For the Allen-Bradley 20-COMM-C

Page 102

5-28

Using the I/O

PowerFlex 700S, PowerFlex 700L with 700S Control, PowerFlex 750-Series, and PowerFlex Digital DC Drives When using any of these drives, which contain both DINT (32-bit format) and REAL (floating point format) data types, you will always read from and write to the LSW data table address in the controller first. Then if the data value exceeds 16 bits, the remaining value will be in the MSW data table address. Table 5.L PLC-5 Data Table Addresses for PowerFlex 700S Drives (Phase I Control) Data Table Address N9:0 N9:1 N9:2 N9:3 N9:4 N9:5 N9:6 N9:7 N9:8 N9:9 N9:10 N9:11 N9:12 N9:13 N9:14 N9:15 N9:16 N9:17 N9:18 N9:19 N10:0 N10:1 N10:2 N10:3 N10:4 N10:5 N10:6 N10:7 N10:8 N10:9 N10:10 N10:11 N10:12 N10:13 N10:14 N10:15 N10:16 N10:17 N10:18 N10:19

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Description Logic Status (see Appendix D) Not Used Speed Feedback LSW Speed Feedback MSW Value of parameter assigned to Parameter 724/725 [Data Out A1] LSW Value of parameter assigned to Parameter 724/725 [Data Out A1] MSW Value of parameter assigned to Parameter 726/727 [Data Out A2] LSW Value of parameter assigned to Parameter 726/727 [Data Out A2] MSW Value of parameter assigned to Parameter 728/729 [Data Out B1] LSW Value of parameter assigned to Parameter 728/729 [Data Out B1] MSW Value of parameter assigned to Parameter 730/731 [Data Out B2] LSW Value of parameter assigned to Parameter 730/731 [Data Out B2] MSW Value of parameter assigned to Parameter 732/733 [Data Out C1] LSW Value of parameter assigned to Parameter 732/733 [Data Out C1] MSW Value of parameter assigned to Parameter 734/735 [Data Out C2] LSW Value of parameter assigned to Parameter 734/735 [Data Out C2] MSW Value of parameter assigned to Parameter 736/737 [Data Out D1] LSW Value of parameter assigned to Parameter 736/737 [Data Out D1] MSW Value of parameter assigned to Parameter 738/739 [Data Out D2] LSW Value of parameter assigned to Parameter 738/739 [Data Out D2] MSW Logic Command (see Appendix D) Not Used Speed Reference LSW Speed Reference MSW Value of parameter assigned to Parameter 707/708 [Data In A1] LSW Value of parameter assigned to Parameter 707/708 [Data In A1] MSW Value of parameter assigned to Parameter 709/710 [Data In A2] LSW Value of parameter assigned to Parameter 709/710 [Data In A2] MSW Value of parameter assigned to Parameter 711/712 [Data In B1] LSW Value of parameter assigned to Parameter 711/712 [Data In B1] MSW Value of parameter assigned to Parameter 713/714 [Data In B2] LSW Value of parameter assigned to Parameter 713/714 [Data In B2] MSW Value of parameter assigned to Parameter 715/716 [Data In C1] LSW Value of parameter assigned to Parameter 715/716 [Data In C1] MSW Value of parameter assigned to Parameter 717/718 [Data In C2] LSW Value of parameter assigned to Parameter 717/718 [Data In C2] MSW Value of parameter assigned to Parameter 719/720 [Data In D1] LSW Value of parameter assigned to Parameter 719/720 [Data In D1] MSW Value of parameter assigned to Parameter 721/722 [Data In D2] LSW Value of parameter assigned to Parameter 721/722 [Data In D2] MSW

Page 103

Using the I/O

5-29

Table 5.M PLC-5 Data Table Addresses for: PowerFlex 700S Drives with Phase II Control PowerFlex 700L Drives with 700S Control Data Table Address N9:0 N9:1 N9:2 N9:3 N9:4 N9:5 N9:6 N9:7 N9:8 N9:9 N9:10 N9:11 N9:12 N9:13 N9:14 N9:15 N9:16 N9:17 N9:18 N9:19 N10:0 N10:1 N10:2 N10:3 N10:4 N10:5 N10:6 N10:7 N10:8 N10:9 N10:10 N10:11 N10:12 N10:13 N10:14 N10:15 N10:16 N10:17 N10:18 N10:19

Description Logic Status (see Appendix D) Not Used Speed Feedback LSW Speed Feedback MSW Value of parameter assigned to Parameter 660 [DPI Data Out A1] LSW Value of parameter assigned to Parameter 660 [DPI Data Out A1] MSW Value of parameter assigned to Parameter 661 [DPI Data Out A2] LSW Value of parameter assigned to Parameter 661 [DPI Data Out A2] MSW Value of parameter assigned to Parameter 662 [DPI Data Out B1] LSW Value of parameter assigned to Parameter 662 [DPI Data Out B1] MSW Value of parameter assigned to Parameter 663 [DPI Data Out B2] LSW Value of parameter assigned to Parameter 663 [DPI Data Out B2] MSW Value of parameter assigned to Parameter 664 [DPI Data Out C1] LSW Value of parameter assigned to Parameter 664 [DPI Data Out C1] MSW Value of parameter assigned to Parameter 665 [DPI Data Out C2] LSW Value of parameter assigned to Parameter 665 [DPI Data Out C2] MSW Value of parameter assigned to Parameter 666 [DPI Data Out D1] LSW Value of parameter assigned to Parameter 666 [DPI Data Out D1] MSW Value of parameter assigned to Parameter 667 [DPI Data Out D2] LSW Value of parameter assigned to Parameter 667 [DPI Data Out D2] MSW Logic Command (see Appendix D) Not Used Speed Reference LSW Speed Reference MSW Value of parameter assigned to Parameter 651 [DPI Data In A1] LSW Value of parameter assigned to Parameter 651 [DPI Data In A1] MSW Value of parameter assigned to Parameter 652 [DPI Data In A2] LSW Value of parameter assigned to Parameter 652 [DPI Data In A2] MSW Value of parameter assigned to Parameter 653 [DPI Data In B1] LSW Value of parameter assigned to Parameter 653 [DPI Data In B1] MSW Value of parameter assigned to Parameter 654 [DPI Data In B2] LSW Value of parameter assigned to Parameter 654 [DPI Data In B2] MSW Value of parameter assigned to Parameter 655 [DPI Data In C1] LSW Value of parameter assigned to Parameter 655 [DPI Data In C1] MSW Value of parameter assigned to Parameter 656 [DPI Data In C2] LSW Value of parameter assigned to Parameter 656 [DPI Data In C2] MSW Value of parameter assigned to Parameter 657 [DPI Data In D1] LSW Value of parameter assigned to Parameter 657 [DPI Data In D1] MSW Value of parameter assigned to Parameter 658 [DPI Data In D2] LSW Value of parameter assigned to Parameter 658 [DPI Data In D2] MSW

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 104

5-30

Using the I/O

Table 5.N PLC-5 Data Table Addresses for PowerFlex 750-Series Drives Data Table Address N9:0 N9:1 N9:2 N9:3 N9:4 N9:5 N9:6 N9:7 N9:8 N9:9 N9:10 N9:11 N9:12 N9:13 N9:14 N9:15 N9:16 N9:17 N9:18 N9:19 N10:0 N10:1 N10:2 N10:3 N10:4 N10:5 N10:6 N10:7 N10:8 N10:9 N10:10 N10:11 N10:12 N10:13 N10:14 N10:15 N10:16 N10:17 N10:18 N10:19

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Description Logic Status (see Appendix D) Not Used Speed Feedback LSW Speed Feedback MSW Value of parameter assigned to Parameter 905 [Data Out A1] LSW Value of parameter assigned to Parameter 905 [Data Out A1] MSW Value of parameter assigned to Parameter 906 [Data Out A2] LSW Value of parameter assigned to Parameter 906 [Data Out A2] MSW Value of parameter assigned to Parameter 907 [Data Out B1] LSW Value of parameter assigned to Parameter 907 [Data Out B1] MSW Value of parameter assigned to Parameter 908 [Data Out B2] LSW Value of parameter assigned to Parameter 908 [Data Out B2] MSW Value of parameter assigned to Parameter 909 [Data Out C1] LSW Value of parameter assigned to Parameter 909 [Data Out C1] MSW Value of parameter assigned to Parameter 910 [Data Out C2] LSW Value of parameter assigned to Parameter 910 [Data Out C2] MSW Value of parameter assigned to Parameter 911 [Data Out D1] LSW Value of parameter assigned to Parameter 911 [Data Out D1] MSW Value of parameter assigned to Parameter 912 [Data Out D2] LSW Value of parameter assigned to Parameter 912 [Data Out D2] MSW Logic Command (see Appendix D) Not Used Speed Reference LSW Speed Reference MSW Value of parameter assigned to Parameter 895 [Data In A1] LSW Value of parameter assigned to Parameter 895 [Data In A1] MSW Value of parameter assigned to Parameter 896 [Data In A2] LSW Value of parameter assigned to Parameter 896 [Data In A2] MSW Value of parameter assigned to Parameter 897 [Data In B1] LSW Value of parameter assigned to Parameter 897 [Data In B1] MSW Value of parameter assigned to Parameter 898 [Data In B2] LSW Value of parameter assigned to Parameter 898 [Data In B2] MSW Value of parameter assigned to Parameter 899 [Data In C1] LSW Value of parameter assigned to Parameter 899 [Data In C1] MSW Value of parameter assigned to Parameter 900 [Data In C2] LSW Value of parameter assigned to Parameter 900 [Data In C2] MSW Value of parameter assigned to Parameter 901 [Data In D1] LSW Value of parameter assigned to Parameter 901 [Data In D1] MSW Value of parameter assigned to Parameter 902 [Data In D2] LSW Value of parameter assigned to Parameter 902 [Data In D2] MSW

Page 105

Using the I/O

5-31

Table 5.O PLC-5 Data Table Addresses for PowerFlex Digital DC Drives Data Table Address N9:0 N9:1 N9:2 N9:3 N9:4 N9:5 N9:6 N9:7 N9:8 N9:9 N9:10 N9:11 N9:12 N9:13 N9:14 N9:15 N9:16 N9:17 N10:0 N10:1 N10:2 N10:3 N10:4 N10:5 N10:6 N10:7 N10:8 N10:9 N10:10 N10:11 N10:12 N10:13 N10:14 N10:15 N10:16 N10:17

Description Logic Status (see Appendix D) Speed Feedback Value of parameter assigned to Parameter 618 [Data Out A1] LSW Value of parameter assigned to Parameter 618 [Data Out A1] MSW Value of parameter assigned to Parameter 619 [Data Out A2] LSW Value of parameter assigned to Parameter 619 [Data Out A2] MSW Value of parameter assigned to Parameter 620 [Data Out B1] LSW Value of parameter assigned to Parameter 620 [Data Out B1] MSW Value of parameter assigned to Parameter 621 [Data Out B2] LSW Value of parameter assigned to Parameter 621 [Data Out B2] MSW Value of parameter assigned to Parameter 622 [Data Out C1] LSW Value of parameter assigned to Parameter 622 [Data Out C1] MSW Value of parameter assigned to Parameter 623 [Data Out C2] LSW Value of parameter assigned to Parameter 623 [Data Out C2] MSW Value of parameter assigned to Parameter 624 [Data Out D1] LSW Value of parameter assigned to Parameter 624 [Data Out D1] MSW Value of parameter assigned to Parameter 625 [Data Out D2] LSW Value of parameter assigned to Parameter 625 [Data Out D2] MSW Logic Command (see Appendix D) Speed Reference Value of parameter assigned to Parameter 610 [Data In A1] LSW Value of parameter assigned to Parameter 610 [Data In A1] MSW Value of parameter assigned to Parameter 611 [Data In A2] LSW Value of parameter assigned to Parameter 611 [Data In A2] MSW Value of parameter assigned to Parameter 612 [Data In B1] LSW Value of parameter assigned to Parameter 612 [Data In B1] MSW Value of parameter assigned to Parameter 613 [Data In B2] LSW Value of parameter assigned to Parameter 613 [Data In B2] MSW Value of parameter assigned to Parameter 614 [Data In C1] LSW Value of parameter assigned to Parameter 614 [Data In C1] MSW Value of parameter assigned to Parameter 615 [Data In C2] LSW Value of parameter assigned to Parameter 615 [Data In C2] MSW Value of parameter assigned to Parameter 616 [Data In D1] LSW Value of parameter assigned to Parameter 616 [Data In D1] MSW Value of parameter assigned to Parameter 617 [Data In D2] LSW Value of parameter assigned to Parameter 617 [Data In D2] MSW

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 106

5-32

Using the I/O

With any drive, you can use the controller data table addresses to directly control and monitor the drive without creating any ladder logic program. However, if you intend to use Human Machine Interface devices (PanelView, and so forth) to operate the drive and view its status, you will need to create descriptive controller data table addresses (Table 5.P and Table 5.Q) and a ladder logic program that will pass that data to the data table addresses used for messaging. Table 5.P PLC-5 and Program Data Table Address Descriptions for Example Logic Status/Feedback Ladder Logic Program Description

PLC-5 Data Table Address

Description

Program Data Table Address

Drive Ready

N9:0/0

Status Ready

B3:1/0

Drive Active

N9:0/1

Status Active

B3:1/1

Actual Direction (XIO)

N9:0/3

Status Forward

B3:1/3

Actual Direction (XIC)

N9:0/3

Status Reverse

B3:1/4

Drive Faulted

N9:0/7

Status Faulted

B3:1/7

Drive At Speed

N9:0/8

Status At Speed

B3:1/8

Speed Feedback (PowerFlex 70) N9:1 (PowerFlex 753/755) N9:2

Speed Feedback (PowerFlex 70) N20:1 (PowerFlex 753/755) F8:1

Table 5.Q Program and PLC-5 Data Table Address Descriptions for Example Logic Command/Reference Ladder Logic Program Description

Program Data Table Address

Description

PLC-5 Data Table Address

Command Stop

B3:20/0

Drive Stop

N10:0/0

Command Start

B3:20/1

Drive Start

N10:0/1

Command Jog

B3:20/2

Drive Jog

N10:0/2

Command Clear Faults

B3:20/3

Drive Clear Faults

N10:0/3

Command Forward Reverse (XIO)

B3:20/4

Drive Forward

N10:0/4

Command Forward Reverse (XIC)

B3:20/4

Drive Reverse

N10:0/5

Speed Reference (PowerFlex 70) N30:1 (PowerFlex 753/755) F8:3

Speed Reference (PowerFlex 70) N10:1 (PowerFlex 753/755) N10:2

An example ladder logic program that uses these descriptive controller data table addresses and passes their data to the descriptive program data table addresses is shown in Figure 5.13, Figure 5.14, Figure 5.15, and Figure 5.16.

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 107

Using the I/O

5-33

Figure 5.13 PLC-5 Example Ladder Logic Program for Logic Status

PowerFlex 70 and PowerFlex 750-Series Drives

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 108

5-34

Using the I/O

Figure 5.14 PLC-5 Example Ladder Logic Program for Speed Feedback

PowerFlex 70 Drive Speed Feedback

PowerFlex 750-Series Drive Speed Feedback

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 109

Using the I/O

5-35

Depending on the drive being used, see one of the following subsections for information on speed Reference and Feedback scaling. Subsection

Page

PowerFlex 70/700/700H and PowerFlex 700L Drives with 700 Control

5-9

PowerFlex 700S and PowerFlex 700L Drives with 700S Control

5-10

PowerFlex 753/755 Drives

5-10

PowerFlex Digital DC Drives

5-11

Figure 5.15 PLC-5 Example Ladder Logic Program for Logic Command

PowerFlex 70 and PowerFlex 750-Series Drives

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P

Page 110

5-36

Using the I/O

Figure 5.16 PLC-5 Example Ladder Logic Program for Speed Reference PowerFlex 70 Drive Speed Reference

PowerFlex 750-Series Drive Speed Reference

(Continued on next page.)

20-COMM-C/Q ControlNet Adapter User Manual Publication 20COMM-UM003F-EN-P