The text of a spec sheet · part 2 of 2

Control and Load Switch Specifications, Bulletin Number 194E, 194L, pages 13 to 26

Pages 13 to 26 of 26: 194L Control and Load Switches; Back Cover

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 194L

Page 13

Specifications

194L Control and Load Switches

Switching Diagrams Contact target tables: X = Contact Closed [Blank] = Contact Open

Circuit Diagram Nos. 1501…4253

Rockwell Automation Publication 194-TD002B-EN-P

13

Page 14

194L Control and Load Switches

Specifications

Circuit Diagram Nos. 4271…5531

14

Rockwell Automation Publication 194-TD002B-EN-P

Page 15

Specifications

194L Control and Load Switches

Circuit Diagram Nos. 5012…5272

Rockwell Automation Publication 194-TD002B-EN-P

15

Page 16

194L Control and Load Switches

Specifications

Circuit Diagram Nos. 5273…8771

16

Rockwell Automation Publication 194-TD002B-EN-P

Page 17

Specifications

194L Control and Load Switches

Electrical Ratings Performance Data IEC Applications Rated voltage Ue

IEC-947

[V]

12 A

16 A

20 A

25 A

32 A

40 A

690

690

690

690

690

690

Isolating conditions acc. to VDE fulfilled up to rated impulse voltage Uimp

[kV]

6

6

6

6

8

8

Thermal rated current

40 °C IEC-947

[A]

16

20

25

30

32

45

Thermal rated current Ithe

60 °C IEC-947

[A]

12

16

20

25

32

45

Rated current Non-inductive or slightly inductive loads/ switching of resistive loads with slight overload Non-inductive or slightly AC-1 inductive loads Switching of mixed resistive AC22A and inductive loads with slight overload Switching of inductive drives, AC-15 motors, valves, and electromagnets. DC switching capacity Rated current Ie

AC-1/ AC-21A

Rated Voltage [V]

DC-21A

For resistive loads, T ≤ 1ms Ue max = 600V

IEC-947

690V

[A]

12

16

20

25

32

40

SEV

660V

[A]

12

16

20

25

32

40

IEC-947

220…500V 690V

[A] [A]

12 12

16 16

20 20

25 25

32 32

40 40

IEC-947

220…240V 380…415V 500V

[A] [A] [A]

5 3 2

6 4 2.5

7 5 3

8 6 4, - Contacts in series 1 24 48 60 110 220

2 48 96 120 220 440

3 72 144 180 330 660

4 96 192 240 440, 5 120 240 300 550, 6 144 288 360 660, 8 192 384 450, - [A] [A] [A] [A] [A]

12 10 8 2 0.5

16 12 10 2.5 0.6

20 16 12 4 0.7

22 18 14 5 0.8, - 32, - - - 40, - 440, - - - - - [A]

0.4

0.4

0.5

0.5, - 25.2 50.4

50.4 75.6 100.8 126 100.8 151.2 201.6 252

151.2 201.6 302.4 403.2

[A] [A]

18 15

24 21

30 24

33 27, - - - 63

126

60

Rated making/breaking capacity (= 1.5 x Ie) 1.05 x Rated voltage [V] For resistive loads, T Ith 1ms

378

504

[A]

12

18

18

21

48

115.5 231

346.5 462

577.5, - [A]

3

4.5

6

7.5, - 231

462, - - - - [A] 0.75

1.12

1.05

1.2, - 462, - - - - - [A] 0.52

0.78

0.47

0.75, - 24 30 48 60 110 220

48 60 96 120 220, 72 90 144 180 330, 96 120 192 240 440, 120 150 240 300 550, 144 180 288 360 660, 192 240 384 450, - [A] [A] [A] [A] [A] [A]

8 4.5 1.5 1 0.4, 10 5.5 2 1.2 0.5, 12 7 2.5 1.5 0.6, 14 8 3 1.8 0.7, 16, 8 4.8 2 0.6

16, 8 4.8 2 0.6

1.1 x Rated voltage [V]

26.4 33

52.8 66

79.2 99

105.6 132 132 165

158.4 184.8 198 231

[A] 8.8 [A] 4.95

11 6.05

13.2 7.7

1.54 8.8, - For inductive loads T = 50 ms

52.8

105.6 158.4 211.2 264

316.8 369.6

[A] 1.65

2.2

2.75

3.3

8.8

17.6, 8.8

Ue max = 600V

66

132

198

264

330

396

462

[A]

1.1

1.32

1.65

1.98

5.28

121

242

363

484

605, - [A] 4.95 [W] 0.3

6.05 0.5

7.7 0.6

8.8 0.9

2.2 0.8

2.2 1.4

[kW] [kW] [kW] [kW] [kW] [kW] [kW] [kW] [kW] [kW]

0.15 0.25 0.30 0.37 0.30 0.50 0.75 1.20 0.50 1.20

0.20 0.30 0.37 0.50 0.37 0.75 1.00 1.40 0.75 1.40

0.25 0.37 0.50 0.75 0.50 1.00 1.20 1.60 1.00 1.50

0.30, 0.50, 1.00, - - - - 0.30, 0.50, 1.00, - - - - Ue max = 600V

189

252

315

Rated current Ie Rated voltage [V] For inductive loads T = 50 ms Rated voltage [V]

Rated making/breaking capacity (= 1.1 x Ie)

Power Lost Rated power Pe

Rated voltage [V] DC-23A, DC-3, DC-5 For inductive loads, T ≤1 ms

5.28

Contacts in series 24 24 48 48 60 60 110 110 220 220

1 2 2 3 2 4 4 6 4 6

0.12 0.20 0.25 0.30 0.25 0.37 0.50 1.00 0.37 1.00 standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-NonFused-Disconnect-Switches#specifications

Rockwell Automation Publication 194-TD002B-EN-P

17

Page 18

194L Control and Load Switches

Specifications

Performance Data, Continued

12 A

16 A

20 A

25 A

32 A

40 A

IEC Applications, Continued Rated making/breaking capacity (= 4 x Ie) DC-23A, DC-3, DC-5 For inductive loads, T ≤ 7.5 ms

Contacts in series

Rated Voltage [V] 25.2 25.2 50.4 50.4 63 63 115.5 115.5 231 231

1 2 2 3 2 4 4 6 4 6

[A] [A] [A] [A] [A] [A] [A] [A] [A] [A]

20.0 33.3 21.0 25.0 16.6 24.6 18.1 36.4 6.7 18.1

25.0 41.6 25.0 30.8 20.0 33.3 27.2 43.6 9.1 21.8

33.3 50.0 30.8 42.0 24.6 50.0 36.4 51.0 13.6 25.2

41.6 61.6 41.6 62.4 33.2 66.4 44.0 58.2 18.2 27.2

50.0, 41.6, 66.6, - - - - 50.0, 41.6, 66.6, - - - - at 220V 0.45 [cos j] at 380V 0.45 [cos j] at 660V 0.45[cos j]

[A]

72

96

128

176

296

296

[A]

72

96

128

176

280

336

[A]

53

72

86

112

196

196

240V 380V 415V 440V 500V 660V

[kW] [kW] [kW] [kW] [kW] [kW]

3 5.5 5.5 5.5 7.5 7.5

4 7.5 7.5 7.5 10 10

5.5 9 9 9 11 11

5.5 13 13 13 15 15, - - - - - - - - - - - 220…240V 380…440V 500V 660V

[kW] [kW] [kW] [kW]

2.2 4 5.5 5.5

3 5.5 7.5 7.5

4.5 7.5 10 8

5.5 11 13 11

7.5 15, 18.5

7.5 18.5, 18.5

110V 220…240V 380…440V

[kW] [kW] [kW]

0.75 1.3 2.2

1.1 2.2 3.7

1.2 2.5 4.5

1.6 3.2 5.5, 4 8, 4 16

3-phase 3-pole

220…240V 380…415V 440…550V

[kW] [kW] [kW]

0.75 1.5 1.5

1.5 2.2 2.2

3 3.7 3.7

4 5.5 5.5

5.5 7.5 7.5

5.5 7.5 11

1-phase 2-pole

110V 240V 380V 440V

[kW] [kW] [kW] [kW]

0.18 0.37 0.75 0.75

0.37 0.75 1.1 1.1

0.55 1.5 1.8 1.8

0.75 2.2 3 3, - - - - - - - Rated breaking capacity

Rated power

AC-2

IEC-947

Slip-ring motors: starting, reversing and electric braking; star/delta starting

3-phase 3-pole

IEC-947

AC-3

3-phase Squirrel-cage motors: starting and stopping 3-pole of running motors 1-phase 2-pole IEC-947

AC-4

Squirrel-cage motors: starting, reversing, electric braking, inching standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-NonFused-Disconnect-Switches#specifications

18

Rockwell Automation Publication 194-TD002B-EN-P

Page 19

Specifications

194L Control and Load Switches

Performance Data, Continued

12 A

16 A

20 A

25 A

32 A

40 A

IEC Applications, Continued

AC-23A

Occasional switching of motors and other highly inductive loads (criterion for selecting main switches)

IEC-947 3-phase 3-pole

220…240V 380…440V 500V 660V

[kW] [kW] [kW] [kW]

2.2 4 5.5 5.5

3 5.5 7.5 7.5

4.5 7.5 10 8

5.5 11 13 11

11 18.5, 22

11 22, 22

1-phase 2-pole

110V 220…240V 380…440V

[kW] [kW] [kW]

0.75 1.3 2.2

1.1 2.2 3.7

1.2 2.5 4.5

1.6 3.2 5.5, 5.5 11, 5.5 11

[kArms] [A]

0.48

0.48

0.6

0.75

0.8 35

0.8 40

[kA]

6

6

5

5

5

5

[ops/h]

120

120

120

120

120

120

Short-circuit ratings Rated short-time current (1s) Strongest series fuse, not in (gL characteristic) enclosure Conditional rated shortcircuit Switch Rate electrical

CSA and UL Applications Rated Voltage Ue Ampere Rating Rated power Pe§

600

600

600

600

600

600

[A]

A600 12

A600 16, 20, 25, 32, 40

(FLA)

(FLA)

(FLA)

(FLA)

3-phase 3-pole

120V 240V 480V 600V

[Hp] [Hp] [Hp] [Hp]

1 (7.2) 2 (6.8) 5 (7.6) 5 (6.1)

1.5 (12) 3 (9.6) 7.5 (11) 7.5 (9)

2 (13.6) 4 (12.4) 8 (11.6) 10 (11)

3 (19.2) 6 (18) 12 (17) 15 (17)

5 (30.4) 7.5 (22) 20 (27) 20 (22)

5 (30.4) 10 (28) 25 (34) 25 (27)

1-phase 2-pole

120V 240V 480V 600V

[Hp] 0.5 (9.8) .75 (13.8) [Hp] 1 (8.0) 1.5 (10.0) [Hp] 2 (6.0) 3 (8.5) [Hp] 3 (6.8) 3 (6.8)

1 (16) 2 (12) 4 (11.2) 5 (11.2)

1.5 (20) 3 (17) 6 (17) 7.5 (16)

2 (24) 5 (28) 7.5 (21) 10 (20)

2 (24) 5 (28) 10 (26) 15 (27)

120V 240V

[Hp] [Hp] [A], - 35, - 55, - 60, - 80

[kA]

5

5

5

5

120

120

UL (CSA)

Standard motor DOL rating (similar to AC-3)

Heavy motor load, reversing Rating (similar to AC-4) Max. back-up fuse Short Circuit Ratings

[V AC] Pilot Duty Contact class General Use Non-inductive or slightly inductive load‡

3-phase 3-pole (gG characteristic)

Maximum Short Circuit Prospective Fault Current Maximum Fuse Size

Switching Rate electrical

[A]

35

55

60

80

[ops/h]

120

120

120

120

Mechanical Data Performance Data Protection class acc. to IEC 529

Handles Switch Bodies

Mechanical Endurance Switching rate mechanical

12/16 A

20/25 A

32/40 A

IP66 IP20

IP66 IP20

IP66 IP20

[mil.ops]

1

1

1

[ops/h]

1200

1200

1200

AWG [mm2] AWG [mm2]

(2)18…12 (2)1…2.5 (2)18…12 (2)1…2.5

(2)16…10 (2)1.5…6 (2)16…10 (2)1.5…4

(2)12…8 (2)4…10 (2)14…10 (2)2.5…6

Maximum Wire Gauges rigid wire fine strands

Environmental Data Performance Data

12/16/20/25 A

32/40 A

Operation

-25…+60 °C (-13…+140 °F)

-25…+60 °C (-13…+140 °F)

Storage

-40…+80 °C (-40…+176 °F)

-40…+80 °C (-40…+176 °F)

Ambient temperature

Does not apply to switches in enclosure. ‡ Suitable for switching off-load (AC-20) above 660V, but only up to 660V for switches with screws at the rear. § See standards compliance listed on http://ab.rockwellautomation.com/Circuit-and-Load-Protection/Disconnect-Switches/Non-Visible-Blade/194R-Fused-NonFused-Disconnect-Switches#specifications

Rockwell Automation Publication 194-TD002B-EN-P

19

Page 20

194L Control and Load Switches

Approximate Dimensions

Approximate Dimensions Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Cat. No. 194L-C… for Central Fixing (194L-HC…) Cat. No. 194L-HCA…

Cat. No. 194L-HCB…

Cat. No. 194L-HCD…

Dia. 30 (1-3/16)

L No. of Contacts Cat. No. 194L-C32/40...

1…2 86 (3-25/64)

3…4 103.5 (4-5/64)

5…6 121 (4-49/64)

7…8 138.5 (5-29/64)

9…10 156 (6-9/64)

Cat. No. 194L… for Front (Door) Installation

Cat. No. 194L-E 12/16…

Cat. No. 194L-E 20/25…

Mounting Dimensions

Cat. No. 194L-E 12/16… Cat. No. 194L-E 20/25… L No. of Contacts Cat. No.

1…2

3…4

5…6

7…8

9…10

194L-E12/16...

44 (1-47/64)

54 (2-1/8)

64 (2-33/64)

74 (2-29/32)

84 (3-5/16)

194L-E20/25...

44.5 (1-3/4)

57 (2-1/4)

69.5 (2-3/4)

82 (3-15/64)

94.5 (3-23/32)

194L-E32/40...

43 (1-11/16)

58.5 (2-5/16)

76 (2-63/64)

93.5 (3-11/16)

111 (4-3/8)

Control Knob Cat. No.

P

194L-HE4A...

48 (1-57/64) x 48 (1-57/64)

194L-HE4I... 194L-HE4S... 194L-HE6A...

48 (1-57/64) x 62 (2-7/16) 28 (1-7/64)

194L-HE6I... 194L-HE6S...

20

64 (2-33/64) x 64 (2-33/64) 64 (2-33/64) x 78 (3-5/64)

194L-HE6N... 194L-HE6G...

Q

34 (1-11/32)

Rockwell Automation Publication 194-TD002B-EN-P

67 (2-41/64) x 67 (2-41/64)

Page 21

Approximate Dimensions

194L Control and Load Switches

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Cat. No. 194L-A… for Base/DIN Rail Installation Cat. No. 194L-A 20/25… Dia. 3.3 (1/8)

Y Dimension Min. 2.5 (7/64)

Cat. No. 194L-A 12/16…

Max. 9.5 (3/8)

No. of Contacts Cat. No.

1…2

3…4

5…6

7…8

194L-A12/16...

58 (2-9/32)

68 (2-11/16)

78 (3-5/64)

88 (3-15/32)

194L-A20/25...

58 (2-9/32)

71.5 (2-13/16)

84 (3-5/16)

96.5 (3-51/64)

194L-A32/40...

67.5 (2-21/32)

85 (3-11/32)

102.5 (4-1/32)

120 (4-47/64)

Control Knob Cat. No.

P

B

194L-HE4A… 36 (1-27/64)

194L-HE4I… 194L-HE4S… 194L-HE6A…

64 (2-33/64) x 64 (2-33/64)

194L-HE6S… 194L-HE6G…

48 (1-57/64) x 48 (1-57/64) 48 (1-57/64) x 62 (2-7/16)

28 (1-7/64)

194L-HE6I… 194L-HE6N…

Q

48 (1-57/64) 34 (1-11/32)

64 (2-33/64) x 78 (3-5/64) 67 (2-41/64) x 67 (2-41/64)

With DIN 46 277 (35) Rail + 2.5 mm (7/64)

Rockwell Automation Publication 194-TD002B-EN-P

21

Page 22

194L Control and Load Switches

Approximate Dimensions

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Cat. No. 194L-A… With Shaft Extension Cat. No. 194L-G2853 Extensions

Dia. 3.3 (1.8)

No. of Contacts

Shaft Cat. No.

with No. of Extensions

Cat. No. 194L-A12/16... 10mm (0.39)

Cat. No. 194L-A20/25... 12.5mm (0.49)

Cat. No. 194L-A32/40

L No. of Contacts 1…2

3…4

5…6

7…8

1…2

3…4

5…6

7…8

1…2

3…4

5…6

7…8

With 1 extension

82 (3-15/64)

92 (3-5/8)

102 (4-1/64)

112 (4-13/32)

83 (3-17/64)

95.5 (3-49/64)

108 (4-1/4)

120.5 (4-3/4)

91.5 (3-15/64)

108 (4-1/4)

126.5 (5-63/64)

144 (6-43/64)

With 2 extensions

106 (4-11/64)

116 (4-37/64)

126 (4-31/32)

136 (5-23/64)

107 (4-7/32)

119.5 (4-45/64)

132 (5-13/64)

144.5 (5-11/16)

115.5 (5-35/64)

133 (5-15/64)

150.5 (6-5/16)

168 (7-5/8)

With 3 extensions

130 (5-1/8)

140 (5-33/64)

150 (5-29/32)

160 (6-19/64)

131 (5-5/32)

143.5 (5-21/32)

156 (6-9/64)

168.5 (6-5/8)

135.5 (5-11/32)

157 (6-3/16)

174.5 (7-7/8)

182 (8-9/16)

With 4 extensions

154 (6-1/16)

164 (6-15/32)

174 (6-55/64)

184 (7-15/64)

155 (6-7/64)

167.5 (6-19/32)

180 (7-3/32)

192.5 (7-37/64)

163.5 (6-7/16)

181 (7-1/8)

198.5 (8-53/64)

216 (9-33/64)

With 5 extensions

178 (7-1/64)

188 (7-13/32)

198 (7-51/64)

208 (8-3/16)

179 (7-3/64)

191.5 (7-35/64)

204 (8-1/32)

216.5 (8-33/64)

187.5 (7-3/8)

205 (8-5/64)

222.5 (9-49/64)

240 (9-29/64)

With 6 extensions

202 (7-61/64)

212 (8-23/64)

222 (8-3/4)

232 (9-1/8)

203 (7-63/64)

215.5 (8-31/64)

228 (8-63/64)

240.5 (9-15/32)

211.5 (8-21/64)

229 (12)

No. of Extensions

246.5 264 (10-23/32) (10-13/32)

Control Knob Cat. No. 194L-HE4A… 194L-HE4I… 194L-HE6A… 194L-HE6I… 194L-HE6N… 194L-HE6G…

Q

B

48 (1-57/64) x 48 (1-57/64)

36 (1-27/64)

64 (2-33/64) x 64 (2-33/64) 48 (1-57/64) 67 (2-41/64) x 67 (2-41/64)

When more than four modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853). ‡ Mounting on DIN 46 277 (35) Rails.

22

Rockwell Automation Publication 194-TD002B-EN-P

Page 23

Approximate Dimensions

194L Control and Load Switches

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Cat. No. 194L-A… With Metal Shafts

Cat. No.

A

194L-G3393…

110 (4-21/64)…235(9-1/4)

194L-G3394…

230 (9-1/16)…350 (13-25/32)

No. of Contacts Cat. No.

1…2

3…4

5…6

7…8

194L-A12/16...

54 (2-1/8)

64 (2-33/64)

74 (2-29/32)

84 (3-5/16)

194L-A20/25...

55 (2-11/64)

67.5 (2-21/32)

80 (3-5/32)

92.5 (3-41/64)

194L-A32/40...

63.5 (2-31/64)

81 (3-3/16)

88.5 (3-7/8)

116 (4-9/16)

Enclosure Mounting Depth§ No. of Extension Modules 0

1

2

3

4

5

6

Required End Shaft

Cat. No. 194L-A12/16…

Cat. No. 194L-A20/25…

44 (1-47/64) ♣

71.5…77.5 (2-13/16…3-1/16)

75…80.5 (2-61/64…3-11/64)

52 (2-3/64)

77…87 (3-1/32…3-27/64)

80…90 (3-5/32…3-35/64)

57 (2-1/4)

82…92 (3-15/64…3-5/8)

85…95 (3-11/32…3-3/4)

44 (1-47/64) ♣

95.5…101.5 (3-49/64…4)

99…105 (3-29/32…4-9/64)

52 (2-3/64)

97.5…111 (3-27/32…4-3/8)

101…114.5 (3-63/64…4-33/64)

57 (2-1/4)

102.5…116 (4-3/64…4-37/64)

106…119.5 (4-11/64…4-45/64)

44 (1-47/64) ♣

119.5…125.5 (4-45/64…4-61/64)

123…129 (4-27/32…5-5/64)

52 (2-3/64)

121.5…135 (4-51/64…5-5/16)

125…138.5 (4-59/64…5-29/64) 130…143.5 (5-1/8…5-21/32)

57 (2-1/4)

126.5…140 (4-63/64…5-33/64)

44 (1-47/64) ♣

143.5…149.5 (5-21/32…5-57/64)

147…153 (5-51/64…6-1/32)

52 (2-3/64)

145.5…159 (5-47/64…6-17/64)

149…162.5 (5-7/8…6-13/32) 154…167.5 (6-1/16…6-19/32)

57 (2-1/4)

150.5…164 (5-15/16…6-15/32)

44 (1-47/64) ♣

167.5…173.5 (6-19/32…6-27/32)

171…177 (6-47/64…6-31/32)

52 (2-3/64)

169.5…183 (6-43/64…7-13/64)

173…186.5 (6-13/16…7-11/32) 178…191.5 (7-1/64…7-35/64)

57 (2-1/4)

174.5…188 (6-7/8…7-13/32)

44 (1-47/64) ♣

191.5…197.5 (7-35/64…7-25/32)

195…201 (7-43/64…7-59/64)

52 (2-3/64)

193.5…207 (7-5/8…8-5/32)

197…210.5 (7-49/64…8-19/64) 202…215.5 (7-61/64…8-31/64)

57 (2-1/4)

198.5…212 (7-53/64…8-23/64)

44 (1-47/64) ♣

215.5…221.5 (8-31/64…8-23/32)

219…225 (8-5/8…8-55/64)

52 (2-3/64)

217.5…231 (8-37/64…9-3/32)

221…234.5 (8-45/64…9-15/64)

57 (2-1/4)

222.5…236 (8-49/64…9-19/64)

226…239.5 (8-29/32…9-7/16)

When more than 4 modules are used, attach the first one to the switch body using the screws supplied with the extension (Cat. No. 194L-G2853). § For DIN Rail-mounted devices, remember to deduct the offset distance provided by the rail. For example, deduct 2.5 mm (7/64 in.) from the mounting depth for Bulletin 194L switch body mounted on DIN 46277 rail. ♣ One 44 mm (1-47/64 in) end shaft is supplied with all Bulletin 194L Switch Bodies.

Rockwell Automation Publication 194-TD002B-EN-P

23

Page 24

194L Control and Load Switches

Approximate Dimensions

Modular Shaft Extensions (Cat. No. 194L-G2853) Select No. of Extension Modules and Shaft for use with enclosures. Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes. Cat. No. 194L-A… With Cat. No. 194L-HE4P-…

L

Installation on DIN 46277 (35 mm) Rails + 2.5 mm (7/64 in.)

No. of Contacts

Cat. No. 194L-E… With Terminal Cover

Cat. No. 194L-A… With Terminal Cover

24

Cat. No.

1…2

3…4

5…6

7…8

194L-A12/16...

35 (1-3/8)

45 (1-49/64)

55 (2-11/64)

65 (2-9/16)

194L-A20/25...

33.5 (1-21/64)

48 (1-57/64)

60.5 (2-3/8)

73 (2-7/8)

194L-A32/40...

43 (1-11/16)

61 (2-13/32)

79 (3-7/64)

97 (3-53/64)

Cat. No.

A

B

C

D

194L-E12/16…

40 (1-37/64)

42.5 (1-43/64)

12 (15/32)

2.5 (7/64)

194L-E20/25…

49 (1-15/16)

37.5 (1-31/64)

12 (15/32)

2.5 (7/64)

194L-E32/40…

59 (2-21/64)

50 (1-31/32)

15 (19/32)

2.5 (7/64)

Cat. No.

A

B

C

D

194L-A12/16…

40 (1-37/64)

42.5 (1-43/64)

12 (15/32)

2.5 (7/64)

194L-A20/25…

49 (1-15/16)

37.5 (1-31/64)

12 (15/32)

2.5 (7/64)

194L-A32/40…

63.5 (2-1/2)

49 (1-53/64)

12 (15/32)

2 (5/64)

Rockwell Automation Publication 194-TD002B-EN-P

Page 25

Approximate Dimensions

194L Control and Load Switches

Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.

Enclosure Cat. No. 194L-G3572…Cat. No. 194L-G3579

Cat. No. 194L-G3572/G3576 G3574/G3578

Cat. No. 194L-G3573/G3577 G3575/G3579

Rockwell Automation Publication 194-TD002B-EN-P

25

Page 26

Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication 194-TD002B-EN-P, May 2017 Supersedes Publication 194-TD002A, August 2014

Copyright © 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.