
1
1.3
1.5
2.9
4.1
5.1
7.2, - - Rated power Pe DC-23A, DC-3, DC-5 For inductive loads, T ≤ 15 ms
90V
[kW]
3 poles 110V in series 220V
[kW]
1
1.1
1.3
2.2
3.3
5.5
7
[kW]
0.8
0.9
1.1
1.7
2
3.5
4.4
440V
[kW]
0.6
0.6
0.6
0.9
0.9
1.1
1.1
600V
[kW]
0.4
0.4
0.4
0.5
0.5
0.9
0.9, See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-NonFused-Disconnect-Switches#specifications
Rockwell Automation Publication 194-TD002B-EN-P
3
Page 4
194E Load Switches
Specifications
Electrical Ratings, Continued Performance Data
16 A
25 A
32 A
40 A
63 A
80 A
100 A
UL/CSA Applications Continuous current Heavy Pilot Duty
[A]
16
25
32
40
63
80
100, [AC]
A600
A600
A600, - - - A600 Q600
Standard Duty
[DC], - - - - - - Motor rating 60 Hz
[FLA]
16
16
16
24
34
56
80
120V, 1P 240V, 1P
Single-phase (2 poles)
480V, 1P 600V, 1P 120V, 3P 240V, 3P
Three-phase 480V, 3P 600V, 3P
Aux. Contacts
[Hp]
1
1
1
2
3
5
7.5
[FLA]
12
12
17
17
28
50
68
[Hp]
2
2
3
3
5
10
15
[FLA]
8.5
8.5
14
21
26
34
68
[Hp]
3
3
5
7.5
10
15
30
[FLA]
11.2
11.2
11.2
16
20
27
44
[Hp]
5
5
5
7.5
10
15
25
[FLA]
13.6
13.6
19.2
30.4
40
56
84
[Hp]
2
2
3
5
7.5
10
15
[FLA]
9.6
15.2
22
28
42
68
80
[Hp]
3
5
7.5
10
15
25
30
[FLA]
11
14
21
27
34
52
65
[Hp]
7.5
10
15
20
25
40
50
[FLA]
11
11
17
22
27
52
52
[Hp]
10
10
15
20
25
50
50, - Mechanical Data 16 A
25…32 A
40…63 A
80…100 A
Aux. Contacts handles
IP66
IP66
IP66
IP66
IP66 switch bodies
IP20
IP20
IP20
IP20
IP20
0.2
0.2
0.2
0.2
0.2
Performance Data Protection class according to IEC 529 Motor rating 60 Hz
Mechanical life
[million operations]
Max wire gauges Terminal size per IEC 947-1
A4
A6
A7
A9
2xA2 rigid wire
[AWG] [mm2]
16…10 1…10
14…8 1.5…16
12…4 2.5…25
10…1 4…50
18…14 0.75…2.5 fine strands
[AWG] [mm2]
16…8 1.5…6
14…8 1.5…10
12…4 2.5…16
10…1 4…35
18…14 0.5…2.5
[N•m]/[lb•in]
1.4/12.2
1.4/12.2
2.8/24.5
5.6/50
1/8.8
Tightening torque
Environmental Data
4
Storage
-40…+80 °C (-40…+176 °F)
Operation
-25…+60 °C (-13…+140 °F)
Rockwell Automation Publication 194-TD002B-EN-P
Page 5
Approximate Dimensions
194E Load Switches
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Front Installation Cat. No. 194E-E…
1 (3/64)…5 (13/64)
Dia. 3.3 (1/8)
9.5 (3/8) 6-Pole 3-Pole Handles Cat. No.
P
Q
194L-HE4A
28 (1-7/64)
48 x 48 (1-57/64 x 1-57/64) 48 x 48 (1-57/64 x 1-57/64)
194L-HE4I
28 (1-7/64)
194E-HE4N
34 (1-11/32)
54 x 54 (2-1/8 x 2-1/8)
194E-HE4G
34 (1-11/32)
54 x 54 (2-1/8 x 2-1/8)
194L-HE6A
28 (1-7/64)
64 x 64 (2-33/64 x 3-5/64)
194L-HE6I
28 (1-7/64)
64 x 64 (2-33/64 x 3-5/64)
194L-HE6N
34 (1-11/32)
67 x 67 (2-41/64 x 2-41/64)
194L-HE6G
34 (1-11/32)
67 x 67 (2-41/64 x 2-41/64)
Switch Body Use with Cat. No.
B2
F
H
L‡
G
194E-E16
28 (1-7/64)
N/A
36 (1-37/64)
63 (2-31/64)
51 (2)
90 (3-35/64)
194E-E25/32
36 (1-27/64)
N/A
45 (1-25/32)
64 (2-33/64)
60 (2-3/8)
90 (3-1/2)
194E-E40/63
48 (1-57/64)
36 (1-27/64)
54 (2-1/8)
72 (2-27/32)
74 (2-29/32)
108 (4-1/4)
194E-E80/100
48 (1-57/64)
36 (1-27/64)
72 (2-27/32)
90 (3-35/64)
90 (3-35/64)
144 (5-11/16)
Does not apply to 194E-40/63A, 6-Pole Switches. Use B2 dimensions for 6-pole devices. ‡ For 6-pole switches, add 1 in. to the "L" dimension.
Cat. No. 194E-E Switch Body with Cat. No. 194L-HC4A Handle for 22.5 mm Hole Mounting Style
Type
L
194E-E16
76 (3)
194E-E25/32
84.5 (3-21/64)
194E-E40/63
98.5 (3-7/8)
194E-E80/100
114.5 (4-33/64)
Rockwell Automation Publication 194-TD002B-EN-P
5
Page 6
194E Load Switches
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Mounting Cat. No. 194E-A…
6-Pole 3-Pole
Handles Cat. No.
P
Q
194L-HE4A
28 (1-7/64)
48 x 48 (1-57/64 x 1-57/64)
194L-HE4I
28 (1-7/64)
48 x 48 (1-57/64 x 1-57/64)
194L-HE4S
28 (1-7/64)
48 x 62 (1-57/64 x 2-7/16)
194E-HE4N
34 (1-11/32)
54 x 54 (2-1/8 x 21/8)
194E-HE4G
34 (1-11/32)
54 x 54 (2-1/8 x 21/8)
194L-HE6A
28 (1-7/64)
64 x 64 (2-33/64 x 3-5/64)
194L-HE6I
28 (1-7/64)
64 x 64 (2-33/64 x 3-5/64)
194L-HE6S
28 (1-7/64)
64 x 78 (2-33/64 x 3-5/64)
194L-HE6N
34 (1-11/32)
67 x 67 (2-41/64 x 2-41/64)
194L-HE6G
34 (1-11/32)
67 x 67 (2-41/64 x 2-41/64) Cover Requirements
For Use With
Y min.
X≥
Y max.
X≥
194E-A16
5 (13/64)
142 (5-19/32)
9.5 (3/8)
90 (3-35/64)
194E-A25/32
5 (13/64)
142 (5-19/32)
9.5 (3/8)
90 (3-35/64)
194E-A40/63
2.5 (7/64)
150 (5-29/32)
9.5 (3/8)
90 (3-35/64)
194E-A80/100
2.5 (7/64)
150 (5-29/32)
9.5 (3/8)
90 (3-35/64)
Switch Body Use With Cat. No.
D3
E
F1
F2
G
H
L‡
J
194E-A16
4.5 (3/16)
70 (2-49/64)
12.5 (31/64)
23.5 (59/64)
90 (3-35/64)
63 (2-31/64)
80 (3-5/32)
36 (1-27/64)
194E-A25/32
4.5 (3/16)
70 (2-49/64)
30 (1-3/16)
15 (19/32)
90 (3-1/2)
64 (2-33/64)
59 (2-5/16)
45 (1-25/32)
194E-A40/63
4.5 (3/16)
80 (3-5/32)
37 (1-15/32)
17 (43/64)
108 (4-1/4)
72 (2-27/32)
73 (2-55/64)
54 (2-1/8)
194E-A80/100
5.6 (7/32)
95 (3-3/4)
48.5 (1-29/32)
23.5 (59/64)
144 (5-11/16)
90 (3-35/64)
89 (3-1/2)
72 (2-27/32)
‡ For 6-pole switches, add 1 in. to the "L" dimension.
6
Rockwell Automation Publication 194-TD002B-EN-P
Page 7
Approximate Dimensions
194E Load Switches
Base Mounting Cat. No. 194E-A… Cat. No. 194E-A… Switch Body with Cat. No. 194L-G2853 Shaft Extension Shaft extensions
Switch body
Switch Body Cat. No.
194E-A 16
194E-A 25/32
194E-A 40/63
194E-A 80/100
With 1 shaft extension
79 (3-7/64)
88 (3-15/32)
102 (4-1/32)
118 (4-21/32)
With 2 shaft extensions
103 (4-37/64)
112 (4-27/64)
126 (4-31/32)
142 (5-19/32)
With 3 shaft extensions
127 (5)
136 (5-23/64)
150 (5-29/32)
166 (6-35/64)
With 4 shaft extensions
151 (6-61/64)
160 (6-5/16)
174 (6-55/64)
190 (7-31/64)
With 5 shaft extensions
175 (7-57/64)
184 (7-1/4)
198 (7-51/64)
214 (8-7/16)
With 6 shaft extensions
199 (8-27/32)
208 (8-13/64)
222 (8-3/4)
238 (9-3/8)
For 6-pole switches, add 1 in. to the "L" dimension. Shaft
Y
194L-G2830
2.5…9.5 (7/64…3/8)
Type
B
Q
P
194L-G3194
9…18 (23/64…23/32)
194L-HE4A
36 (1-27/64)
48 x 48 (1-57/64 x 1-57/64)
28 (1-7/64)
194L-G3195
14…23 (9/16)…(29/32)
194L-HE4I
36 (1-27/64)
48 x 48 (1-57/64 x 1-57/64)
28 (1-7/64)
194E-HE4G
28 (1-7/64)
54 x 54 (2-1/8 x 2-1/8)
34 (1-11/32)
194E-HE4N
28 (1-7/64)
54 x 54 (2-1/8 x 2-1/8)
34 (1-11/32)
194L-HE6A
48 (1-57/64)
64 x 64 (2-33/64 x 2-33/64)
28 (1-7/64)
194L-HE6I
48 (1-57/64)
64 x 64 (2-33/64 x 2-33/64)
28 (1-7/64)
194L-HE6N
48 (1-57/64)
67 x 67 (2-41/64 x 2-41/64)
34 (1-11/32)
194L-HE6G
48 (1-57/64)
67 x 67 (2-41/64 x 2-41/64)
34 (1-11/32)
Handles
Rockwell Automation Publication 194-TD002B-EN-P
7
Page 8
194E Load Switches
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Installation Cat. No. 194E-A… Cat. No. 194E-A Switch Body with Metal Shaft Extension
Cat. No.
A
Cat. No.
194L-G3393
110…235 (4-11/32…9-1/4)
194E-A16
51 (2)
194L-G3394
230…350 (9-1/16…13-25/32)
194E-A25/32
60 (2-3/8)
194E-A40/63
74 (2-59/64)
194E-A80/100
90 (3-35/64)
For 6-pole switches, add 1 in. to the "L" dimension.
Base and Front Installation Cat. No. 194E… with Auxiliary Contact Block Installed
Contacts
M
1 N.O. + 1 N.C.
9 (23/64)
2 N.O. + 2 N.C.
18 (23/32)
Cat. No. 194E… with 4-Pole, Ground and Neutral Terminals
8
Cat. No.
M
194E-16
12.5 (31/64)
194E-25/32
14 (9/16)
194E-40/63
17.5 (11/16)
194E-80/100
22 (7/8)
Rockwell Automation Publication 194-TD002B-EN-P
Page 9
Approximate Dimensions
194E Load Switches
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Base Mounting Cat. No. 194E-A… Thermoplastic Enclosures
Complete Switches
Enclosures ABS
Cat. No.
Poles 3 and 4
Mounting Holes§
Noryl Cat. No.
Height A
Width B
Knockouts‡ ØD1
120 (4-23/32)
70 (2-3/4)
M16/M20 16/20 mm M25/M30 25/30 mm
194E-Y16
F
Depth H
PG11/PG16 18.5/22.5 mm
50 (1-31/32)
105 (4-9/64)
70 (2-49/65)
PG21/PG29 28.5/37.5 mm
On Center
145 (5-23/32)
105 (4-1/8)
6
194E-G3663 194E-G3664
180 (7-3/32)
125 (4-59/64)
3 and 4
194L-G3572 194L-G3576
150 (5-29/32)
95 (3-3/4)
PG16/PG21 22.5/28.5 mm
60 (2-3/8)
115 (4-17/32)
86 (3-3/8)
6
194E-G3663 194E-G3664
180 (7-3/32)
125 (4-59/64)
PG21/PG29 28.5/37.5 mm
On Center
145 (5-23/32)
105 (4-1/8)
3 and 4
194E-G3663 194E-G3664
180 (7-3/32)
125 (4-59/64)
PG21/PG29 28.5/37.5 mm
On Center
145 (5-23/32)
105 (4-1/8)
6
194E-G3665 194E-G3666
230 (9-1/16)
175 (6-57/64)
PG29/PG36 37.5/47.5 mm
155 (6-3/32)
195 (7-43/64)
120 (4-47/64)
3 and 4
194E-G3665 194E-G3666
230 (9-1/16)
175 (6-57/64)
PG29/PG36 37.5/47.5 mm
155 (6-3/32)
195 (7-43/64)
120 (4-47/64)
194E-Y25/32
194E-Y40/63
194E-Y80/100
E
Empty enclosures not available for purchase. ‡ Cat. No. 194E-A16 units have 1 knockout on each end. all others have 2 knockouts on each end. A letter "M" in the catalog number indicates metric knockouts; the unit is otherwise supplied with PG knockouts. § All mounting holes have a 4.2 mm (5/32 in. ) diameter. Cat. No. 194E-A 20/32…
Cat. No. 194E-A 40/63…
Cat. No. 194E-A 80/00…
With 1 extension
No. of Extensions
96 (3-25/32)
107 (4-7/32)
114 (4-31/64)
With 2 extensions
120 (4-23/32)
131 (5-5/32)
138 (5-7/16)
With 3 extensions
144 (5-43/64)
155 (6-7/64)
162 (6-3/8)
With 4♣ extensions
168 (6-39/64)
179 (7-3/64)
186 (7-21/64)
With 5♣ extensions
192 (7-9/16)
203 (8)
210 (8-17/64)
With 6♣ extensions
216 (8-1/2)
227 (8-15/16)
234 (9-7/32)
♣ When more than four modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853).
Dimensions are shown in (millimeters) inches. Dimensions are not intended to be used for manufacturing purposes.
Rockwell Automation Publication 194-TD002B-EN-P
9
Page 10
194E Load Switches
Approximate Dimensions
194E Enclosed Switches with 194R Handles 160.0 (6.30) 139.9 (5.51) 100.1 (3.94)
199.64 (7.86) 50.8 (2.00) 62.48 (2.46)
124.97 89.92 (4.92) 109.98 (3.54) (4.33)
1.02 (0.04)
150.11 (5.91)
87.37 (3.44)
87.37 (3.44)
100.1 (3.94)
49.02 (1.93)
Cat. Nos. 194E-KA-16..63
237.24 (9.34)
240.03 (9.45) 210.06 (8.27)
150.11 119.89 (5.91) (4.72)
50.8 (2.00)
100.07 (3.94)
199.9 (7.87) 180.09 (7.09)
1.02 (0.04)
150.11 (5.91)
4.57 (0.18) 186.94 (7.36)
279.91 (11.02) 299.97 (11.81) 1.02 (0.04)
99.57 (3.92)
55.11 (2.17)
9.91 (0.39)
31.75 (1.25)
Cat. Nos. 194E-KA-16X...63X, 194E-KA-80...00
241.3 (9.50) 222.25 (8.75) 210.31 (8.28) 158.75 (6.25)
210.57 (8.29) 50.8 (2.00)
13.71 (0.54)
167.38 127 (5.00)
107.95 159.51 (6.59) (4.25) (6.28)
107.95 (4.25)
14.22 (0.56) 3.81 (0.15) 36.32 (1.43)
2.28 (0.09) 159.77 (6.29)
16.51 (0.65)
152.4 (6.00) 215.9 (8.50)
Cat. Nos. 194E-AA-16X...63X, 194E-AA-80...00, 194E-FA-16X...63X, 194E-FA-80...00
10
Rockwell Automation Publication 194-TD002B-EN-P
Page 11
Approximate Dimensions
194E Load Switches 249.17 (9.81) 230.12 (9.06) 208.53 (8.21) 162.81 (6.41)
127 101.6 (5.00) (4.00)
209.29 (8.24) 50.8 (2.00)
101.6 (4.00)
180.59 (7.11) 168.40 (6.63)
3.05 (0.12) 13.71 (0.54)
14.22 (0.56)
2.28 (0.09) 158.50 (6.24)
45.97 (1.81)
160.27 (6.31) 223.77 (8.81) 249.17 (9.81)
Cat. Nos. 194E-CA-16X...63X, 194E-CA-80...00
191.62 (7.53) 197.10 (7.76)
172.21 (6.78) 158.49 (6.24) 108.71 (4.28)
50.8 (2.00)
13.71 (0.54)
57.15 115.57 107.95 (2.25) (4.55) (4.25)
76.2 50.8 (3.00) (2.00)
2.28 (0.09)
3.81 (0.15) 10.16 (0.40) 146.30 (5.76)
36.32 (1.43)
16.51 (0.65)
102.36 (4.03) 165.86 (6.53) 191.62 (7.53)
Cat. Nos. 194E-AA-16...63, 194E-FA-16...63
190.5 (7.50) 171.45 (6.75) 157.99 (6.22)
160.53 (6.32) 50.8 (2.00)
107.95 (4.25)
76.2 50.8 (3.00) (2.00)
57.15 (2.25)
124.46 117.60 (4.90) (4.63)
78.99 (3.11)
13.71 (0.54)
95.25 (3.75)
39.62 (1.56)
2.28 (0.09)
3.56 (0.14) 109.73 (4.32)
14.22 (0.56)
101.6 (4.00) 165.1 (6.50) 190.5 (7.50)
Cat. Nos. 194E-CA-16...63
Rockwell Automation Publication 194-TD002B-EN-P
11
Page 12
194E Load Switches
Approximate Dimensions 171.45 (6.75) 157.99 (6.22)
160.53 (6.32)
139.7 (5.50) 107.95 (4.25)
50.8 (2.00)
101.6 127 (4.00) (5.00)
168.13 (6.62)
177.8 (7.00)
3.56 (0.14)
2.28 (0.09)
13.71 (0.54)
47.50 (1.87)
39.62 (1.56)
109.73 (4.32)
14.22 (0.56)
101.6 (4.00) 165.1 (6.50) 190.5 (7.50)
Cat. Nos. 194E-DA-16...63
190.5 (7.50) 171.45 (6.75) 157.99 (6.22)
160.53 (6.32) 50.8 (2.00)
107.95 (4.25)
76.2 50.8 (3.00) (2.00)
57.15 (2.25)
124.46 117.60 (4.90) (4.63)
78.99 (3.11)
13.71 (0.54)
95.25 (3.75)
39.62 (1.56)
14.22 (0.56)
101.6 (4.00) (
12
2.28 (0.09)
3.56 (0.14)
)
Cat. Nos. 194E-GA-16...63
Rockwell Automation Publication 194-TD002B-EN-P
109.73 (4.32)